
3. System remote controller
CONTROLLER
3 - 66
Contr
oller
* This figure omits the power supply line and only shows the transmission line.
For
AG-150A/GB-50ADA.
example, 5 contacts connected to the DIDO controller are calculated as the equivalent of 5 indoor units connected to
<Restrictions>
Maximum of 50 units (50 channels) per AG-150A/GB-50ADA
However, the number of units that can be connected to a AG-150A/GB-50ADA is up to 50 including the number of contacts used on
this device, an indoor unit, LOSSNAY unit, etc.
Up to 6 contacts can be connected to the DIDO controller (1 M-NET address). One contact connected to this device is calculated as
the equivalent of one indoor unit connected to AG-150A/GB-50ADA.
NOTE
• For the shield ground of the M-NET centralized control line, use single-point grounding at the power unit for
the transmission line.
However, when supplying electric power to the M-NET centralized control line from the R410A series outdoor
unit
*1
without using a power supply unit for the transmission line, use single-point grounding at the TB7 of that
outdoor unit. *1 : Except PUMY model.
Furthermore, when connecting this device to the M-NET indoor control line, use grounding at the TB3 for each
outdoor unit system.
• If the M-NET transmission line of this device is connected to the M-NET indoor control line and the outdoor
unit is down because, for example, the power supply is interrupted for servicing or there is a failure, the DIDO
controller cannot be controlled from the system controller.
• Controlling the ON/OFF remote controller is only possible with channel 1 of a standard terminal block.
• DIDO controller can only be monitored or performed from AG-150A LCD, AG-150A/GB-50ADA Web browser
and TG-2000A.
• When AG-150A/GB-50ADA is connected, monitoring control can only be performed from AG-150A,GB-50ADA
Web or TG-2000A. Monitoring control cannot be performed from the ON/OFF remote controller.
(a) ON/OFF, (ON) output
(b) (OFF) output
(c) ON/OFF input
(d) Error/Normal input
Standard: Terminal block (for 2 units)
Expansion: Connectors (for 4 units)
Total: 6 units
(c)
M-NET
M-NET
LAN
(a) (b)
(d)
(a) (b)
(c) (d)
Centralized control line
Indoor control line
DIDO controller
or
ON/OFF remote controller
DIDO control
Ventilation fan,
lighting, etc.
× up to 6 units
Ventilation fan,
lighting, etc.
24 VDC
Power supply
24 VDC
Power supply
Power supply unit
PAC-SC51KUA
× up to 6 units
HYBRID CITY MULTI
HBC controller
AG-150A
(GB-50ADA)
AG-150A(GB-50ADA)
web or TG-2000A
CENTRALIZED CONTROLLER AG-150A
Summary of Contents for PURY-WP-YJM-A
Page 3: ...Databook ...
Page 5: ...1 2 INDOOR UNITS ...
Page 39: ...1 36 INDOOR UNITS ...
Page 51: ...1 48 INDOOR UNITS ...
Page 61: ...1 58 INDOOR UNITS ...
Page 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Page 69: ...2 2 OUTDOOR UNITS ...
Page 85: ...2 18 OUTDOOR UNITS ...
Page 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Page 173: ...4 2 SYSTEM DESIGN ...