3. Choose Zone Type which could be:
a) [
Not Used
] - switches off unwanted card zones
b) [
Manifold
] - sets the zone to a slower response curve
c) [
Probe
] - sets the zone to a faster response curve
d) [
Monitor
] – allows you to set any control zone from any card, as a
monitor zone only with no control function
e) [
Special
] - available if Auto-Detect sees that a Quad IO card is fitted
4. Choose any header color if the default selection is not required.
5.6
Preconfigured Setup Values
Table 5-2 shows the whole setup chart and the pre-configured values that
are given to probe and manifold zones. These values may be changed to suit
each tool.
Table 5-2
Pre-Configured Setup Values
Parameter
Probe and
Manifold Cards
Other Monitoring
Cards
Alarm Hi and Lo
25ºC or 45ºF
25ºC or 45ºF
Alias
blank
blank
Analogue Input
blank
20 lt / min flow
Display Group
1
blank
Master Zone
blank
blank
Max Power Setting
80%
blank
Max Setpoint Setting
350ºC or 662ºF 350ºC or 662ºF
Min Setpoint Setting
0ºC
blank
Rack Position
slot address
slot address
Sensor
J-type
blank
Shutdown Stage
off
off
Speed
Auto
blank
Standby and Boost
0ºC or 0ºF
blank
Startup Stage
off
off
T/C Offset Value
0ºC or 0ºF
blank
T/C Open Mode
Normal
blank
Triac
On-board
blank
Warn Hi and Lo
5ºC or 9ºF
blank
Set Zone Types - continued
5-5
SETUP
© 2021 Mold-Masters (2007) Limited. All Rights Reserved.
M1 Plus Controller User Manual