 271

3. Piping Design

SYSTEM DESIGN

3. Piping Design

3-1. Piping Design

3-1-1. IF 16 ports or less are in use, I.e., if only one BC controller is in use with no sub BC controller

Table 

3-1-1-1

. Piping length limitation

Table3-1-1-2. Bent equivalent length "M"

Item

Piping in the figure

Max. length

Max. equivalent length

Outdoor Model

M (m/bent)

Total piping length

A+B+a+b+c+d

220 *1

PUHY-RP200YJM-B

0.35

Farthest IU from OU

A+B+d

100 (90) *2

125 (115)

PUHY-RP250YJM-B

0.42

Distance between OU and BC

A

70 (60) *2

PUHY-RP300YJM-B

0.42

Farthest IU from BC controller

B+d

30

Heignt between OU and IU (OU above IU) H

50

Heignt between OU and IU (OU under IU) H'

40

Height between IU and BC

h1

15 (10) *3
15 (10) *3

Height between IU and IU

h2

Table3-1-1-3. Piping "A"size selection rule

(mm [in.])

(m)

Outdoor Model

Pipe(High pressure)

Pipe(Low pressure)

RP200YJM

ø19.05 [3/4"]

ø28.58 [1-1/8"] *4

RP250YJM

ø19.05 [3/4"]

ø28.58 [1-1/8"]

RP300YJM

ø19.05 [3/4"]

ø28.58 [1-1/8"]

Table3-1-1-4. Piping "B" size seleciton rule

(mm [in.])

Total down-stream Indoor capacity

Pipe(Liquid)

Pipe(Gas)

P80 or less

ø9.52 [3/8"]

ø15.88 [5/8"]

P81 or more

ø12.7 [1/2"]

ø19.05 [3/4"]

Table3-1-1-5. Piping "a", "b", "c", "d" size selection rule (mm [in.])

Indoor Unit size

Pipe(Liquid)

Pipe(Gas)

P15 to P40, GUF-50RD(H)

ø6.35 [1/4"]

ø12.70 [1/2"]

P50 to P80, GUF-100RD(H)

ø9.52 [3/8"]

ø15.88 [5/8"]

P200

ø12.7 [1/2"]

ø25.4 [1"] or
ø28.58 [1-1/8"]

ø9.52 [3/8"]

ø19.05 [3/4"]

P250

ø12.7 [1/2"]

ø28.58 [1-1/8"]

P100 to P140

Note1. No Header usable on PURY system.
Note2. Indoor unit sized P100-P250 should be connected to BC controller via Y shape joint CMY-R160-J1 ;
Note3. Indoor unit sized P100-P250 does NOT share BC controller ports with other Indoor units ;
Note4. As bents cause pressure loss on transportation of  refrigerant, fewer bents design is better ;

Piping length needs to consider the actual length and equivalent length which bents are counted.
Equivalent piping length (m)=Actual piping "M" x Quantity of bent.

Note5. Set DIP-SW 4-6 to ON of BC controller, in case of connected Indoor unit sized P100-P140 with 2 ports.
Note6. It is also possible to connect Indoor unit sized P100-P140 with 1 port (set DIP-SW 4-6 to OFF).

Note7. Individual indoor units grouped together to connect to the BC controller via one port cannot operate

individually in heating and cooling modes at the same time. I.e., they must all function in either heating

However, the cooling capacity decreases a little (For details, refer to the chapter OUTDOOR UNITS,
R2 SERIES, 6-4. Correction by port counts of the BC controller).

or cooling together.

Note8. Indoor capactiy is described as its model size. For example, PEFY-P63VML-E, its capacity is P63.

Note9. Total down-stream Indoor capacity is the summary of the model size of Indoors down-stream.

For example, PEFY-P63VML-E + PEFY-P32VML-E : Total Indoor capacity = P63 + P32 = P95.

OU : Outdoor Unit ; IU : Indoor Unit 

(P100-250)

BC controller

a

b

H

H'

h1

IU

(P15-P80)

Joint
(CMY-R160-J1)

IU

Joint

Max.3 sets for 1 port.
Total capacity <= P80

B

c

d

IU

A

OU

Reducer (P15~P50)

(attached with BC controller)

IU

h2

For outodoor units equal to or larger than a size P400, on
the BC controller please ensure CMB-P

V-GA1 is used.

