3. System remote controller
CONTROLLER
3 - 80
Contr
oller
2) Channel 1 (Channel 2) Analog Input (4 to 20 mADC, 1 to 5 VDC, 0 to 10 VDC)
CAUTION
• Select a power supply that is suitable for the sensor to be used.
• Do not install the sensor input line parallel to or near the M-NET transmission line or power line. Also avoid
loop wiring.
Furthermore, confirm the precautions for the sensor.
• Strip 12 1 mm (15/32 1/32 in) of the wire coating and insert firmly into the terminal.
• Make sure that the copper wiring is not short-circuiting the plates (cover, lower case) or neighboring wires.
• Perform wiring so that the terminal block is not strained.
If strained, use a wire guide or junction terminal to alleviate the stress on the terminal block.
(b) When 4 to 20 mADC
(type for which power is supplied to the signal line)
is connected
(a) When 1 to 5 VDC, 0 to 10 VDC, or 4 to 20 mADC
(type for which power is supplied to the sensor)
is connected
CN05
(CN08)
CN05
(CN08)
Sensor
Power supply
Field
Connections
Power supply
Sensor
Device side
Field
Connections
Device side