2. M-NET control
SYSTEM DESIGN
264
2-4-3-6. ME remote controller, Multi-refrigerant-system, System Controller at TB 7side, LOSSNAY, Booster for long M-NET wiring
1. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME RC consume the M-NET power for transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to
2-3 "System configuration restrictions".
NOTE:
2. Indoor units should be set with a branch number.
3. Assign an address to each of the sub BC controllers which equals the sum of the smallest address of the indoor
units that are connected to each sub BC controller and 50.
When the address assigned to sub BC controller overlaps those of any other units including outdoor units (OC/OS) or main BC controller,
sub BC controller will be given priority to have the address.
Indoor unit
ME R/C ME R/C
*1 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
For AG-150A, 24VDC should be used with the PAC-SC51KUA.
01
02
03
30
TB5
BC controller
(Main)
52
TB02
BC controller
(Sub)
80
TB02
BC controller
TB02
TB5
TB5
TB2
Transmission Booster
PAC-SF46EPA
TB5
TB3
ME R/C ME R/C
PZ-60
DR-E
Indoor unit
ME R/C
ME R/C
PZ-52SF-E
142
144
145
195
130
180
143
*1
41
92
42
43
44
45
TB5
TB5
LOSSNAY
TB5
TB5
TB5
ME R/C
141
ME R/C
101
ME R/C
102
Group 2
Group 1
Group 21
Group 32
Group 33
Group 31
Group 34
Group 35
TB7
TB7
TB7
TB3
TB2
000 or 201
Power supply unit
(PAC-SC51KUA)
51
OC
PURY
SC
TB3
91
OC
PURY
TB3
97
OC
CN41
CN40
CN41
CN40
CN41
CN40
ON
DipSW2-1
ON
DipSW2-1
ON
DipSW2-1
PURY
2-4-3-7. Example : BC, BC sub
NOTE
• Indoor units should be set with a branch number.
• BC (main) address = O/U a 1
• BC (sub) address = Lowest address within the indoor units connected to the BC controller (sub) + 50
• If applicable, set the sub BC controllers in an PURY system in the following order:
(1) Indoor unit to be connected to the BC controller (Main)
(2) Indoor unit to be connected to the BC controller (No.1 Sub)
(3) Indoor unit to be connected to the BC controller (No.2 Sub)
Set the address so that (1)<(2)<(3)
OC
BC controllers
Group 1
51
TB3
TB02
TB5
TB5
TB5
TB5
TB5
TB5
TB5
TB5
TB02
TB02
01
02
03
101
Group 3
Group 2
04
05
06
104
106
52
54
CMB-V-GB1(No.1 sub)
BC controllers
: M-NET wiring
CMB-V-GA1(main)
DipSW2-1
OFF
CN41
CN40
: Piping
Group 4
07
08
107
57
CMB-V-GB1(No.2 sub)
BC controllers
PURY
46
TB5
TM4
LOSSNAY
Group 36
Summary of Contents for PUHY-RP-Y(S)JM-B
Page 1: ...DATA BOOK AIR CONDITIONERS MODEL PUHY RP Y S JM B PURY RP YJM B ...
Page 3: ......
Page 63: ...60 OUTDOOR UNITS ...
Page 191: ...188 INDOOR UNITS ...
Page 243: ...240 SYSTEM DESIGN ...
Page 287: ...284 SYSTEM DESIGN ...