- 101 -
NO
OK
If the step listed as the wrong example above is taken, thermo may go off.
The percentage of the demand listed in the table above is an approximate value based on the
compressor volume and does not necessarily correspond with the capacity.
(Wrong)
(Correct)
100%
100%
→
→
0%
75%
→
→
50%
50%
Demand control
steps
Adaptor for external input
(PAC-SC36NA)
CN3D
X
Y
X
Y
Maximum allowable length of wiring is 10 m.
SW1 : NIGHT MODE or demand command
SW2 : Demand command
X,Y
: Relay (contact rating DC1mA)
SW1
SW2
Orange 1
Brown
2
Red
3
Remote controller board
Relay circuit
Outdoor unit
controller board
Power supply to relay
To be
acquired
on site
[ Example of wiring connection ]
OPEN
OPEN
SHORT
SHORT
OPEN
SHORT
OFF
ON
Compressor ON/OFF
CN3D 1-3P
OPEN
SHORT
ON
OFF
NIGHT MODE
CN3D 1-2P
CN3D 1-2P
100% (no demand)
75%
0%
50%
CN3D 1-3P
Note the following steps to be taken when using the STEP DEMAND
(Example) When witching from 100% to 50%
SW4-7 : OFF (Compressor ON/OFF and NIGHT MODE)
SW4-7 : ON (STEP DEMAND)
13. Demand control
Cooling/heating operation can be prohibited (thermo OFF) by an external input to the indoor units.
Note : When DIPSW4-7 are on, STEP DEMAND are possible. NIGHT MODE will become unavailable however.