Chapter 10
82
Diagnostics
LED indication on module
Possible error
codes
Possible reasons
Possible measures
CPU module
(WS0-CPU0, WS0-
CPU1 or WS0-CPU3)
Safety I/O module
(WS0-XTIO or
WS0-XTDI)
MS =
Red (1 Hz)
EFI =
Red (1 Hz)
One or more safety I/O
modules:
MS =
Red (1 Hz)
(firmware
≥
V2.00.0)
or
MS =
Red/green
(1 Hz) (firmware
V1.xx.0)
CPU module:
0x0014000A
If WS0-CPU1: EFI device address
conflict:
There are at least 2 CPU modules
with the same EFI address
connected.
Change the EFI device address
with Setting and Monitoring Tool,
either of the CPU module or of the
connected device.
CPU module:
0x0015000A
If WS0-CPU1 and Flexi Link: Wrong
Flexi Link ID:
EFI1 and EFI2 is swapped in the
wiring.
There is at least 1 CPU module
with a different Flexi Link ID
connected.
Check wiring between the Flexi Link
stations: EFI1 connected with EFI1,
and if applies EFI2 with EFI2.
Connect Flexi Link stations with
matching Flexi Link IDs.
Download configuration to all Flexi
Link stations with same Flexi Link
IDs.
CPU module:
0x001F0006,
0x00230006,
0x00234006,
0x001F4006
Configuration in memory plug is
incompatible for at least one safety I/O
module:
Wrong type or version of module
(whose MS LED is flashing red or
red/green).
Too many safety I/O modules are
connected (whose MS LED is
flashing red or red/green).
Safety I/O modules are missing
(MS LED of all other modules is
flashing red or red/green).
Download a configuration with the
same module type and the same or
a smaller firmware version for all
safety I/O modules.
Replace the affected safety I/O
module in the hardware installation
by a module with the same module
type and the same or smaller
firmware version as selected in the
project file.
MS =
Green (1 Hz)
CV =
Yellow (1
Hz)
MS =
Green (1 Hz)
--
System is in Stop state (ready to run).
Start application in Setting and
Monitoring Tool.
For automatic start after power up a
verification of the project is necessary
with Setting and Monitoring Tool.
MS =
Green (1 Hz)
CV =
Yellow
MS =
Green (1 Hz)
--
System is in Stop state (ready to run).
Start application in Setting and
Monitoring Tool.
MS =
Green
MS =
Green
--
System is in operation. No error
detected.
--
One or more safety I/O
modules :
MS =
Red/green
(1 Hz) (firmware
≥
V2.00.0)
or
MS =
Red (1 Hz)
(firmware V1.xx.0)
and
Q1+Q2+Q3+Q4 =
Green (1 Hz)
WS0-XTIO:
0x4804,
0x4806,
0x4807
Module power supply of WS0-XTIO is
too low or missing.
Check supply voltage at terminals A1
(24 V) and A2 (0 V) at the WS0-XTIO
module, also under worst case load
conditions.
Error is reset automatically after
approx. 8 seconds, if the error reason
no longer exists.