4. Outdoor Installation
SYSTEM DESIGN
234
4-3-5. Refrigerant pipe routing
4-3-4. Installation
· RP200-RP350
Installation base perpendicular to the unit’s front panel
When the pipes and/or cables are routed at the bottom of the unit, make sure that the through hole at the base of
the unit does not get blocked with the installation base.
When the pipes are routed at the bottom of the unit, the base should
Model
㧭
PUHY-RP200YJM-B(-BS)
PUHY-RP250YJM-B(-BS) 145
[5-23/32]
PUHY-RP300YJM-B(-BS)
PUHY-RP350YJM-B(-BS) 150
[5-29/32]
be at least 100 mm [3-15/16 in.] in height.
(Unit : mm [in.])
221 150
86 [3-13/32]
92 [3-5/8]
145 [5-23/32]
A
(Mounting pitch)
(Mounting pitch)
2X2-14X20 Oval hole
Refrigerant service
valve <gas>
Refrigerant service
valve <liquid>
(760 [29-15/16])
80
760 [29-15/16]
80
18
18
131
83
251
186
Bottom view
724(721 727)
[5-3/16]
[23/32]
[23/32]
[28-13/32~28-5/8]
[3-5/32]
[3-5/32]
[7-11/32]
[9-29/32] [3-9/32]
[8-23/32] [5-29/32]
The gaps around the edges of through holes for pipes and wires on the
unit allow water or mice to enter the unit and damage its parts. Close
these gaps with filler plates.
This unit allows two types of pipe routing:
• Bottom piping
• Front piping
To prevent small animals, water, and snow from
entering the unit and damage its parts, close the
gap around the edges of through holes for pipes
and wires with filler plates.
CAUTION
Fill the gap at the site
Filler plate
(not supplied)