No-load high-speed function setting mode
If the No-load judgment level is raised, the No-load high-speed operation will be smoothly
started (No-load high-speed operation can be started even if the load is heavier).
If the No-load high-speed function for lifting or lowering operation is disabled,
or
will flash.
If the upper limit for operation is not set, the No-load high-speed function will be disabled for
the lifting operation.
•
Overload stoppage function setting mode
The value set for the overload judgment level represents the target level. This value, therefore,
does not represent a physical quantity of the load.
The optimum overload judgment level depends on the model.
If the overload judgment level is raised, the overload stoppage function will not be easily
activated (a heavier load can be lifted because the overload stoppage function is not easily
activated).
If the power supply voltage is low, overload may be detected even if the applied load is 100%.
The optimum overload judgment level depends on the operation conditions (voltage,
temperature, etc.).
For this reason, after installing the host, change the set overload judgment level value.
If the overload judgment level is extremely raised, operation may be stopped due to overcurrent,
starting error, speed adjustment error, etc. before detecting overload.
Summary of Contents for UM 10t
Page 51: ... 47 Structural Drawing of Hoist Main Body 5t 10t PA00531 ...
Page 52: ... 48 Structural Drawing of Electric Traversing Unit Monorail Type 10t P288922 ...
Page 53: ... 49 Structural Drawing of Electric Traversing Unit Double rail type 5t PA00483 ...
Page 54: ... 50 Structural Drawing of Traversing Mortor Double rail type 10t P276926 ...
Page 55: ... 51 Structural Drawing of Hook Block 5t PG49975 ...
Page 56: ... 52 Structural Drawing of Hook Block 10t PG49976 ...