S

T

M

N

CMY-R160-J1

(

Gas 

side)

IU

CMY-R160-J1

(

Liquid 

side)

BC controller

Fig. 3-1-1AA

Fig. 3-1-1A Piping scheme

(T)ø19.05ID

(N)ø9.52ID

(M)ø3/8"(Brazing)

(M)ø3/8"(Brazing)

(S)ø5/8"(Brazing)

(S)ø5/8"(Brazing)

226

226

Joint CMY-R160-J1 Gas side

Joint CMY-R160-J1 Liquid side

* 1  Do not exceed the amount of refrigerant to be charged written below.
       PURY-RP200-300YJM-B : 0.16 × L

1

 + 0.11 × L

2

 + 0.12 × L

3

 + 0.06 × L

4

 + 0.024 × L

5

 < 20

      

       L

1

: Total length of ø19.05 high pressure pipe (m)

       L

2

: Total length of ø15.88 high pressure pipe (m)

       L

3

: Total length of ø12.7 liquid pipe (m)

       L

4

: Total length of ø9.52 liquid pipe (m)

       L

5

: Total length of ø6.35 liquid pipe (m)

* 2 The value in (   ) in the table is applied when indoor total capacity exceeds 130% of 
      outdoor unit capacity.
* 3 Distance of indoor unit size P200, P250 from BC must be less than 10 m, if any.

* 4 ø25.4 for R22

Summary of Contents for PUHY-RP-Y(S)JM-B

Page 1: ...DATA BOOK AIR CONDITIONERS MODEL PUHY RP Y S JM B PURY RP YJM B ...

Page 2: ...REPLACE MULTI 1 OUTDOOR UNIT Y SERIES 1 R2 SERIES 61 2 CAPACITY TABLES Indoor unit 87 3 SYSTEM DESIGN Y SERIES 189 R2 SERIES 241 4 CONTROLLER 285 ...

Page 3: ......

Page 4: ...ITY TABLES 25 6 1 Correction by temperature 25 6 2 Correction by total indoor 39 6 3 Correction by refrigerant piping length 43 6 4 Correction at frost and defrost 46 6 5 Operation temperature range 47 7 OPTIONAL PARTS 48 7 1 OUTDOOR TWINNING KIT 48 8 UNIT SELECTION 49 8 1 Indoor and outdoor unit selection 49 8 2 Calculation samples 51 8 3 Pipe diameter correction factor 54 ...

Page 5: ...D mm 1 710 1 650 without legs x 920 x 760 1 710 1 650 without legs x 920 x 760 in 67 3 8 65 without legs x 36 1 4 x 29 15 16 67 3 8 65 without legs x 36 1 4 x 29 15 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi Inverter circuit COMP FAN Over heat protection Ove...

Page 6: ...10 1 650 without legs x 920 x 760 1 710 1 650 without legs x 920 x 760 in 67 3 8 65 without legs x 36 1 4 x 29 15 16 67 3 8 65 without legs x 36 1 4 x 29 15 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi Inverter circuit COMP FAN Over heat protection Over curren...

Page 7: ... x 36 1 4 x 29 15 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi Inverter circuit COMP FAN Over heat protection Over current protection Over heat protection Over current protection Compressor Over heat protection Over heat protection Fan motor Thermal switch The...

Page 8: ...gs x 36 1 4 x 29 15 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi Inverter circuit COMP FAN Over heat protection Over current protection Over heat protection Over current protection Compressor Over heat protection Over heat protection Fan motor Thermal switch T...

Page 9: ...s x 36 1 4 x 29 15 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi Inverter circuit COMP FAN Over heat protection Over current protection Over heat protection Over current protection Compressor Over heat protection Over heat protection Fan motor Thermal switch Th...

Page 10: ...s x 36 1 4 x 29 15 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi Inverter circuit COMP FAN Over heat protection Over current protection Over heat protection Over current protection Compressor Over heat protection Over heat protection Fan motor Thermal switch Th...

Page 11: ...s x 36 1 4 x 29 15 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi Inverter circuit COMP FAN Over heat protection Over current protection Over heat protection Over current protection Compressor Over heat protection Over heat protection Fan motor Thermal switch Th...

Page 12: ...s x 36 1 4 x 29 15 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi Inverter circuit COMP FAN Over heat protection Over current protection Over heat protection Over current protection Compressor Over heat protection Over heat protection Fan motor Thermal switch Th...

Page 13: ...hout legs x 36 1 4 x 29 15 16 67 3 8 65 without legs x 36 1 4 x 29 15 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi Inverter circuit COMP FAN Over heat protection Over current pro tection Over...

Page 14: ...out legs x 36 1 4 x 29 15 16 67 3 8 65 without legs x 36 1 4 x 29 15 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi Inverter circuit COMP FAN Over heat protection Over current pro tection Over ...

Page 15: ...thout legs x 36 1 4 x 29 15 16 67 3 8 65 without legs x 36 1 4 x 29 15 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi Inverter circuit COMP FAN Over heat protection Over current pro tection Ove...

Page 16: ...thout legs x 36 1 4 x 29 15 16 67 3 8 65 without legs x 36 1 4 x 29 15 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi Inverter circuit COMP FAN Over heat protection Over current pro tection Ove...

