- 31 -
IC
TB5
TB15
1 2
01
IC
TB5
TB15
1 2
02
A1 B2
MA
A1 B2
MA
TB5
05
IC
TB5
1 2
TB15
IC
TB5
TB15
1 2
04
03
TB5
06
A1 B2
MA
L3
L2
L1
L4
L23
L22
L21
L24
L31
L25
NO
a. Indoor/outdoor transmission line
Farthest length (1.25mm
2
or more)
L1 + L2 + L3 + L4
200m
L21 + L22 + L23 + L24
200m
L25
200m
b. Centralized control transmission line
Farthest length via outdoor unit (1.25mm
2
or more)
L25 + L31 + L1 + L2 + L3 + L4
500m
L1 + L2 + L3 + L4 + L31 + L21 + L22 + L23 + L24
500m
c. MA remote controller wiring
The same as 1. (1)
Control wiring example
Group
Prohibited items
Allowable length
1. M-NET and MA remote controllers can not be connected to-
gether to the indoor unit within the same group.
2. MA remote controller of 3 units or more can not be connected
to the indoor unit within the same group.
3. Do not connect together the terminal blocks (TB5) of the in-
door unit connected to different outdoor units.
4. Replacement of the power supply selecting connector (CN41)
on the outdoor unit should be done only on one outdoor unit.
5. Grounding work is required for S-terminal of the centralized
control transmission block (TB7) on one outdoor unit only.
6. The system controller connectable to the indoor/outdoor trans-
mission line counts for 3 sets maximum. While G-50 counts
for only 1 set
7. When the total number of indoor units exceeds 26 sets, th e
system controller may not be connected to the indoor/out-
door transmission line.
8. When the total number indoor units exceed 18 sets and they
includes Type 200 or above, the system controller may not
be connected to the indoor/outdoor transmission line.
Interlocking with ventilation
– Example to use shielded wire –
Group
Group
LC
LC
Note 1
System controller
Note 1. LM adaptor may not be connected to indoor/outdoor transmission line.
≤
≤
≤
≤
≤
✻
1. BC and BS are found only in the R2 system.
NO
OC
TB3
TB7
51
✻
1 BC
TB02
55
OC
TB3
TB7
53
✻
1 BC
TB02
54
TB02
52
✻
1 BS
Connect
CN41
→
CN40 Replace
SW2-1 OFF
→
ON
Leave CN41 as it is.
SW2-1 OFF
→
ON
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
S
M1M2
M1M2
1. System using MA remote controller
(6) In the case of connecting system controller to indoor/outdoor transmission line (excluding LM adaptor)