Functions of the Operator
Module
07/04 AWB2700-1428GB
40
Display programs on the hard disk (internal) and on the
CompactFlash card (external)
After choosing the DISPLAY menu item you can view the content
of the hard disk and the CompactFlash card:
X
Use the MSS on the operator module to choose MAIN MENU
r
PROGRAM
r
INTERNAL (or EXTERNAL)
r
DISPLAY.
The name of the program will appear. The large full-stop character
in front of the name indicates that an executable version of this
program is also present in the working memory.
Startup with configuration scan
On startup, the PLC system always scans the modules which
comprise the PLC. If the configuration does not change, for
example, after commissioning has been completed, the
configuration can be “frozen” for diagnostic tasks.
To do this, disable the AUTOCONFIG function:
X
Choose MAIN MENU
r
DEVICE
r
HARDWARE
r
AUTOCONFIG.
The cursor will be positioned at ON:
X
Turn the MSS until the display shows OFF.
X
Press the MSS. The word ENTER will appear on the display.
X
Press the MSS to return to the menu.
This function can be reactivated at any time.
The next time that the PLC is started up, the PLC will detect if any
modules are missing or faulty. This will be indicated by the SF LED
being lit up.
The following error text will appear in the DIAGNOSTICS
r
ERROR
menu:
The number 1 in the designation XC-NET-1 indicates the module:
Error and event messages
Error messages
In the event of an error, the SF LED will light up and ! will appear
in the display. Display shows “!”.
The following errors will cause an error message to be output:
The type of error, with date and time, is displayed in the
Diagnostics menu under ERROR.
The error message can be deleted as described below, together
with the event messages:
X
Choose menu item MAIN MENU
r
DIAGNOSTICS
r
CLEAR.
The display shows:
X
Turn the MSS until NO is replaced by YES.
X
Press the MSS.
X
Turn the MSS: BACK will be replaced with ENTER.
X
Press the MSS to reach the next higher menu.
h
Only bootable programs are displayed!
AUTOCONFIG:
ON
BACK
05.12_15:32
XC-NET-1
NOT DETECTED
BACK
Number
(Hardware) address of the module
0
CE000
1
CC000
2
D4000
From the system
PROG: ??? – No program loaded. Other
system errors are listed in the Appendix
From the operator
module
Battery discharged – Battery is empty or not
present
From local
XI/ON modules
XION not detected
h
Other error messages are explained in the Appendix.
h
The message will be retained if the error is still present.
15:21:10 !P
RUN-P
SAWING.PRO
>MAIN MENU
CLEAR:
NO
BACK