Page 17: ...hout legs x 36 1 4 x 29 15 16 67 3 8 65 without legs x 36 1 4 x 29 15 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi High pressure sensor High pressure switch at 4 15 3 3MPa 601 479 psi Inverter circuit COMP FAN Over heat protection Over current pro tection Over...

Page 18: ... necessary spacing around the unit and foundation work 2 The detachable leg can be removed at site 3 At brazing of pipes wrap the refrigerant service valve with wet cloth and keep the temperature of refrigerant service valve under 120 C Accessories Connecting pipe Gas Elbow IDø25 4 ODø25 4 Pipe IDø25 4 ODø19 05 Pipe IDø25 4 ODø22 2 Pipe IDø25 4 ODø28 58 Pipe IDø25 4 ODø34 93 Liquid Pipe IDø9 52 OD...

Page 19: ...ltiple units are installed adjacent to each other secure enough space to allow for air circulation and walkway between groups of units as shown in the figures below At least two sides must be left open As with the single installation add the height that exceeds the height limit h to the figures that are marked with an asterisk If there is a wall at both the front and the rear of the unit install u...

Page 20: ...7 RP250 PUHY RP300YJM B BS PUHY RP350YJM B BS PUHY RP650YSJM B BS PUHY RP300YJM B BS PUHY RP300YJM B BS PUHY RP600YSJM B BS PUHY RP250YJM B BS PUHY RP300YJM B BS PUHY RP550YSJM B BS PUHY RP250YJM B BS PUHY RP250YJM B BS PUHY RP500YSJM B BS PUHY RP200YJM B BS PUHY RP250YJM B BS PUHY RP450YSJM B BS Twinning pipe Outdoor unit d or f Gas Liquid c or e RP200 Unit model b Gas Liquid Outdoor unit 1 ø9 52...

Page 21: ...B BS Liquid PUHY RP250YJM B BS Outdoor unit 3 PUHY RP300YJM B BS Outdoor unit 1 PUHY RP800YSJM B BS Outdoor unit 2 Component unit name PUHY RP250YJM B BS PUHY RP250YJM B BS PUHY RP250YJM B BS Package unit name Outdoor Twinning Kit optional parts Indoor unit Twinning pipe 2 PUHY RP250YJM B BS Twinning pipe 1 Twinning pipe 2 PUHY RP750YSJM B BS PUHY RP200YJM B BS PUHY RP300YJM B BS PUHY RP300YJM B B...

Page 22: ...ITS 3 CENTER OF GRAVITY PUHY RP200 RP250 RP300 RP350YJM B BS 760 80 Y 724 1410 Z 920 X 760 Model X Y Z Unit mm 330 337 550 325 342 550 325 352 550 325 352 550 PUHY RP200YJM B BS PUHY RP250YJM B BS PUHY RP300YJM B BS PUHY RP350YJM B BS ...

Page 23: ...SV1a Z3 2 1 M NET power supply circuit C5 LED3 CPU in operation LED1 Normal operation SC L1 SC L2 1 2 W U SC W 1 Z5 R1 R2 R3 C3 C2 F3 F2 F1 Z1 Z2 R4 D1 R5 R6 C11 DB1 C7 C8 C9 C10 C4 C1 C6 Power Source 3N 50 60Hz 380 400 415V N L3 L2 L1 TB1 N L3 L2 L1 L F4 AC250V 6 3A T black white red 3 1 CN3 green TB24 N TB23 L3 TB22 L2 TB21 L1 CN1B 4 1 3 1 CN1A U U U F1 F2 F3 AC250V 6 3A T U Z4 DSA CN2 6 5 3 1 N...

Page 24: ...nd central frequency Hz Octave band sound level dB Approximate minimum audible limit on continuous noise Stand 50 60Hz Low 50 60Hz Sound level of PUHY RP200YJM B BS 63 125 250 500 1k 2k 4k 8k dB A Standard 50 60Hz 62 0 65 0 63 0 57 0 53 5 49 0 48 0 42 0 60 0 Low noise mode 50 60Hz 62 0 54 0 48 5 46 0 41 5 40 0 41 5 39 5 50 0 When Low noise mode is set the A C system s capacity is limited The syste...

Page 25: ...0 5 38 0 51 0 When Low noise mode is set the A C system s capacity is limited The system could return to normal operation from Low noise mode automatically in the case that the operation condition is severe 10 20 30 40 50 60 70 80 90 63 125 250 500 1k 2k 4k 8k NC 40 NC 30 NC 20 NC 60 NC 50 NC 70 Octave band central frequency Hz Octave band sound level dB Approximate minimum audible limit on contin...

