Service manual
Continuation frequency controller description
Functional test
The three control lines on the control connection terminal are wired according to the following table,
whereby status „1“ means 230V. This can be measured and compared to ”N”.
D2 D1
D0
Function
0
0
0
Fan motor is not running
0
1
0
Right direction
0
0
1
Left direction
The output voltage on the motor outlet terminal is 230V 60Hz when in use.
When turned on, this function can also be controlled with the green LED which is on the controller.
LED status
Description
Steps to take.
On
Frequency converter is working perfectly -
Off
Frequency converter is not working
Control input voltage if
necessary replace
frequency converter.
3 flashes/period
Overheating of frequency converter.
Test fan function, if
necessary replace
frequency converter.
6 flashes /period
Short circuit in motor
Test motor, replace if
necessary.
7 flashes/period
Frequency converter does not start
Jumper J1 is configured
incorrectly.
29