3. System remote controller
3 - 59
CONTROLLER
Controller
Item
Rating and Specification
Power Supply
24 VDC 10%: 5 W
Screw terminal block (M3) (*3)
Interface
M-NET communication 17 to 30 VDC (*1)
Screw terminal block (M3) (*3)
Non-voltage a-contact
input
Number of contacts: 4
Pulse signal:
a-contact
Pulse width:
100 ms to 300 ms
(Idle period until next pulse: 100 ms or more)
Rated current: 1 mA or less (*2)
Screwless terminal block
Environment
Conditions
Temperature
Operating temperature range
0 to 40 [32 to 104 ]
Storage temperature range
-20 to 60 [-4 to 140 ]
Humidity
30 to 90%RH (no condensation)
Dimensions
200 (W) 120 (H) 45 (D) mm / 7
7
/
8
(W) 4
3
/
4
(H) 1
25
/
32
(D) in
Weight
0.6 kg / 1
3
/
8
lb
Time Backup
During Power
Failure
In the event of power failure or shut-off, the internal capacitor will continue to track time for approximately one week.
(The internal capacitor takes about 24 hours to fully charge; a replacement battery is not necessary.)
Installation
Environment
Inside the metal control board (indoors)
* Use this product in a hotel, a business office environment or similar environment.
100 ms or more
100 ms ~ 300 ms
TB3
M-NET
M-NET
LAN
TB7
Centralized control line
Indoor control line
PI controller
AG-150A
(GB-50ADA)
AG-150A(GB-50ADA)
web or TG-2000A
Uninterruptible
power supply
(UPS)
Watt-hour meter with
pulse transmitter, etc.
*This figure omits the power supply line and only shows the transmission line.
Power supply unit
PAC-SC51KUA
PI controller
24 VDC
power supply
Up to 4 contacts
Watt-hour meter with
pulse transmitter, etc.
Uninterruptible
power supply
(UPS)
24 VDC
power supply
Up to 4 contacts
HYBRID CITY MULTI
HBC controller
1. Specifications
(1). Device Specifications
*1: Supply electric power from a power unit for the transmission line or an outdoor unit. Furthermore, the power consumption factor of
the M-NET circuitry of this device is "1/4" (equivalent to one ME Remote Controller).
*2: Supply electric power from the main unit to the contacts of the meters.
*3: M3 is the size of the screw on the terminal block (ISO metric screw thread). The number indicates the screw diameter (mm).
<Restrictions>
Maximum of 15 units (total of 60 channels) per AG-150A/GB-50ADA Ver. 2.45 or later
Maximum of 5 units (total of 20 channels) per AG-150A (Expansion controller)/GB-50ADA Ver. 2.45 or earlier
However, the number of units that can be connected to a AG-150A/GB-50ADA is up to 50 including this device, indoor units,
LOSSNAY units, etc.
The HYBRID CITY MULTI units do not support the Charging function.
The electric power consumption cannot be apportioned.
Rated voltage: 24 VDC
CENTRALIZED CONTROLLER AG-150A
Summary of Contents for PURY-WP-YJM-A
Page 3: ...Databook ...
Page 5: ...1 2 INDOOR UNITS ...
Page 39: ...1 36 INDOOR UNITS ...
Page 51: ...1 48 INDOOR UNITS ...
Page 61: ...1 58 INDOOR UNITS ...
Page 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Page 69: ...2 2 OUTDOOR UNITS ...
Page 85: ...2 18 OUTDOOR UNITS ...
Page 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Page 173: ...4 2 SYSTEM DESIGN ...