07/04 AWB2700-1428GB
General messages
41
Event message
Events are written with the time and date for additional
information.
Events include:
The events are displayed through the menu ‹DIAGNOSTICS
r
EVENTS›. You can look at the individual messages in the list by
turning the MSS.
As soon as you call up the EVENT menu, the exclamation mark is
deleted. All event messages will be deleted by using the menu
item CLEAR in the diagnostics menu.
General messages
Deleting programs from the hard disk
Requirement: a bootable version of the program is on the hard
disk.
X
Use the MSS to choose MAIN MENU
r
PROGRAM
r
INTERNAL
r
DELETE.
The name of the program will appear.
X
Press the MSS.
X
Turn the MSS so that the text ENTER appears instead of menu
item BACK.
X
Press the MSS.
The higher-level menu appears, and the bootable program is
deleted. But there is still an executable version of this program in
the working memory that is not deleted by this procedure. If the
OMS is set to RUN-P, this indicates that the (executable) program
is still running. The program can only be deleted via a Reset
(HARD/Original).
Deleting programs from the working memory
The program can be deleted by means of a Reset (HARD/Original),
a
following section.
Reset function (initialisation of variables)
The function can be executed via XSoft as well as via the operator
module.
Executing Reset via XSoft
The Reset function can be executed in three different ways via the
XSoft Online menu or via the operator module of the XC600:
Method 1:
This function initialises the simple variables and POU variables.
The variable assigned with RETAIN will be retained. The PLC is
switched from RUN to STOP status.
Method 2:
This function initialises the simple variables and POU variables as
well as those variables that have been declared with RETAIN.
The PLC is switched from RUN to STOP status.
Method 3:
After this function has been executed, the STOP LED will light up.
The executable program has been deleted, the bootable program
is retained, but it has been deactivated. When you restart the PLC,
the display will show “PROG:???” (no program). You have to
switch the supply voltage off and on again to restart a program via
XSoft or to reactivate a saved and bootable program. As an
alternative, you can also use the REBOOT or LOAD function. The
OMS must be set to RUN (-P).
Executing RESET on the operator module
X
Turn and press the MSS to choose MAIN MENU
r
PROGRAM
r
RESET.
X
Select either WARM, COLD or HARD.
The subsequent NO/YES prompt can also be changed by turning
the MSS. Pressing the MSS will call up the ENTER? prompt.
Pressing it once more will execute the Reset.
System
Start program or Stop program
XI/ON modules
XION Diag extended – an error has occurred, e.g.
short-circuit of an output, that is displayed via the
extended diagnostics.
XI/ON param conf failed – the set configuration
does not match the actual configuration
PROG: ???
There is no executable program in the PLC.
Attention
no signal
System error. The power supply in the PLC must be
switched off and on again.
XSoft
XC600 operator module
Reset
RESET WARM
XSoft
XC600 operator module
Reset (cold)
RESET COLD
XSoft
XC600 operator module
Reset (original)
RESET HARD