Diagnostics for the local XI/
ON-BUS and the PROFIBUS-DP /
CANopen bus
07/04 AWB2700-1428GB
54
Diagnostics for the local XI/ON-BUS and the PROFIBUS-DP/
CANopen bus
For the local XI/ON bus or the PROFIBUS-DP bus: EXTENDEDINFO
contains general diagnostic data for the participants and the
diagnostic structure specified in the PROFIBUS-DP standard, with
six standard diagnostic bytes and the following manufacturer-
specific diagnostic data, as described on the device documentation
and the corresponding GSD file.
In the following description, the most important data have a grey
background.
EXTENDEDINFO[0]
// for PROFIBUS-DP: Slave address
EXTENDEDINFO[1..4]
// No significance
EXTENDEDINFO[5]
// Length byte for the device diagnosis
EXTENDEDINFO[6&7]
// No significance
EXTENDEDINFO[8..13]
// 6 octets of DP standard diagnosis
according to the standard
EXTENDEDINFO[8]
// Status_1
Bit 0:
Device does not respond (no
valid IO-data)
Bit 1:
Slave not ready
Bit 2:
Configuration discrepancy
Bit 3:
Extended diagnosis is
available
Bit 4:
Unknown command
Bit 5:
Invalid response
Bit 6:
Parameterization incomplete
Bit 7:
Parameterization from a
different master
EXTENDEDINFO[9]
// Status_2
Bit 0:
Ready for new start-up
sequence
Bit 1:
No parameterization
Bit 2:
„1“
Bit 3:
Watchdog activated
Bit 4:
FREEZE command active
Bit 5:
SYNC command active
Bit 6:
Reserved
Bit 7:
Slave not incorporated in
project
EXTENDEDINFO[10]
// No significance
EXTENDEDINFO[11]
// With PROFIBUS-DP: master address
EXTENDEDINFO[12&13]
// Own ID number
EXTENDEDINFO[14]
// Length byte for the manufacturer-specific
data
EXTENDEDINFO[15..99]
// Free for manufacturer-specific diagnosis.
2 bytes are available for local and remote
XI/ON modules, to hold general messages.
The messages are derived from the GSD file
for the local XI/ON and the remote XI/ON
Gateway. They are Bytes 15 and 16 of the
EXTENDEDINFO output. The next byte
(EXTENDEDINFO[17..max. 99]) contains
the error code for the modules with
diagnostic capability. This is performed in
the sequence of the modules. There is no
byte for modules without a diagnostic
capability.
EXTENDEDINFO[15]
// Bit 0:
Module diagnosis available
Bit 2:
Parameterization incomplete
Bit 3:
Configuration discrepancy
EXTENDEDINFO[16]
// Bit 1:
Field voltage error
(only for local XI/ON)
Bit 2:
Module bus error
Bit 3:
Master configuration error
Bit 4:
No module detected
(only for local XI/ON)
Bit 5:
Station configuration error
Bit 6:
I/O assistant force mode
active
Bit 7:
Module bus failure
EXTENDEDINFO[17...99]
//One or more bytes for each module with
diagnostic capability
from
EXTENDEDINFO[17]
//Diagnosis bytes for the modules with
diagnostic capability (
a
following table;
additional information can be found in the
XI/ON PROFIBUS-DP manual
(AWB2700-1394GB).
Example: power supply module
XN-BR-24VDC-D
Bit 0:
Module bus voltage warning
Bit 2:
Field voltage missing
XN-PF-24VDC-D
Bit 2:
Field voltage missing
XN-PF-120/230VAC-D
Bit 2:
Field voltage missing
Example: output modules
XN-2DO-24VDC-0.5A-P
XN-2DO-24VDC-2A-P
XN-2DO-24VDC-0.5A-N
XN-16DO-24VDC-0.5A-P
Bit 0:
Overcurrent, channel 1
Bit 1:
Overcurrent, channel 2
Example: analog module