SA-COM Series
Push-typed Screwless Terminal Block for Power Common
User’s Guide
Thank you for purchasing product of SAMWON ACT.
Please check model of product that you purchase first, and read this manual prior to use it.
●
Caution for Safety
Caution
Case that results in serious damage in human body or equipment, and fire if user handles this equipment wrongly
Warning
Case that results in slight damage in human body or equipment, and fire if user handles this equipment wrongly
Caution
1. When machining and wiring the mounting hole, do not allow foreign matter such as dust or wire covering
to enter the connection terminal. Failure to do so may result in damage to the unit, heat, or ignition.
2. Be sure to shut off the power supply from the outside before mounting and wiring.
Warning
1. Use within the specified temperature range. (-10
℃
~ +50
℃
) Damage to the outer case may occur.
2. Use within the specified rated voltage and rated current range.
This may result in fire or damage to the product.
3. Read this user's guide which is attached to product, and check product's nominal, characteristics,
specification, wiring diagram and how to handle prior to use.
4. Please make sure to check the arrangement of the +,- when wiring.
It may be the cause of malfunction or damage of this equipment and user's.
※
The connection cable for PLC of various makers is provided by us. Please refer to the
catalogue or contact Head or branch office if you need more detail models and specifications.
●
Model Selection
●
Characteristics
●
Material
※
Be sure to use a ferrule or round type terminal when using a stranded wire.
●
Model Configuration
❶
Common dedicated Push Type 5.0mm pitch
European screwless terminal block
❷
No. of terminal Poles
❸
Common terminal configuration
SA-COM 20
❶
❷
❸
Model
No. of
Poles
Common terminal configuration
Dimensions
(W * D mm)
Mounting
method
SA-COM20
20
Upper row 10P(+)/ Lower row 10P(-) Common
57.5
✽
48.0
Screw
mounting/
DIN Rail
SA-COM20B
Left side row 10P(+)/ Right side row 10P(-) Common
SA-COM20D
40(20x2)
Upper terminal block 20P(+) / Lower terminal block 20P(-) Common
63.0
✽
56.2
DIN Rail
SA-COM40
40
Upper row 20P(+)/ Lower row 20P(-) Common
107.5
✽
48.0
Screw
mounting/
DIN Rail
SA-COM40B
Left side row 20P(+)/ Right side row 20P(-) Common
Rated voltage
125V AC / 24V DC
Rated current
10A (Total)
Insulation resistance
100
㏁
or above (DC 500V)
Dielectric strength
AC500V 1min
Applicable
wire
Single wire
0.5~1.5
㎟
Twisted wire
UL : 17~22AWG / IEC 1.0
㎟
Wire stripping length
8~9mm
Ambient temperature
-10
℃
~
+50
℃
(No condensation)
Terminal
PA66
Pin header
Copper, Tin plated
Wire guard
Stainless steel
Cover
Modified PPO
P.C.B
Epoxy 1.6t
●
Ferrule Selection
AWG/ (
㎟
)
DIN46228
Other
A(
㎜
)
B(
㎜
)
C(
㎜
)
20/0.5
White
White/Orange
10.0
1.3
3.2
18/0.75
Gray
Blue/White
10.0
1.5
3.4
17/1.0
Red
Red/Yellow
10.0
1.7
3.6
●
Method of removal wire
●
Appropriate tool
'ULYHU
When using a stranded wire,
use a ferrule or a round type
terminal. In case of a solid wire,
use it without crimping tool.
Insert into the terminal block
without using a separate tool.
When disconnecting the wires,
keep the disconnect button
pressed with the driver (- type)
and disconnect the wires.