- 25 -
IC
TB5
TB15
1 2
01
IC
TB5
TB15
1 2
03
A1 B2
MA
A1 B2
MA
TB5
06
IC
TB5
1 2
TB15
IC
TB5
TB15
1 2
1 2
04
02
IC
TB5
TB15
05
A1 B2
MA
L3
L4
L23
L24
NO
L1
L2
L22
L21
L31
m2
m3
a. Indoor/outdoor transmission line
Farthest length (1.25mm
2
or more)
L1 + L2 + L3 + L4
200m
L21 + L22 + L23 + L24
200m
b. Centralized control transmission line
Farthest length via outdoor unit (1.25mm
2
or more)
L1 + L2 + L3 + L4 + L31 + L21 + L22 + L23 + L24
500m
c. MA remote controller wiring
The same as 1. (1)
Control wiring example
Group
Prohibited items
Allowable length
1. M-NET and MA remote controllers can not be connected to-
gether to the indoor unit within the same group.
2. MA remote controller of 3 units or more can not be connected
to the indoor unit within the same group.
3. Do not connect together the terminal blocks (TB5) of the in-
door unit connected to different outdoor units.
4. Replacement of the power supply selecting connector (CN41)
on the outdoor unit should be done only on one outdoor unit.
5. Grounding of S-terminal of the centralized control terminal
block (TB7) on outdoor unit should be done only on one out-
door unit.
6. When the total number of indoor units exceeds 26 units in-
cluding that above Type 200, a transmission booster is re-
quired.
Interlocking with ventilation
– Example to use shielded wire –
Group
Group
LC
≤
≤
≤
NO
✻
1. BC and BS are found only in the R2 system.
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
M1M2
51
55
53
54
52
Connect
OC
OC
Leave CN41
as it is.
CN41
→
CN40
Replace
TB02
TB02
TB02
TB7
TB3
TB7
TB3
BC
✻
1
BC
✻
1
BS
✻
1
1. System using MA remote controller
(3) In the case of different refrigerant grouping operation