Chapter 6
70
Mounting/Dismantling
6
Mounting/Dismantling
This chapter describes the mounting of the modules of the MELSEC-WS safety
controller.
6.1
Steps for mounting the modules
The MELSEC-WS safety controller must be mounted in a control cabinet with
at least IP 54 enclosure rating!
In a MELSEC-WS safety controller, the WS0-CPU0, WS0-CPU1 or WS0-CPU3 is
positioned at the far left.
The two optional network modules follow directly to the right of the CPU module.
Connect further MELSEC-WS safety I/O modules (e.g. WS0-XTIO or WS0-XTDI)
on the right side of the network modules or on the right side of the CPU module, if
no network module is used. The I/O modules can be mounted in any order.
Connect an additional safety relay output module (WS0-4RO) on the far right of
the entire MELSEC-WS safety controller.
The modules are located in a 22.5 mm wide modular system for 35 mm DIN
mounting rails to IEC/EN 60715.
The modules are connected to each other via the
plug connection
integrated in the housing. Take into account that, when replacing a module, the
MELSEC-WS modules have to be pushed approx. 10 mm apart before the
corresponding module can be removed from the DIN mounting rail.
Mount the modules in accordance with EN 50274.
Ensure that suitable ESD protective measures are taken during mounting.
Otherwise the backplane bus may be damaged.
Take suitable measures to ensure that foreign matter does not enter the
connector openings, in particular that of the memory plug.
ATTENTION