3. System remote controller
CONTROLLER
3 - 68
Contr
oller
2. Wiring Instructions
(1). Connecting the Power and M-NET Transmission Lines
CAUTION
• Use a power line and M-NET transmission line that satisfy the specifications described in "1-(2). Parts
Purchased Separately".
• Attach a circuit comprising the following components to the supply primary side of the 24 VDC power supply.
(1) Varistor, (2) Arrester, (3) Noise filter, (4) Fuse
• It is important to pay attention to the polarity when connecting to the 24 VDC power supply terminal block.
Connecting the positive and negative in the reverse order will cause a failure.
• Fix the power line and M-NET transmission line in place on the outside to ensure that the terminal block is not
affected by any external force.
Not securely connecting and fixing the wires in place may cause heat generation and fire.
• Make sure that the copper wiring is not short-circuiting the plates (cover, lower case) or neighboring wires.
Cover the shielded line of the M-NET transmission line with materials such as vinyl tape and prevent
short-circuiting with the plates.
CN16
CN17
A/B/S
V+/V-/FG
S
FG
M-NET
S / B /
A
(M1)
(M2)
U
U
R
DIDO controller
Field
Connections
(example)
AC Power Line
Fuse
Varistor
Varistor
* Functional
ground
Arrester
Noise
Filter
24 VDC
Power
source
Tightening torque for terminal screws: 1 N·m
Connect the M-NET transmission line of this device to a power
supply unit (PAC-SC51KUA) for the M-NET transmission line
or an outdoor unit (either a centralized control line or indoor
control line can be connected).
* Only the M-NET circuitry of this device receives the power from the
M-NET transmission line. The power consumption factor is "1/4"
(equivalent to one ME Remote Controller).
Summary of Contents for PURY-WP-YJM-A
Page 3: ...Databook ...
Page 5: ...1 2 INDOOR UNITS ...
Page 39: ...1 36 INDOOR UNITS ...
Page 51: ...1 48 INDOOR UNITS ...
Page 61: ...1 58 INDOOR UNITS ...
Page 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Page 69: ...2 2 OUTDOOR UNITS ...
Page 85: ...2 18 OUTDOOR UNITS ...
Page 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Page 173: ...4 2 SYSTEM DESIGN ...