25
6. CAPACITY TABLES
OUTDOOR UNITS
6. CAPACITY TABLES
6-1. Correction by temperature
CITY MULTI could have various capacities at different designing temperatures. Using the nominal cooling/heating capacity values
and the ratios below, the capacity can be found for various temperatures.
Nominal
Cooling
Capacity
Input
kW
BTU/h
kW
Nominal
Heating
Capacity
Input
kW
BTU/h
kW
RP200YJM-B RP250YJM-B
22.4
76,400
5.68
28.0
95,500
7.62
25.0
85,300
5.69
31.5
107,500
7.22
RP200YJM-B RP250YJM-B
0.8
0.9
1.0
1.1
1.2
1.3
1.4
0.7
0.6
0.5
0.4
Ratio of power input
1.2
1.3
1.4
1.1
0.9
0.6
0.8
0.5
0.7
0.4
1.0
Ratio of heating capacity
Ratio of heating capacity and power input
-4
5
14
23
32
41
50
59
-20
-15
-10
-5
0
5
10
15
°FWB
°CWB
Outdoor Temperature
Indoor Temperature
15°CDB
59°FDB
20°CDB
68°FDB
25°CDB
77°FDB
27°CDB
80°FDB
15°CDB
59°FDB
20°CDB
68°FDB
25°CDB
77°FDB
27°CDB
80°FDB
PUHY-
PUHY-
-5
23
0
32
5
41
10
50
15
59
20
68
25
77
30
86
35
95
40
104
45
113
°CDB
°FDB
Outdoor Temperature
0.6
0.8
0.9
1.0
1.2
1.1
0.7
0.6
0.5
0.4
Ratio of power input
1.3
1.4
1.2
1.0
0.9
0.8
0.7
1.1
Ratio of cooling capacity
Ratio of cooling capacity and power input
Indoor Temperature
24°CWB
75°FWB
22°CWB
72°FWB
20°CWB
68°FWB
18°CWB
64°FWB
16°CWB
61°FWB
15°CWB
59°FWB
24°CWB
75°FWB
22°CWB
72°FWB
20°CWB
68°FWB
18°CWB
64°FWB
16°CWB
61°FWB
15°CWB
59°FWB