Functions of the Operator
Module
07/04 AWB2700-1428GB
44
Displaying text from the user program
The SENDSTRINGTODISPLAY function allows you to define texts (3
x
12 characters) in the user program that can be shown in the first
three lines of the display when the function is called.
The function must always be selected via the menu:
X
For this, turn the MSS in the basic menu until menu item
DISPLAY is shown.
X
Press the MSS to delete the display in STOP mode, or show the
text in RUN mode.
Use BACK to return to the basic menu.
Example program in IL:
Shutting down the system
X
Use the MSS to choose MAIN MENU
r
SYSTEM
r
SHUTDOWN
and press the MSS.
The cursor is positioned on the ENTER menu item.
X
Press the MSS to execute the function.
The STOP LED will go out. The display shows:
/
is a symbol. It keeps turning as long as the function is in progress.
Once the function has been completed, the following message will
appear:
X
Switch off the power supply.
Switching off the power supply
Switching off the power supply of the UPS device will cause the
Power Supply contact to open. The contact will break the PFI loop
on the XC600 controller, which causes the system to shut down.
Depending on the operating status, the RUN or STOP LED will go
out.
The display shows:
/
is a symbol. It keeps turning as long as the function is in progress.
The UPS device will switch off the power supply after two minutes.
LD 'Hello World'
SendStringToDisplay
SHUTDOWN
IN PROGRESS
/
TURN OFF
YOUR
CONTROLLER
PFI SHUTDOWN
IN PROGRESS
/
Summary of Contents for XControl XC600
Page 4: ...II...
Page 8: ...07 04 AWB2700 1428GB 4...
Page 30: ...07 04 AWB2700 1428GB 26...
Page 40: ...07 04 AWB2700 1428GB 36...
Page 74: ...07 04 AWB2700 1428GB 70...
Page 78: ...07 04 AWB2700 1428GB 74...