3. System remote controller
3 - 25
CONTROLLER
Controller
(A) For level signal
4).
Recommended circuit example
The contact relay, DC power source, extension cable, etc., must be prepared separately at the site.
The connection cable can be extended up to 10m (32 ft). (Use a 0.3mm
2
(AWG 22) or larger wire.)
Strip the extra cable near the connector, and securely insulate the exposed section with tape, etc.
CN5
Lead wire
Details of each terminal
No.1
Green
Common (External ground)
No.2
Black
ON/OFF*
No.3
Brown
Malfunction/normal
(2). External signal output function
1).
External output
When one or more air conditioners are running, the " ON " signal will be output and if a malfunction occurs in one or more air
conditioners, the " Malfunction " signal will be output.
2).
External output specifications
3).
Recommended circuit example
Each element will turn on while ON operation or a malfunction occurs.
The connection cable can be extended up to 10m (32 ft).
The relays, lamps, diodes and extension cables, etc, must be prepared separately at the site.
* To use the external signal input, an external I/O adapter (PAC-YG10HA; sold separately) and an external power supply are required.
Red
Orange
Max.10m
(32 ft)
CN5
X1
ON/OFF or
Emergency stop
Power supply(*1)
(12VDC or 24VDC)
This unit
X1
Max.10m
(32 ft)
This unit
CN5
Power supply(*1)
(12VDC or 24VDC)
Red
Gray
Blue
Yellow
Orange
Y2
Y1
X2
X1
Run Stop Prohibit Enable
(B) For pulse signal
X1
X2
Y1
Y2
Punch out the knockout hole
Use Z1 and Z2 relays that meet the following specifications.
Operation coil
Rated voltage
: 12VDC, 24VDC
Power Consumption: 0.9W or less
(*1) Prepare a power supply separately according to the relay
being used. (12VDC or 24VDC)
(*2) Always insert a diode on both ends of the relay coil.
Brown
Black
Diode(*2)
Power
(*1)
Supply
Z1
Z2
CN5
Green
Max.10m
(32 ft)
L1: Run display lamp
L2: Malfunction display lamp
This unit
L1
L2
Z1
Z2
NOTE
* When connecting the external input/output cables to connector CN5
on the controller, punch out the knockout hole.
Use relays X1, X2, Y1, and Y2 that meet the
following specifications.
Contact rating
Rated voltage
Rated current
>= 12VDC
>= 0.1A
Minimum applicable load =< 1mA at DC
(*2)
(*2)
* The operation status of DIDO controller is not output.
* Operation signal is output during an error.
The " ON" signal is output even while the " Malfunction"
signal is being output.
Summary of Contents for PURY-WP-YJM-A
Page 3: ...Databook ...
Page 5: ...1 2 INDOOR UNITS ...
Page 39: ...1 36 INDOOR UNITS ...
Page 51: ...1 48 INDOOR UNITS ...
Page 61: ...1 58 INDOOR UNITS ...
Page 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Page 69: ...2 2 OUTDOOR UNITS ...
Page 85: ...2 18 OUTDOOR UNITS ...
Page 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Page 173: ...4 2 SYSTEM DESIGN ...