Chapter 12
97
Technical data
12.1.2
Min. switch off time
The minimum switch-off time (e.g. of connected sensors) is the minimum time for
which a switch-off condition must be present in order to be detected so that error-
free switching is possible. The min. switch-off time must be …
greater than the logic execution time + 1 ms, and
greater than the test gap + Long gap, if the input is connected to test output
X1…X8 and the test gap is > 1 ms, and
greater than the test period (i.e. the higher value of the two test outputs used) +
the max. Off-on delay, if safety mats or bumpers are used.
*1 Take the values from the Setting and Monitoring Tool report.