3. System remote controller
3 - 55
CONTROLLER
Controller
<LMAP04-E Network Variables>
The proper communication is not obtainable when communication intervals exceed its performance, assure sufficient intervals.
ACK Service is recommended for the network service.
Detailed specifications for the L
ON
W
ORKS
network can be found in "FTT-10A Free Topology Transceiver User's Guide" or " FT3120/FT3150 Smart
Transceiver Data Book" by Echelon Corporation.
Please obtain the Network Variables Specification for details from your dealer.
Item
Description
TMPN3150/FT3150-P20 (10MHz)
Neuron CHIP
MITSUBISHI ELECTRIC
Connected Equipment
FTT-10A/FT-X1 (Free Topology 78kbps)
( For details of the connectable models,please contact the dealer.)
Network Transceiver
Performance
2.5 inputs/second
Average communication capacity
50 inputs/second (for one second)
Peak communication capacity
Multiple split-type air conditioners
Heat recovery ventilators
LM-AP can control 50 indoor units (including LOSSNAY)
Number of Units
HYBRID CITY MULTI
LOSSNAY
Environment specification
®
Indoor[1]-[50]
Network Variables
nv1n
nviOnOff_n
SNVT_switch
nv2n
nvoOnOff_n
SNVT_ switch
nv3n
nviMode_n
SNVT_hvac_mode
nv4n
nvoMode_n
SNVT_hvac_mode
nv5n
nviSetP_n
SNVT_temp_p
nv6n
nvoSetP_n
SNVT_temp_p
nv7n
nviCoolSetP_n
SNVT_temp_p
nv8n
nvoCoolSetP_n
SNVT_temp_p
nv9n
nviHeatSetP_n
SNVT_temp_p
nv10n
nvoHeatSetP_n
SNVT_temp_p
nv11n
nviAutoSetP_n
SNVT_temp_p
nv12n
nvoAutoSetP_n
SNVT_temp_p
nv19n
nviFanSpeed_n
SNVT_switch
nv20n
nvoFanSpeed_n
SNVT_switch
(*2, 3, 4)
(*9, 10, 11)
(*2, 3, 4)
(*2, 3, 4)
nv21n
nviProOnOff_n
SNVT_switch
nv22n
nvoProOnOff_n
SNVT_switch
nv23n
nviProMode_n
SNVT_switch
nv24n
nvoProMode_n
SNVT_switch
nv25n
nviProSetP_n
SNVT_switch
nv26n
nvoProSetP_n
SNVT_switch
(*2, 3, 4)
(*2, 3, 4)
(*2, 3, 4)
(*5)
(*8)
(*9)
(*9)
(*9, 10, 11)
(*8)
(*9)
(*9)
nv27n
nviThermoOff_n
SNVT_switch
nv28n
nvoThermoOff_n
SNVT_switch
(*5)
(*6)
nv29n
nviFiltReset_n
SNVT_switch
nv30n
nvoOnTime_n
SNVT_time_hour
(*6)
nv31n
nvoSpaceTemp_n
SNVT_temp_p
nv32n
nvoAlarm_n
SNVT_switch
nv33n
nvoErrCode_n
SNVT_count
nv34n
nvoErrAdrs_n
SNVT_count
nv35n
nvoThermoSt_n
SNVT_state
nv36n
nvoThermo_n
SNVT_switch
nv38n
nvoIcMdlSize_n
SNVT_count
nv39n
nvoGroupNo_n
SNVT_count
(*7)
Notes
*1: "n" of the network variable shows M-NET
address of indoor units.
*2: It may be unable to be used by the system
configuration of air-conditioners units.
*3: It is possible to use with an "MA or ME" remote controller.
*4: For the use of this function, turn ON the switch (SW1-1) on
LM ADAPTER. (Factory setting "OFF")
*5: For the use of this function, turn ON the switch (SW1-8) on
LM ADAPTER. (Factory setting "OFF")
*6: For the use of this function, turn ON the switch (SW1-4) on
LM ADAPTER. (Factory setting "OFF")
*7: It is possible to use with other system controller.
*8: This function is available only for the conventional indoor
units which don't support the dual setpoint.
*9: These functions are available for the units which support
the dual setpoint.
*10: This function is available for the DOAS was manufactured
in October, 2012 or later, when it uses for the DOAS.
*11: This function is available when the auto mode should be
controlled by single set point like the conventional one,
even when the dual set point is valid.
Summary of Contents for PURY-WP-YJM-A
Page 3: ...Databook ...
Page 5: ...1 2 INDOOR UNITS ...
Page 39: ...1 36 INDOOR UNITS ...
Page 51: ...1 48 INDOOR UNITS ...
Page 61: ...1 58 INDOOR UNITS ...
Page 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Page 69: ...2 2 OUTDOOR UNITS ...
Page 85: ...2 18 OUTDOOR UNITS ...
Page 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Page 173: ...4 2 SYSTEM DESIGN ...