Page 26: ...A C system s capacity is limited The system could return to normal operation from Low noise mode automatically in the case that the operation condition is severe 10 20 30 40 50 60 70 80 90 63 125 250 500 1k 2k 4k 8k NC 40 NC 30 NC 20 NC 60 NC 50 NC 70 Octave band central frequency Hz Octave band sound level dB Approximate minimum audible limit on continuous noise Stand 50 60Hz Low 50 60Hz Sound le...

Page 27: ...0 41 0 53 5 When Low noise mode is set the A C system s capacity is limited The system could return to normal operation from Low noise mode automatically in the case that the operation condition is severe 10 20 30 40 50 60 70 80 90 63 125 250 500 1k 2k 4k 8k NC 40 NC 30 NC 20 NC 60 NC 50 NC 70 Octave band central frequency Hz Octave band sound level dB Approximate minimum audible limit on continuo...

Page 28: ...1 4 1 1 0 9 0 6 0 8 0 5 0 7 0 4 1 0 Ratio of heating capacity Ratio of heating capacity and power input 4 5 14 23 32 41 50 59 20 15 10 5 0 5 10 15 FWB CWB Outdoor Temperature Indoor Temperature 15 CDB 59 FDB 20 CDB 68 FDB 25 CDB 77 FDB 27 CDB 80 FDB 15 CDB 59 FDB 20 CDB 68 FDB 25 CDB 77 FDB 27 CDB 80 FDB PUHY PUHY 5 23 0 32 5 41 10 50 15 59 20 68 25 77 30 86 35 95 40 104 45 113 CDB FDB Outdoor Tem...

Page 29: ... 0 Ratio of heating capacity Ratio of heating capacity and power input 4 5 14 23 32 41 50 59 20 15 10 5 0 5 10 15 FWB CWB Outdoor Temperature Indoor Temperature 15 CDB 59 FDB 20 CDB 68 FDB 25 CDB 77 FDB 27 CDB 80 FDB 15 CDB 59 FDB 20 CDB 68 FDB 25 CDB 77 FDB 27 CDB 80 FDB 5 23 0 32 5 41 10 50 15 59 20 68 25 77 30 86 35 95 40 104 45 113 CDB FDB Outdoor Temperature 0 6 0 8 0 9 1 0 1 2 1 1 0 7 0 6 0 ...

Page 30: ...B PUHY 0 8 0 9 1 0 1 1 1 2 1 3 1 4 0 7 0 6 0 5 0 4 Ratio of power input 1 2 1 3 1 4 1 1 0 9 0 6 0 8 0 5 0 7 0 4 1 0 Ratio of heating capacity Ratio of heating capacity and power input 4 5 14 23 32 41 50 59 20 15 10 5 0 5 10 15 FWB CWB Outdoor Temperature Indoor Temperature 15 CDB 59 FDB 20 CDB 68 FDB 25 CDB 77 FDB 27 CDB 80 FDB 15 CDB 59 FDB 20 CDB 68 FDB 25 CDB 77 FDB 27 CDB 80 FDB 5 23 0 32 5 41...

Page 31: ...ing capacity Ratio of heating capacity and power input 4 5 14 23 32 41 50 59 20 15 10 5 0 5 10 15 FWB CWB Outdoor Temperature Indoor Temperature 15 CDB 59 FDB 20 CDB 68 FDB 25 CDB 77 FDB 27 CDB 80 FDB 15 CDB 59 FDB 20 CDB 68 FDB 25 CDB 77 FDB 27 CDB 80 FDB PUHY PUHY PUHY PUHY 5 23 0 32 5 41 10 50 15 59 20 68 25 77 30 86 35 95 40 104 45 113 CDB FDB Outdoor Temperature 0 6 0 8 0 9 1 0 1 2 1 1 0 7 0 ...

Page 32: ... Input kW BTU h kW Nominal Heating Capacity Input kW BTU h kW 96 0 327 600 27 11 101 0 344 600 28 29 108 0 368 500 26 47 113 0 385 600 28 39 PUHY RP850YSJM B RP900YSJM B PUHY RP850YSJM B RP900YSJM B 5 23 0 32 5 41 10 50 15 59 20 68 25 77 30 86 35 95 40 104 45 113 CDB FDB Outdoor Temperature 0 6 0 7 0 8 0 9 1 1 1 0 0 6 0 5 0 4 0 3 Ratio of power input 1 3 1 4 1 2 1 0 0 9 0 8 0 7 1 1 Ratio of coolin...

Page 33: ... 1 0 1 1 1 2 0 7 0 6 0 5 0 4 Ratio of power input 1 2 1 3 1 4 1 1 0 9 0 6 0 8 0 5 0 7 0 4 1 0 Ratio of heating capacity Ratio of heating capacity and power input 4 5 14 23 32 41 50 59 20 15 10 5 0 5 10 15 FWB CWB Outdoor Temperature Indoor Temperature 24 CWB 75 FWB 22 CWB 72 FWB 20 CWB 68 FWB 18 CWB 64 FWB 16 CWB 61 FWB 15 CWB 59 FWB 24 CWB 75 FWB 22 CWB 72 FWB 20 CWB 68 FWB 18 CWB 64 FWB 16 CWB 6...

