18 - 4
18.2 List of Error Message/System Alarm
17
M
A
IN
TE
N
A
N
C
E AN
D
IN
SP
ECTIO
N
18
ERROR MESSA
GE
AND S
YSTEM
ALARM
APP
ENDICE
S
322
Dedicated device is out of range.
Confirm device range.
The monitored device No. is set out of the permissible range of the
targeted PLC CPU, or the data length for a device dedicated to 32 bits is
set other than 32 bits.
1. Set the device within the range that can be monitored by the monitored
PLC CPU and parameter settings.
2. AB: L device/ S7-200: HC device/ OMPON temperature controller: Set
the data length of C0, C1 and C3 devices to 32 bits.
330
Insufficient memory media
capacity.
Confirm M-card capacity.
Available memory of the memory card is insufficient.
Check the available memory of the memory card on the Drive Information
of GT Designer2.
GT Designer2 Version Basic Operation/Data Transfer Manual
Section8.4 Obtaining the Drive Information [GOT to PC]
331
Memory card not installed or M-
CARD switched OFF
The memory card is uninstalled or access switch is OFF in drive.
1. Install the memory card in the specified drive.
2. Turn ON the access switch.
332 Memory media is not formatted.
Memory card is not formatted or formatted incorrectly.
Format the memory card.
334
Memory media error.
Replace memory media.
Memory card is faulty.
Replace the memory card.
345
BCD/BIN conversion error.
Correct data
The BCD/BIN conversion disabled data is being displayed/input.
1. Change the device data to be displayed to the BCD value.
2. Correct the input value to the 4 digits integer.
351
Recipe file error.
Confirm content of recipe file.
The contents of the recipe file are not normal.
1. Confirm the contents of the recipe files in the memory card.
2. Reboot the GOT after deleting the recipe file in the memory card
(format).
352
Recipe file make error.
Reboot GOT after inserting
memory card.
Failed to generate recipe file.
Reboot the GOT after installing the memory card.
353
Unable to write Recipe file.
Confirm memory card is inserted.
Failed to write in the recipe file.
1. Confirm the contents of the memory card.
2. Do not pull out the memory card while recipe is operating.
354 Recipe file write error
Error occurred while writing in the recipe file.
Do not unplug the memory card while recipe is operating.
355 Recipe file read error
Error occurred while writing in the recipe file.
1. Do not unplug the memory card while recipe is operating.
2. Confirm the contents (device value) of the recipe file in the memory
card.
356
File system error occurred in
PLC.
Confirm file register.
Error occurred in the specified file register when executing the recipe
function by specifying the file register name.
1. Execute the recipe function again after confirming the file register
name.
2. Execute the recipe function again after formatting the PC memory in the
specified PLC CPU drive with GX Developer.
Error
code
Error message
Action
Summary of Contents for GOT1000 GT11