Chapter 12
102
Technical data
Power supply unit (A1, A2)
Supply voltage
24 V DC (16.8 V DC … 30 V DC)
Supply voltage
UL/CSA applications
24 V DC
Type of supply voltage
PELV or SELV
The current of the power supply unit for the module
has to be limited to a maximum of 4 A – either by the
power supply unit itself or by a fuse.
Power consumption
Max. 120 W (30 V × 4 A), determined by the load at
the outputs Q1 to Q4, plus max. 1 W power input for
the internal circuit
Switch-on time
Max. 18 s
Short-circuit protection
4 A gG (with tripping characteristic B or C)
Input circuit (I1 … I8)
Input voltage High
13 … 30 V DC
Input voltage Low
–5 … +5 V DC
Input current High
2.4 … 3.8 mA
Input current Low
–2.5 … 2.1 mA
Input reverse current in case of
ground interruption
*3
Hardware version < V1.10.1
Max. 20 mA
1.5 k
Ω
effective reverse resistance to power supply
Hardware version
≥
V1.10.1
Max. 2 mA
Switching current (with
mechanical contacts)
14.4 mA at 5 V
3 mA at 24 V
Input pulse filtering (pulses within
these limits have no effect)
Pulse width
Max. 0.9 ms
Pulse period
Min. 4 ms
Input capacitance
Max. 10 nF + 10 %
Discrepancy times
4 ms … 30 s, configurable
Number of inputs
8
*3 Do not switch other safe inputs in parallel, if the reverse current could lead to a High state at the