Page 34: ...or Temperature 24 CWB 75 FWB 22 CWB 72 FWB 20 CWB 68 FWB 18 CWB 64 FWB 16 CWB 61 FWB 15 CWB 59 FWB 24 CWB 75 FWB 22 CWB 72 FWB 20 CWB 68 FWB 18 CWB 64 FWB 16 CWB 61 FWB 15 CWB 59 FWB 15 CDB 59 FDB 20 CDB 68 FDB 25 CDB 77 FDB 27 CDB 80 FDB 15 CDB 59 FDB 20 CDB 68 FDB 25 CDB 77 FDB 27 CDB 80 FDB PUHY RP300YJM B RP350YJM B PUHY RP300YJM B RP350YJM B PUHY RP400YSJM B PUHY RP400YSJM B 33 5 114 300 8 98...

Page 35: ...2 CWB 72 FWB 20 CWB 68 FWB 18 CWB 64 FWB 16 CWB 61 FWB 15 CWB 59 FWB 15 CDB 59 FDB 20 CDB 68 FDB 25 CDB 77 FDB 27 CDB 80 FDB 15 CDB 59 FDB 20 CDB 68 FDB 25 CDB 77 FDB 27 CDB 80 FDB Nominal Cooling Capacity Input kW BTU h kW Nominal Heating Capacity Input kW BTU h kW Nominal Cooling Capacity Input kW BTU h kW Nominal Heating Capacity Input kW BTU h kW Nominal Cooling Capacity Input kW BTU h kW Nomi...

Page 36: ...mperature 24 CWB 75 FWB 22 CWB 72 FWB 20 CWB 68 FWB 18 CWB 64 FWB 16 CWB 61 FWB 15 CWB 59 FWB 24 CWB 75 FWB 22 CWB 72 FWB 20 CWB 68 FWB 18 CWB 64 FWB 16 CWB 61 FWB 15 CWB 59 FWB 15 CDB 59 FDB 20 CDB 68 FDB 25 CDB 77 FDB 27 CDB 80 FDB 15 CDB 59 FDB 20 CDB 68 FDB 25 CDB 77 FDB 27 CDB 80 FDB Nominal Cooling Capacity Input kW BTU h kW Nominal Heating Capacity Input kW BTU h kW Nominal Cooling Capacity...

Page 37: ...5 14 23 32 41 50 59 20 15 10 5 0 5 10 15 FWB CWB Outdoor Temperature Indoor Temperature 24 CWB 75 FWB 22 CWB 72 FWB 20 CWB 68 FWB 18 CWB 64 FWB 16 CWB 61 FWB 15 CWB 59 FWB 24 CWB 75 FWB 22 CWB 72 FWB 20 CWB 68 FWB 18 CWB 64 FWB 16 CWB 61 FWB 15 CWB 59 FWB 15 CDB 59 FDB 20 CDB 68 FDB 25 CDB 77 FDB 27 CDB 80 FDB 15 CDB 59 FDB 20 CDB 68 FDB 25 CDB 77 FDB 27 CDB 80 FDB Nominal Cooling Capacity Input k...

Page 38: ... 0 4 1 0 Ratio of heating capacity Ratio of heating capacity and power input 4 5 14 23 32 41 50 59 20 15 10 5 0 5 10 15 68 20 77 25 86 30 FWB CWB Outdoor Temperature HEX unit inlet water temperature HEX unit inlet water temperature 35 C 95 F 30 C 86 F 25 C 77 F 20 C 68 F 15 C 59 F 10 C 50 F 35 C 95 F 30 C 86 F 25 C 77 F 20 C 68 F 15 C 59 F 10 C 50 F 10 C 50 F 20 C 68 F 30 C 86 F 35 C 95 F 40 C 104...

Page 39: ... 15 68 20 77 25 86 30 FWB CWB Outdoor Temperature HEX unit inlet water temperature HEX unit inlet water temperature 35 C 95 F 30 C 86 F 25 C 77 F 20 C 68 F 15 C 59 F 10 C 50 F 35 C 95 F 30 C 86 F 25 C 77 F 20 C 68 F 15 C 59 F 10 C 50 F 10 C 50 F 20 C 68 F 30 C 86 F 35 C 95 F 40 C 104 F 10 C 50 F 20 C 68 F 30 C 86 F 35 C 95 F 40 C 104 F Nominal Cooling Capacity Input kW BTU h kW Nominal Heating Cap...

