- 139 -
Checking
code
Meaning, detecting method
System
com-
position
Cause
Cause checking method &
Countermeasure
Generating
unit
address
Display of
trouble
Detecting
method
6607
When no ACK signal is detected in 6 continuous times with 30 seconds
interval by transmission side controller, the transmission side detects
error.
Note : The address/attribute shown on remote controller indicates the
controller not providing the answer (ACK).
No ACK abnormality
1. Outdoor
unit(OC)
2. BC
controller
(BC)
3. Indoor
unit (IC)
4. Remote
controller
(RC)
No reply
(ACK) at BC
transmission
to OC
No reply
(ACK) at IC
transmission
to BC
No reply
(ACK) at RC
transmission
to IC
No reply
(ACK) at IC
transmission
to RC
Remote
controller
(RC)
M-NET
remote
controller
(RC)
MA remote
controller
(MA)
Remote
controller
(RC)
Remote
controller
(RC)
(1) Poor contact of transmission
line of OC or BC.
(2) Damping of transmission line
voltage/signal by acceptable
range of transmission wiring
exceeded.
Farthest:
Less than 200m
Remote controller wiring:
Less than 10m
(3) Erroneous sizing of
transmission line (Not within
the range below).
Wire diameter:
1.25mm
2
or more
(4) Faulty control circuit board of
OC.
(1) When BC controller address
is changed or modified
during operation.
(2) Faulty or disconnection of
transmission wiring of BC
controller.
(3) Disconnection of BC
controller connector (CN02).
(4) Faulty control board of BC
controller.
(1) When IC unit address is
changed or modified during
operation.
(2) Faulty or disconnection of
transmission wiring of IC.
(3) Disconnection of IC unit
connector (CN2M).
(4) Faulty IC unit controller.
(5) Faulty remote controller.
(1) Faulty transmission wiring at
IC unit side.
(2) Faulty transmission wiring of
RC.
(3) When remote controller
address is changed or
modified during operation.
(4) Faulty remote controller.
Shut down OC unit power source, and
make it again.
It will return to normal state at an
accidental case.
When normal state can not be
recovered,check for the (1) ~ (4) of the
cause.
Shut down the power sources of both
OC and BC for 5 minutes or more, and
make them again.
It will return to normal state at an
accidental case.
When normal state can not be
recovered, check for (1)~(4) of the
cause.
Shut down both OC power source for 5
minutes or more, and make them
again.
It will return to normal state at an
accidental case.
When normal state can not be
recovered, check for the (1) ~ (4) of the
cause.
Shut down OC power sources for 5
minutes or more, and make it again.
It will return to normal state at an
accidental case.
When normal state can not be
recovered, check for the (1) ~ (4) of the
cause.
(1) Single refrig
erant system
Checking
code
Meaning, detecting method
Cause
Checking method & Countermeasure
6606
(1) Data is not properly
transmitted due to casual
erroneous operation of the
generating controller.
(2) Faulty generating controller.
Turn off power sources of indoor unit,
and outdoor unit.
When power sources are turned
off separately, microcomputer is
not reset and normal operations
can not be restored.
→
Controller trouble is the source of the
trouble when the same trouble is
observed again.
Communications with transmission
processor abnormality
Communication trouble between
apparatus processor and
transmission processor.
Note:
The address/attribute shown on
remote controller indicates the
controller which has detected
error.