- 134 -
Checking code
Meaning, detecting method
Cause
Checking method & Countermeasure
4250
4255
4260
4265
5101
5102
5103
5104
Load short
abnormality
(Error details
105)
Cooling fan
abnormality
<In the case of 4250>
(1) Shorting of compressor
(2) Output wiring
(3) Power supply
<In the case of 4255>
(1) Shorting of fan motor
(2) Output wiring
(3) Power supply
Same as 4230 error
Refer to
9
.[4].7.(2).[2]
Refer to
9
.[4].7.(2).[6]
Same as 4230 error
Shorting at the load
(compressor) side detected just
before starting the inverter.
<In the case of 4260>
When the heat sink temperature
(THHS1) 95˚C for 10 minutes
or longer after the inverter starts.
<In the case of 4265>
When the heat sink temperature
(THHS5) 85˚C for 10 minutes
or longer after the inverter starts.
Air inlet
Liquid
pipe
Gas pipe
Outdoor
air
tempera-
ture
(1) Thermistor failure
(2) Contact failure of the
connector
(3) Thermistor wire
disconnection or partial
disconnection
(4) Thermosensor is not set up
or contact failure
(5) Indoor board failure
(detection circuit)
Themistor resistance check
0˚C : 15k
Ω
10˚C : 9.7k
Ω
20˚C : 6.4k
Ω
30˚C : 4.3k
Ω
40˚C : 3.1k
Ω
Check the contact of the
connector
If no fault is found, the indoor
board is a failure.
When shorting or open of the
sensor is detected while the
thermo is ON, the restart
prevention mode will be
operated for 3 minutes. If there
is no recovery after 3 minutes,
the unit will make an error stop.
(If there is a recovery, the unit
will run normally.)
Shorting: detectable at 90˚C or
higher
Open : detectable at –40˚C or
lower
✻
Sensor error at gas-side
cannot be detected under the
following conditions.
· During heating operation
· During cooling operation for
3 minutes after the
compressor turns on.
–
5104
Outdoor
air
tempera-
ture
(1) The connection of the
connector (CN29) is a failure.
(2) The outdoor sir processing
unit is out of order.
Check the contact of the
connector
Replace the sensor.
✻
For the check code on the inverter, refer to
“
7. Inverter and compressor
”
in the section [4]
“
Troubleshooting of principal parts
”
Themal sensor error (Indoor unit)
(Outdoor air processing unit)