Page 40: ...e 35 C 95 F 30 C 86 F 25 C 77 F 20 C 68 F 15 C 59 F 10 C 50 F 35 C 95 F 30 C 86 F 25 C 77 F 20 C 68 F 15 C 59 F 10 C 50 F 10 C 50 F 20 C 68 F 30 C 86 F 35 C 95 F 40 C 104 F 10 C 50 F 20 C 68 F 30 C 86 F 35 C 95 F 40 C 104 F Nominal Cooling Capacity Input kW BTU h kW Nominal Heating Capacity Input kW BTU h kW PUHY RP450YSJM B RP500YSJM B PUHY RP450YSJM B RP500YSJM B 50 0 170 600 13 77 56 0 191 100 ...

Page 41: ...35 C 95 F 30 C 86 F 25 C 77 F 20 C 68 F 15 C 59 F 10 C 50 F 35 C 95 F 30 C 86 F 25 C 77 F 20 C 68 F 15 C 59 F 10 C 50 F 10 C 50 F 20 C 68 F 30 C 86 F 35 C 95 F 40 C 104 F 10 C 50 F 20 C 68 F 30 C 86 F 35 C 95 F 40 C 104 F Nominal Cooling Capacity Input kW BTU h kW Nominal Heating Capacity Input kW BTU h kW PUHY RP700YSJM B RP750YSJM B PUHY RP700YSJM B RP750YSJM B 80 0 273 000 22 22 85 0 290 000 24...

Page 42: ...nd to ensure the system is installed with enough capacity for a particular application Capacity kW Input kW Total capacity of indoor units 10 0 10 0 20 0 30 0 40 0 50 0 0 0 5 0 50 100 200 300 150 250 350 100 200 300 400 500 Capacity kW Input kW Total capacity of indoor units 10 0 20 0 30 0 40 0 50 0 2 5 5 0 10 0 15 0 7 5 12 5 RP200 RP250 PUHY RP200 250YJM B BS PUHY RP300 350YJM B BS Cooling Heatin...

Page 43: ...0 0 40 0 50 0 60 0 0 0 5 0 200 300 400 500 600 700 800 Capacity kW Input kW Total capacity of indoor units 30 0 40 0 50 0 60 0 70 0 0 0 5 0 15 0 20 0 10 0 200 300 400 500 600 Cooling Heating Cooling Heating Cooling Heating Cooling Heating RP500 RP550 RP400 RP450 PUHY RP400 450YSJM B BS PUHY RP500 550YSJM B BS ...

Page 44: ... 0 90 0 0 0 10 0 200 300 400 500 600 700 800 900 300 400 500 600 700 800 900 1000 Capacity kW Input kW Total capacity of indoor units 40 0 20 0 60 0 80 0 100 0 120 0 0 0 10 0 30 0 20 0 RP600 RP650 PUHY RP600 650YSJM B BS PUHY RP700 750YSJM B BS Cooling Heating Cooling Heating Cooling Heating Cooling Heating RP700 RP750 ...

Page 45: ...00 0 120 0 0 0 10 0 40 0 30 0 400 600 800 1000 1400 1200 400 500 600 700 800 1200 900 1000 1100 Capacity kW Input kW Total capacity of indoor units 60 0 40 0 80 0 100 0 120 0 140 0 0 0 10 0 30 0 20 0 Cooling Heating Cooling Heating Cooling Heating RP900 RP800 RP850 PUHY RP800 850YSJM B BS PUHY RP900YSJM B BS ...

Page 46: ...ivalent length m Cooling capacity correction factor 125 188 250 325 0 70 0 75 0 80 0 85 0 90 0 95 1 0 20 40 60 80 100 120 140 Total capacity of indoor unit PUHY RP450YSJM B BS Piping equivalent length m Cooling capacity correction factor 225 338 450 585 0 75 0 80 0 85 0 90 0 95 1 0 20 40 60 80 100 120 140 Total capacity of indoor unit PUHY RP300YJM B BS Piping equivalent length m Cooling capacity ...

Page 47: ...al capacity of indoor unit PUHY RP850YSJM B BS Piping equivalent length m Cooling capacity correction factor 425 637 850 1105 0 70 0 75 0 80 0 85 0 90 0 95 1 0 20 40 60 80 100 120 Total capacity of indoor unit PUHY RP700YSJM B BS Piping equivalent length m Cooling capacity correction factor 350 525 700 910 0 70 0 75 0 80 0 85 0 90 0 95 1 0 20 40 60 80 100 120 Total capacity of indoor unit PUHY RP9...

Page 48: ...oor unit 0 70 x number of bent on the piping m 6 PUHY RP850 900YSJM B BS Equivalent length Actual piping length to the farthest indoor unit 0 80 x number of bent on the piping m PUHY RP200 250YJM B BS 0 20 40 60 80 100 120 140 Heating capacity correction factor 0 95 1 00 Piping equivalent length m 0 90 PUHY RP600 650YSJM B BS 0 20 40 60 80 100 120 Heating capacity correction factor 0 95 1 00 Pipin...

