4
A
(mm)
Å
Outdoor model
RP200
RP250
RP300
RP350
RP400
RP450
RP500
RP550
RP600
RP650
RP700
RP750
RP800
RP850
RP900
unit1
-
-
-
-
RP200
RP200
RP250
RP250
RP300
RP300
RP200
RP250
RP250
RP250
RP300
unit2
-
-
-
-
RP200
RP250
RP250
RP300
RP300
RP350
RP250
RP250
RP250
RP300
RP300
unit3
-
-
-
-
-
-
-
-
-
-
RP250
RP250
RP300
RP300
RP300
ı
Liquid pipe
ø12.7
ø12.7
ø12.7
ø15.88
ø15.88
ø15.88
ø15.88
ø15.88
ø19.05
ø19.05
ø19.05
ø19.05
ø19.05
ø19.05
ø19.05
Ç
Gas pipe
ø28.58*2
ø28.58
ø28.58
ø34.93
ø34.93
ø34.93
ø34.93
ø34.93
ø34.93
ø41.28
ø41.28
ø41.28
ø41.28
ø41.28
ø41.28
ı
Liquid pipe
-
-
-
-
ø9.52
ø9.52
ø9.52
ø9.52
ø12.7
ø12.7
ø9.52
ø9.52
ø9.52
ø9.52
ø12.7
Ç
Gas pipe
-
-
-
-
ø19.05
ø19.05
ø22.2
ø22.2
ø22.2
ø22.2
ø19.05
ø22.2
ø22.2
ø22.2
ø22.2
ı
Liquid pipe
-
-
-
-
ø9.52
ø9.52
ø9.52
ø12.7
ø12.7
ø12.7
ø9.52
ø9.52
ø9.52
ø12.7
ø12.7
Ç
Gas pipe
-
-
-
-
ø19.05
ø22.2
ø22.2
ø22.2
ø22.2
ø28.58
ø22.2
ø22.2
ø22.2
ø22.2
ø22.2
ı
Liquid pipe
-
-
-
-
-
-
-
-
-
-
ø9.52
ø9.52
ø12.7
ø12.7
ø12.7
Ç
Gas pipe
-
-
-
-
-
-
-
-
-
-
ø22.2
ø22.2
ø22.2
ø22.2
ø22.2
ı
Liquid pipe
-
-
-
-
-
-
-
-
-
-
ø19.05
ø19.05
ø19.05
ø19.05
ø19.05
Ç
Gas pipe
-
-
-
-
-
-
-
-
-
-
ø34.93
ø34.93
ø34.93
ø34.93
ø34.93
Unit combination
A
A1 *1
A2 *1
A3 *1
A4
9.2
9
*1 The pipe sizes listed in columns A1 to A3 in this table correspond to the
sizes for the models listed in the unit 1, 2, and 3 columns. When the order
of the models for unit 1, 2, and 3 change, make sure to use the appropriate
pipe size.
*2 ø25.4 for R22
B, C, D
(mm)
a, b, c, d, e
(mm)
Ï
Downstream unit model total
~ 200
201 ~ 400
401 ~ 650
Ó
The 1st branch of P450 ~ P650
651 ~
È
The 1st branch of P700, P750, P800
Ì
Joint
CMY-Y102SS-G2
CMY-Y102LS-G2
CMY-Y202S-G2
CMY-Y302S-G2
Î
Total capacity of indoor units
~ 80
81 ~ 160
161 ~ 330
331 ~ 480
481 ~ 630
631 ~
ı
Liquid pipe
ø9.52
ø12.7
ø12.7
ø15.88
ø15.88
ø19.05
Ç
Gas pipe
ø15.88
ø19.05
ø25.4 or ø28.58
ø31.75 or ø34.93
ø38.1 or ø34.93
ø41.28
‰
Model number
15,20,25,32,40
50,63,71,80
100,125,140
200,250
ı
Liquid pipe
ø6.35
ø9.52
ø9.52
ø12.7
Ç
Gas pipe
ø12.7
ø15.88
ø19.05
ø28.58
Ô
4-Branching header
(Downstream unit
model total
=
200)
CMY-Y104-G
8-Branching header
(Downstream unit
model total
=
400)
CMY-Y108-G
Ò
10-Branching header
(Downstream unit
model total
=
650)
CMY-Y1010-G
Å
Outdoor model
P400 ~ P650
P700 ~ P900
˜
Outdoor twinning kit
CMY-RP100VBK
CMY-RP200VBK
WT06215X01_illust_e.p65
10.12.17, 13:53
4