14.5 Example for the calculation of the response time
of Flexi Line
Calculation of the response time for a MELSEC-WS safety controller:
Flexi Line Station A
Logic execution time = 4ms
Flexi Line update rate = 2ms
Occurrence
In1: Digital inputs
Occurrence
Out2: Output to EFI device
General Tactile
sensor
0ms General Response
time
of
the
actuator (Robot response
time)
40.0ms
General Input
processing
time
6.5ms
When On/Off filter
8.0ms
– When Flexi Line
data are used
logic execution time
4.0ms
When X1 … X8 is connected
at the test output...
–
– General Output
processing
time
4.5ms
Total
Output
56.0ms
Occurrence
Output : Output to Flexi Line
Output to Flexi Line –
–
Total In1
6.5ms
Total Output
0ms
Evaluation1
1. Inputs
Response time of the considered input in
the signal path
In1
6.5ms
2. Logic
Response time of the logic
2 × logic execution time
8.0ms
Delay through logic application
–
3. Outputs
Response time of the considered output in
local
out2
56.0ms
Total response time (remote input to local output)
70.5ms
Evaluation2
1. Inputs
Response time of the considered input in
the signal path
In1
6.5ms
2. Logic
Response time of the logic
2 × logic execution time
8.0ms
Delay through logic application
–
3. Outputs
Response time of the Flexi Line output
Out2
0ms
Total response time (Response time of the Flexi Line output)
14.5ms
Figure 62:
Response times within a
MELSEC-WS safety
controller