1. SPECIFICATIONS
INDOOR UNITS
1 - 50
HBC
I.HBC controller
1. SPECIFICATIONS
Model name
CMB-WP108V-G
Number of branch
8
Power source
220-230-240 V
50 Hz
60 Hz
Power input
Cooling
kW
0.450/0.460/0.470
0.450/0.460/0.470
(220/230/240) Heating
kW
0.450/0.460/0.470
0.450/0.460/0.470
Current input
Cooling
A
2.89/2.83/2.79
2.89/2.83/2.79
(220/230/240) Heating
A
2.89/2.83/2.79
2.89/2.83/2.79
Sound pressure level (measured in anechoice room)
dB <A>
41
Applicable temperature range of installation site
°C (D.B.)
0~32
External finish
Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized powder coating)
Connectable outdoor unit
PURY-WP200/250YJM-A(-BS)
Indoor unit capacity connectable to 1 branch
Model P80 or smaller
(Use a joint pipe (field supply) combining 2 branches when the total unit capacity exceeds P80)
External dimension H x W x D
mm
300 x 1,600 x 541
in.
11-13/16 x 63 x 21-5/16
Refrigerant piping
diameter
(To outdoor unit)
Connectable outdoor unit capacity
To WP200
To WP250
High press. Pipe
mm (in.)
O.D.
15.88 (5/8)
Brazed
19.05 (3/4)
Brazed
Low press. Pipe
mm (in.)
O.D.
19.05 (3/4)
Brazed
22.2 (7/8)
Brazed
Water piping
diameter
(To Indoor unit)
Inlet Pipe
mm (in.)
I.D.
20 (Rc3/4) screw
Outlet Pipe
mm (in.)
I.D.
20 (Rc3/4) screw
Field drain pipe size
mm (in.)
O.D. 32 (1-1/4)
Net weight
kg (lbs)
92 (203) [102 (225) with water]
Standard
attachment
Document
–
Accessory
1.Reducer
2.Drain Connection pipe (with flexible hose and insulation)
Optional parts
Sub drainpan: PAC-HBC01DP-E
Note;
1.Works not included:
Installation / foundation work, electrical connection work, duct work, insulation work, power source switch,
and other items are not specified in this specification.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant and water noise) emitted by the unit will not disturb the neighbours.
For use in quiet environments with low background noise, position the HBC CONTROLLER at least 5 m away from any indoor units.
4.Install the HBC controller in a place where noise will not be an issue.
5.Attach an expansion tank (field supply).
6.Use copper or plastic pipes for the water circuit. Do not use steel or stainless steel pipework.
Furthermore, when using copper pipe-work use a non-oxidative brazing method.
Oxidation of the pipe-work will reduce the pump life.
7.Install an air purge valve where air will gather in the water circuit.
8.Install a pressure reducing valve and a strainer on the water supply to the HBC controller. Also consider installing a non-return valve (check local regulations).
9.Refer to the databook or the installation manual for the specified water quality.
10.This unit is not designed for outside installation.
11.Always leave the power on or remove the circulation water completely when the power is off for an extended period.
*Do not use the circuit water as drinking water.
12.Do not use ground water or well water.
13.When installing the HBC unit in an environment which may drop below 0 °C, please add antifreeze to the circulating water.
(Refer to the data-book and the installation manual).
14.Use cover caps (field supply, dezincification resistant brass (DZR) or bronze only) on unused branches.
15.Install a sub drain pan (sold separately, PAC-HBC01DP-E). If leakage from underneath the HBC would cause no problem in the installed location,
installation of the sub drain pan is not necessary.
16.The system must be serviced at least once a year.
Summary of Contents for PURY-WP-YJM-A
Page 3: ...Databook ...
Page 5: ...1 2 INDOOR UNITS ...
Page 39: ...1 36 INDOOR UNITS ...
Page 51: ...1 48 INDOOR UNITS ...
Page 61: ...1 58 INDOOR UNITS ...
Page 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Page 69: ...2 2 OUTDOOR UNITS ...
Page 85: ...2 18 OUTDOOR UNITS ...
Page 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Page 173: ...4 2 SYSTEM DESIGN ...