Page 49: ...0 93 0 85 0 83 0 84 0 86 0 90 0 90 0 95 0 95 0 95 PUHY RP400YSJM B BS 1 00 0 93 0 85 0 83 0 84 0 86 0 90 0 90 0 95 0 95 0 95 PUHY RP450YSJM B BS 1 00 0 93 0 85 0 83 0 84 0 86 0 90 0 90 0 95 0 95 0 95 PUHY RP500YSJM B BS 1 00 0 94 0 87 0 86 0 87 0 88 0 90 0 90 0 93 0 93 0 93 PUHY RP550YSJM B BS 1 00 0 94 0 87 0 86 0 87 0 88 0 90 0 90 0 93 0 93 0 93 PUHY RP600YSJM B BS 1 00 0 94 0 87 0 86 0 87 0 88 ...

Page 50: ... 0 5 10 15 20 25 30 35 40 45 50 4 5 14 23 32 41 50 59 68 77 86 95 104 113 122 4 5 14 23 32 41 50 59 68 77 86 95 104 113 122 Indoor temperature Outdoor temperature 30 25 20 15 10 5 86 77 68 59 50 41 86 77 68 59 50 41 20 15 10 5 0 5 10 15 20 25 30 35 40 45 50 Indoor temperature Outdoor temperature ...

Page 51: ...shed part Dot dashed part Dot dashed part Dot dashed part Note 2 The straight part of pipe Note 2 The straight part of pipe Note 2 The straight part of pipe Note 2 The straight part of pipe Distributer Distributer Distributer Pipe cover Pipe cover 663 OD ø25 4 ID ø22 2 ID ø22 2 OD ø25 4 ID ø28 58 ID ø19 05 62 62 ID ø19 05 OD ø22 2 62 2 pcs 162 69 2 pcs Distributer OD ø38 1 OD ø15 88 ID ø41 28 ID ø...

Page 52: ...erature and defrost heating Find the piping length correction factor from the diagram that corresponds to the total indoor unit capacity N 4 Make sure the maximum outdoor unit capacity Qm is equal to or greater than the total thermal load Qi If Qm is smaller than Qi reconsider the outdoor unit capacity X so that Qm Qi will hold true 5 After selecting indoor and outdoor units calculate the apportio...

Page 53: ...y x return air temperature correction factor The standard outside air temperatures used to obtain the return air temperature correction factor is 35ºCDB for cooling and 6ºCWB for heating If non standard size pipes are connected use the pipe diameter correction factors for the main pipes merge pipes and branch pipes When deciding the outside air temperature to calculate unit capacity requirements t...

Page 54: ... bulb temperature of 20ºC defrost correction factor is 0 965 piping length is 50 m and capacity correction factor is 0 975 The result shows that the Maximum outdoor unit capacity Qm 35 2 kW exceeds the heating load Qi 29 kW c You can now check to see if this value will meet the capacity requirement for each indoor unit by using the following formula 35 2 x 125 250 x 0 96 16 8 kW where the indoor u...

Page 55: ...0 model outdoor unit can be selected a The standard capacity Qs of the tentatively selected during cooling load calculation 300 model outdoor unit is 37 5 kW The standard capacity Qs is corrected for indoor outside air temperatures and piping length to obtain the maximum outdoor unit capacity Qm as follows Qm 37 5 x 1 00 x 0 975 x 0 975 x 0 98 34 9 kW The result shows that the Maximum outdoor unit...

Page 56: ...ing and heating Select the outdoor unit capacity X Select the outdoor unit one rank higher in capacity Apportion the corrected outdoor unit capacity Qm to each indoor unit Multiply the apportioned capacity by the indoor unit temperature correction factor and make sure it is equal to or greater than the thermal load Thermal load Qi Corrected capacity Qm YES NO Correct the standard outdoor unit capa...

Page 57: ...ction factor PUHY RP350YJM B 0 20 40 60 80 100 Equivalent main piping length m Ø22 2 Ø25 4 1 0 90 0 80 0 60 0 70 Pipe diameter correction factor PUHY RP250YJM B 0 20 40 60 80 100 Equivalent main piping length m Ø28 58 1 0 90 0 80 0 60 0 70 Pipe diameter correction factor PUHY RP400YSJM B 0 20 40 60 80 100 Equivalent main piping length m Ø22 2 Ø25 4 1 0 90 0 80 0 60 0 70 Pipe diameter correction fa...

