- 133 -
Checking code
4240
4245
Meaning, detecting method
Cause
Checking method & Countermeasure
Overload
abnormality
(1) Air passage short cycle.
(2) Air passage blockage.
(3) Power supply.
(4) Wiring defect.
(5) THHS failure.
(6) INV board fan output failure.
(7) Cooling fan failure.
(8) Current sensor (ACCT)
failure.
(9) Inverter circuit failure.
(10) Compressor failure.
Ensure that a short cycle has not
occurred at the unit fan exhaust.
Check to make sure the air
passage of the heat sink cooling
is not blocked.
Check if the power supply
voltage 342V.
Check the cooling fan wiring.
Check the THHS sensor
resistance.
Ensure that the heat sink
temperature is 55˚C or more and
that 220~240V is applied to the
inverter PCB connector CNFAN
when the inverter is on.
Check the cooling fan operation
under the above operating
conditions.
Refer to
9
.[4].7.(4)
“Current sensor ACCT”
Refer to
9
.[4].7.(2).[4]
“Inverter damage check”
Check that the compressor has
not overheated during operation.
→
Check the refrigerant circuit
(oil return section). Replace
the compressor if there are no
problems with the refrigerant
circuit.
When the output current (lac)
> Imax (Arms) or THHS > 90˚C
is detected for 10 minutes in a
row during the inverter operation.
Type P200
Type P250
Type P300
Type P350
Type P400
Type P450
Type P500
Type P550
Type P600
Type P650
27 Arms
27 Arms
27 Arms
27 Arms
27 Arms
27 Arms
27 Arms
27 Arms
27 Arms
27 Arms
4250
4255
IPM
abnomality
(Error details
No.101)
ACCT
overcurrent
abnormality
(Error details
No.102)
DCCT
overcurrent
abnormality
(Error details
No.103)
ACCT
overcurrent
abnormality
(Error details
No.106, 107)
IPM
short/grounding
fault
(Error details
No.104)
<In the case of 4250>
(1) Inverter output related.
(2) Same as 4230 error.
<In the case of 4255>
(1) Grounding fault of fan motor.
(2) FAN board failure.
(1) Inverter output related.
<In the case of 4250>
(1) Grounding fault of
compressor.
(2) Inverter output related.
<In the case of 4255>
(1) Grounding fault of fan motor.
(2) FAN board failure.
Same as 4230 error
Refer to
9
.[4].7.(2).[6]
Refer to
9
.[4].7.(2).[7]
9
.[4].7.(2) inverter output
related trouble processing
Refer to [1] - [5].
Refer to
9
.[4].7.(2)
Refer to
9
.[4].7.(2).[6]
Refer to
9
.[4].7.(2).[7]
IPM error signal detected
Overcurrent break
(94Apeak or 35Arms) de-tected
by the current sensor.
IPM short damage or grounding
at the load side detected just
before starting the inverter.
Imax
✻
For the check code on the inverter, refer to
“
7. Inverter and compressor
”
in the section [4]
“
Troubleshooting of principal parts
”