(1) Screw terminal is loose.
(2) IPM is cracked due to swelling.
(3) Resistance error between each ter-
minal of IPM.
(4) All normal for items (1) ~ (3) above.
Check item
Phenomena
Treatment
[5]
Check the
inverter circuit
trouble.
1. Check to see if the IPM screw
terminal is loose.
2. Check the exterior of the IPM.
3.
1. Check around the fan output
wiring.
Check
(1) Fan motor megger fault
Fault when the megger is 1
Ω
or
less.
(2) Fan motor disconnection
Standard: The winding resistance
is approximately several
Ω
.
(It varies depending on the tempe-
rature or while the inner thermo is
operating, it will be
∞Ω
.)
[6]
Check the fan
motor grounding
fault and the
winding.
Remove the wire for the outdoor
fan motor and check the fan
motor megger and the winding
resistance.
Replace the fan motor.
all IPM screw terminals and
tighten.
• IPM replacement
Check the operation in [3] or [4] after
replacing the IPM.
In the case of an output voltage un-
balance or error recurrence:
→
Replace the G/A board
In the case of an output voltage un-
balance or error recurrence after re-
placement:
→
Replace the INV board
• IPM replacement
Check the operation in [3] or [4] after
replacing the IPM.
In the case of an output voltage un-
balance or error recurrence:
→
Replace the G/A board
In the case of an output voltage un-
balance or error recurrence after re-
placement:
→
Replace the INV board
• IPM replacement
In the case of an output voltage un-
balance or error recurrence after re-
placement:
→
Replace the G/A board
In the case of an output voltage un-
balance or error recurrence after re-
placement:
→
Replace the INV board
Connector contact failure
1) Board side (CNINV)
2) Fan motor side
(2) The same error occurs even if
operated again.
(1) The voltage unbalance among
each motor.
(The voltage unbalance is
grerater than the larger of the
values represented by 5% or 5V.)
[7]
Check the FAN
board failure.
Connect the connector
2. Check the connector CNVDC
connection
Connector contact failure
Connect the connector
3. Check the FAN board failure.
Replace the FAN board.
The same error occurs even if the
board is replaced as described in 3.
4. Check the transformation of
the FAN board.
Replace the power-supply
transformation for FAN board.
Check the resistances between
each terminal of IPM.
Refer to
9
.[4].7.(5) for details
on IPM troubleshooting.
- 182 -