2. M-NET control
4 - 15
SYSTEM DESIGN
Sy
stem
2-4-3. System examples
Original switch setting of the outdoors, indoors, controllers, LM-AP and BM ADAPTER at shipment is as follows.
• Outdoor unit
: Address: 00, CN41: ON (Jumper), DipSW2-1: OFF
• Indoor unit
: Address: 00
• HBC controller
: Address: 00
• BM ADAPTER
: Address: 000, CN41: ON (Jumper)
• DipSW2-1(Outdoor)
: When the system controller is used, all the Dip SW2-1 at the outdoor units should be set to
"ON". * Dip SW2-1 remains OFF when only LM-AP is used.
• DipSW1-2(LM-AP)
: When the LM-AP is used together with the system controller, DipSW1-2 at the LM-AP
should be set to "ON".
• CN40/CN41
: Change jumper from CN41 to CN 40 at outdoor control board will activate central transmission
power supply to TB7;
(Change jumper at only one outdoor unit when activating the transmission power supply
without using a power supply unit.)
Changing jumper from CN41 to CN 40 at LM-AP will activate transmission power supply to
LM-AP itself;
A power supply unit is recommended for use in a system having more than 1 outdoor unit,
because the central transmission power supply is from TB7 of one of the outdoor units, risking
that the outdoor unit failure may let down the whole system controller system.
2-4-3-1. MA remote controller, single-refr igerant-system, no system controller
1. Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address. (Only a single outdoor unit can be connected to a HYBRID CITY MULTI system.)
2. No address setting is needed.
3. For a system having more than 32 indoor units (P15-P140), check the need of a booster at
2-3 "System configuration
restrictions".
4. Indoor units should be set with a branch number.
5. When a PAR-31MAA is connected to a group, no other MA remote controllers can be connected to the same group.
NOTE:
Indoor unit
MA R/C
MA R/C
MA R/C
(Main)
(Sub)
MA R/C
SRU
Wireless R/C
1*
*1 For wireless R/C and signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
1*
00
00
00
00
00
TB15
TB5
TB02
TB5
TB5
TB5
TB5
TB15
TB15
TB15
TB15
Group 2
Group 1
Group 3
Group 4
<Two outdoor units>
<One outdoor unit>
TB3
TB3
00
00
OC
OS
PURY
00
HBC controller
TB3
00
OC
CN41
CN40
CN41
CN40
CN41
CN40
OFF
DipSW2-1
OFF
DipSW2-1
OFF
DipSW2-1
PURY
Factory setting
Setting at the site
• ME remote controller : Address: 101
• LM-AP
: Address: 247, CN41: ON (Jumper), DipSW1-2: OFF
Summary of Contents for PURY-WP-YJM-A
Page 3: ...Databook ...
Page 5: ...1 2 INDOOR UNITS ...
Page 39: ...1 36 INDOOR UNITS ...
Page 51: ...1 48 INDOOR UNITS ...
Page 61: ...1 58 INDOOR UNITS ...
Page 68: ...2 1 HYBRID CITY MULTI OUTDOOR UNITS 2 OUTDOOR UNITS HYBRID CITY MULTI 2 3 ...
Page 69: ...2 2 OUTDOOR UNITS ...
Page 85: ...2 18 OUTDOOR UNITS ...
Page 172: ...4 1 HYBRID CITY MULTI SYSTEM DESIGN 4 SYSTEM DESIGN SYSTEM DESIGN 4 3 ...
Page 173: ...4 2 SYSTEM DESIGN ...