Chapter 12
101
Technical data
General data
Protection class
III (IEC 61140)
Enclosure rating
Terminals: IP 20 (IEC 60529)
Housing: IP 40 (IEC 60529)
Ambient temperature in operation
–25 … +55 °C
Storage temperature
–25 … +70 °C
Humidity
10 … 95 %, non-condensing
Climatic conditions
55 °C, 95 % relative. humidity (IEC 61131-2), No
corrosive gases
Vibration resistance
5-150 Hz/1 g (IEC 60068-2-6)
10-500 Hz/3 g RMS (EN 60068-2-64)
Shock resistance
Continuous shock
10 g, 16 ms (IEC 60068-2-27)
Single shock
30 g, 11 ms (IEC 60068-2-27)
Electromagnetic compatibility
Class A (IEC 61000-6-2, EN 55011)
System connection
Dual level spring clamp terminals
Power input via without
currents to X1, X2
Max. 2.2 W
Cross-section of connecting wires
Single-core or finely stranded:
0.2 … 1.5 mm
2
(24 to 15 AWG)
Finely stranded with ferrules:
0.25 … 1.5 mm
2
(23 to 15 AWG)
Data interface
Backplane bus ()
Dimensions (W × H × D)
22.5 × 106.5 × 120.8 mm
Weight
164 g (± 5%)