Chapter 10
84
Diagnostics
LED indication on module
Possible error
codes
Possible reasons
Possible measures
CPU module
(WS0-CPU0, WS0-
CPU1 or WS0-CPU3)
Safety I/O module
(WS0-XTIO or
WS0-XTDI)
MS =
Green
One or more safety
I/O modules :
MS =
Red/green
(1 Hz) (firmware
≥
V2.00.0)
or
MS =
Red (1 Hz)
(firmware V1.xx.0)
and
I1+I2 or I3+I4 or I5+I6
or I7+I8 =
Green (1 Hz)
WS0-XTIO/
WS0-XTDI:
0x4429 or
0x442A
Discrepancy error or sequence error at
dual channel inputs (whose LEDs are
flashing green):
*1
Cable interruption or short circuit to
0 V at one of both input signals of
the input pair.
Hardware failure of sensor, e.g. one
of both contacts/outputs is
permanently closed (High) or
opened (Low).
Defect sensor (one of both signals
does not change to the
corresponding state to the other
input within the configured
discrepancy time.
Opening or closing of safety door
was too slow so that the 2 contacts
switches (e.g. reed contacts) did not
switch within the configured
discrepancy time.
Only one of both inputs has caused
the switch off condition and has
changed back to the on condition,
without the other input having
changed at all (sequence error).
Check wiring of effected input and
check switching capability of both
contacts/outputs of the connected
sensor.
Check mechanical dependency of
both switches.
Replace switch/sensor in hardware
installation
To reset the error the effected input
pair has to be Low/Low for equivalent
dual channel inputs and Low/High for
complementary dual channel inputs.
MS =
Red
MS =
Red
CPU module:
0xXXXCXXXX.
Safety I/O
modules:
0xCXXX
(X= any value)
Power supply 0 V at WS0-XTIO
module missing (firmware V1.xx.0
only).
Internal error in safety I/O module.
Internal error in CPU module.
Check connection of terminal A2 of
WS0-XTIO modules to 0 V of
power supply.
Check installation for EMC
influence (earthing of DIN mounting
rail,…).
To reset the error power cycle the
CPU module.
If the error persists, then replace
modules.
MS =
Red
MS =
Red (2 Hz)
(with firmware
≥
V2.00.0)
CPU module:
0xXXXCXXXX.
Safety I/O
modules:
0xCXXX
(X= any value)
Internal error in safety I/O module
(whose MS LED is flashing).
Check installation for EMC
influence (earthing of DIN mounting
rail,…).
To reset the error power cycle the
CPU module
If the error persists, then replace
the module whose MS LED is
flashing.
MS =
Red (2 Hz)
(with firmware
≥
V2.01.0)
MS =
Red
CPU module:
0xXXXCXXXX.
Safety I/O
modules:
0xCXXX
(X= any value)
Internal error in CPU module or in the
system.
Check installation for EMC
influence (earthing of DIN mounting
rail,…).
To reset the error power cycle the
CPU module
If the error persists, then replace
subsequently CPU module and
safety I/O modules
Summary of Contents for MELSEC-WS series
Page 1: ...Safety Controller User s Manual WS0 CPU0 WS0 CPU1 WS0 CPU3 WS0 XTDI WS0 XTIO WS0 4RO ...
Page 2: ......
Page 117: ...Chapter 14 114 Annex ...
Page 134: ...Chapter 14 131 Annex ...
Page 151: ......