- 100 -
Operation mode
SVM1
Stop
OFF
Defrost
ON
Heating main
OFF
Heating only
OFF
Cooling main
Cooling only
ON
Pressure difference
control
✻
2
✻
2: The pressure difference (PS1, P3) is controlled every minute to stay constant.
(2) SVM1 control
SVM comes on and off depending on the operation mode.
Operation mode
LEV1
Stop
1200
Defrost
2000
Heating main
110
✻
4
Cooling main
Liquid-level
control
✻
3
Pressure difference
control
✻
2
Heating only
110
Cooling only
2000
LEV2
Type GA only
Type
G, GA
Type
GB
LEV3
600
G:1000
G:2000
Pressure difference
control
✻
2
Pressure difference
control
✻
2
Superheat
control
✻
1
LEV3a
60
60
60
Superheat
control
✻
1
60
Superheat
control
✻
1
✻
1: Superheat control - Every minute, the amount of superheat calculated on the bases of bypass outlet/inlet temperature
(G,GA:TH12,TH15, GB:TH22,TH25) is controlled every minute to stay constant.
✻
2: The pressure difference (PS1, P3) is controlled every minute to stay constant.
✻
3: The liquid level detected on the bases of liquid inlet temperature (TH11) is controlled every minute to stay constant.
✻
4: It may exceed 110 due to a pressure rise on the liquid side (PS1).
(3) LEV
control
The opening of LEV (sj) is controlled based on the operation mode.
Operation mode
SVM2
Stop
OFF
Defrost
OFF
Heating main
Pressure difference
control
✻
2
Heating only
Pressure difference
control
✻
2
Cooling main
OFF
Cooling only
OFF
(4) SVM2 control (Type GA only)
Mode
Pipe
end connection
SV A
SV B
SV C
ON
Cooling
OFF
ON
OFF
Heating
ON
OFF
OFF
Stop
OFF
OFF
OFF
Defrost
OFF
OFF
12. BC controller control (CMB-P G, CMB-P GA, CMB-P GB)
(1) SV A, SV B, SV C control
SV A, SV B, SV C comes on and off depending on the mode at the pipe end connection.