5-4. Cooling capacity with PUHY-RP700-800YSJM
PLFY-P-VCM-E
CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model
Outdoor
Indoor air temp.
size
air temp.
21.5°C D.B.
23°C D.B.
25°C D.B.
27°C D.B.
28°C D.B.
30°C D.B.
32°C D.B.
(Rated kW)
15°C W.B.
16°C W.B.
18°C W.B.
19°C W.B.
20°C W.B.
22°C W.B.
24°C W.B.
°C D.B.
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
20
(2.2)
20.0 2.1
1.8
2.2
1.9
2.4
1.9
2.4
2.0
2.5
2.0
2.7
2.0
2.9
1.9
22.5 2.1
1.8
2.2
1.8
2.3
1.8
2.4
2.0
2.5
2.0
2.6
1.9
2.8
1.9
25.0 2.1
1.8
2.1
1.8
2.3
1.8
2.4
2.0
2.4
1.9
2.6
1.9
2.8
1.9
27.5 2.0
1.7
2.1
1.8
2.2
1.8
2.3
1.9
2.4
1.9
2.6
1.9
2.7
1.9
30.0 2.0
1.7
2.0
1.8
2.2
1.8
2.3
1.9
2.4
1.9
2.5
1.9
2.7
1.9
32.5 1.9
1.7
2.0
1.8
2.2
1.8
2.2
1.9
2.3
1.9
2.5
1.9
2.6
1.9
35.0 1.9
1.7
2.0
1.8
2.1
1.8
2.2
1.9
2.3
1.9
2.4
1.9
2.6
1.8
37.5 1.9
1.7
1.9
1.7
2.1
1.7
2.1
1.9
2.2
1.9
2.4
1.8
2.5
1.8
40.0 1.8
1.7
1.9
1.7
2.0
1.7
2.1
1.9
2.2
1.8
2.3
1.8
2.5
1.8
43.0 1.8
1.6
1.8
1.7
2.0
1.7
2.1
1.8
2.1
1.8
2.3
1.8
2.4
1.8
25
(2.8)
20.0 2.7
2.2
2.8
2.2
3.0
2.2
3.1
2.4
3.2
2.4
3.4
2.3
3.7
2.3
22.5 2.7
2.1
2.8
2.2
3.0
2.2
3.1
2.4
3.2
2.3
3.4
2.3
3.6
2.3
25.0 2.6
2.1
2.7
2.2
2.9
2.2
3.0
2.3
3.1
2.3
3.3
2.3
3.5
2.3
27.5 2.6
2.1
2.7
2.2
2.9
2.2
3.0
2.3
3.1
2.3
3.3
2.3
3.5
2.3
30.0 2.5
2.1
2.6
2.1
2.8
2.1
2.9
2.3
3.0
2.3
3.2
2.3
3.4
2.2
32.5 2.5
2.1
2.6
2.1
2.7
2.1
2.8
2.3
2.9
2.3
3.1
2.2
3.3
2.2
35.0 2.4
2.0
2.5
2.1
2.7
2.1
2.8
2.3
2.9
2.2
3.1
2.2
3.3
2.2
37.5 2.4
2.0
2.5
2.1
2.6
2.1
2.7
2.2
2.8
2.2
3.0
2.2
3.2
2.2
40.0 2.3
2.0
2.4
2.1
2.6
2.1
2.7
2.2
2.8
2.2
3.0
2.2
3.1
2.1
43.0 2.3
2.0
2.4
2.0
2.5
2.0
2.6
2.2
2.7
2.2
2.9
2.1
3.1
2.1
32
(3.6)
20.0 3.5
2.6
3.6
2.7
3.9
2.7
4.0
2.9
4.1
2.9
4.4
2.8
4.7
2.8
22.5 3.4
2.6
3.5
2.7
3.8
2.7
3.9
2.8
4.1
2.8
4.3
2.8
4.6
2.8
25.0 3.4
2.6
3.5
2.7
3.7
2.7
3.9
2.8
4.0
2.8
4.3
2.8
4.5
2.7
27.5 3.3
2.5
3.4
2.6
3.7
2.6
3.8
2.8
3.9
2.8
4.2
2.8
4.5
2.7
30.0 3.2
2.5
3.4
2.6
3.6
2.6
3.7
2.8
3.9
2.7
4.1
2.7
4.4
2.7
32.5 3.2
2.5
3.3
2.6
3.5
2.6
3.7
2.7
3.8
2.7
4.0
2.7
4.3
2.7
35.0 3.1
2.5
3.2
2.5
3.5
2.5
3.6
2.7
3.7
2.7
4.0
2.7
4.2
2.6
37.5 3.1
2.4
3.2
2.5
3.4
2.5
3.5
2.7
3.6
2.7
3.9
2.6
4.1
2.6
40.0 3.0
2.4
3.1
2.5
3.3
2.5
3.4
2.6
3.6
2.6
3.8
2.6
4.0
2.6
43.0 2.9
2.4
3.0
2.4
3.2
2.4
3.4
2.6
3.5
2.6
3.7
2.6
3.9
2.5
40
(4.5)
20.0 4.3
3.1
4.5
3.2
4.8
3.2
5.0
3.3
5.2
3.3
5.5
3.3
5.9
3.3
22.5 4.3
3.0
4.4
3.1
4.7
3.1
4.9
3.3
5.1
3.3
5.4
3.3
5.8
3.2
25.0 4.2
3.0
4.3
3.1
4.7
3.1
4.8
3.3
5.0
3.3
5.3
3.2
5.7
3.2
27.5 4.1
3.0
4.3
3.1
4.6
3.0
4.7
3.2
4.9
3.2
5.2
3.2
5.6
3.1
30.0 4.1
2.9
4.2
3.0
4.5
3.0
4.7
3.2
4.8
3.2
5.1
3.1
5.5
3.1
32.5 4.0
2.9
4.1
3.0
4.4
3.0
4.6
3.1
4.7
3.1
5.0
3.1
5.4
3.1
35.0 3.9
2.9
4.0
2.9
4.3
2.9
4.5
3.1
4.6
3.1
4.9
3.1
5.3
3.0
37.5 3.8
2.8
4.0
2.9
4.2
2.9
4.4
3.1
4.5
3.1
4.8
3.0
5.2
3.0
40.0 3.8
2.8
3.9
2.9
4.2
2.9
4.3
3.0
4.5
3.0
4.8
3.0
5.1
2.9
43.0 3.7
2.7
3.8
2.8
4.1
2.8
4.2
3.0
4.3
3.0
4.6
2.9
4.9
2.9
kcal/h=kW x 860 , BTU/h = kW x 3,412