Page 58: ...lent main piping length m Ø28 58 1 0 90 0 80 0 60 0 70 Pipe diameter correction factor PUHY RP550YSJM B 0 20 40 60 80 100 Equivalent main piping length m Ø34 93 1 0 90 0 80 0 60 0 70 Pipe diameter correction factor PUHY RP700YSJM B 0 20 40 60 80 100 Ø28 58 Equivalent main piping length m 1 0 90 0 80 0 60 0 70 Pipe diameter correction factor PUHY RP600YSJM B 0 20 40 60 80 100 Equivalent main piping...

Page 59: ...8 UNIT SELECTION OUTDOOR UNITS 56 Ø34 93 Equivalent main piping length m 1 0 90 0 80 0 60 0 70 Pipe diameter correction factor PUHY RP800YSJM B 0 20 40 60 80 100 ...

Page 60: ...ipe diameter correction factor P50 0 10 40 20 30 Ø25 4 Ø22 2 Branch piping length m 1 0 90 0 80 Pipe diameter correction factor P250 0 10 40 20 30 Ø15 88 Branch piping length m 1 0 90 0 80 Pipe diameter correction factor P100 P125 P140 0 10 40 20 30 Ø22 2 Ø19 05 Branch piping length m 1 0 90 0 80 Pipe diameter correction factor P200 0 10 40 20 30 ...

Page 61: ...diameter correction factor Ø28 58 P331 P400 0 10 40 20 30 Equivalent main piping length m Ø22 2 Ø19 05 1 0 90 0 80 Pipe diameter correction factor P161 P200 0 10 40 20 30 Equivalent main piping length m Ø28 58 1 0 90 0 80 Pipe diameter correction factor P401 P630 0 10 40 20 30 Equivalent main piping length m Ø22 2 1 0 90 0 80 Pipe diameter correction factor P201 P300 0 10 40 20 30 Equivalent main ...

Page 62: ...59 8 UNIT SELECTION OUTDOOR UNITS Equivalent main piping length m Ø34 93 1 0 90 0 80 Pipe diameter correction factor P651 P800 0 10 40 20 30 ...

Page 63: ...60 OUTDOOR UNITS ...

Page 64: ...TY TABLES 69 6 1 Correction by temperature 69 6 2 Correction by total indoor 73 6 3 Correction by refrigerant piping length 74 6 4 Correction by port counts of the BC controller 76 6 5 Correction at frost and defrost 76 6 6 Operation temperature range 77 7 UNIT SELECTION 78 7 1 Indoor and outdoor unit selection 78 7 2 Calculation samples 80 7 3 Pipe diameter correction factor 83 ...

Page 65: ... 16 x 29 15 16 Protection devices High pressure protection High pressure sensor High pressure switch at 4 15 3 6MPa 601 522 psi High pressure sensor High pressure switch at 4 15 3 6MPa 601 522 psi Inverter circuit COMP FAN Over heat protection Over current protection Over heat protection Over current protection Compressor Discharge thermo protection Over current protection Discharge thermo protect...

Page 66: ... sensor High pressure switch at 4 15 3 6MPa 601 522 psi Inverter circuit COMP FAN Over heat protection Over current protection Compressor Discharge thermo protection Over current protection Fan motor Thermal switch Refrigerant Type x original charge R410A x 11 8kg 27lbs Control Indoor LEV and BC controller Net weight kg lbs 290 640 Heat exchanger Salt resistant cross fin copper tube HIC circuit HI...

Page 67: ... hole Front through hole Bottom through hole Front through hole front and back 2 points Note 2 Accessories Connecting pipe Low pressure Pipe IDø25 4 IDø28 58 1 pc Note 1 Please refer to the next page for information regarding necessary spacing around the unit and foundation work 2 The detachable leg can be removed at site 3 At brazing of pipes wrap the refrigerant service valve with wet cloth and ...

Page 68: ...the installation leg is securely supported as shown in the right figure Fig A B When using a rubber isolating cushion please ensure it is large enough to cover the entire width of each of the unit s legs The protrusion length of the anchor bolt must not exceed 30 mm Fig A B Use four fixing plates as shown in the right figure field supply required when using post installed anchor bolts Fig C D To p...

Page 69: ...ENTER OF GRAVITY OUTDOOR UNITS 66 3 CENTER OF GRAVITY PURY RP200 RP250 RP300YJM B BS 1060 80 Y 724 1470 Z 60 1220 X 760 Model X Y Z Unit mm 445 342 642 443 333 633 PURY RP200YJM B BS PURY RP250 300YJM B BS ...

Page 70: ...D1 Display setting LED2 CPU in operation C5 Z5 C3 C2 F2 R1 R2 3 3 Z24 1 Z25 CNTYP5 green CNTYP4 green 2 4 F1 CNTYP2 black R3 Z1 Z2 R34 C30 C32 C34 C36 2 1 3 63LS 63HS1 2 1 3 3 2 1 CN202 red CN201 2 10 OFF 1 TB1 black F3 N L3 L2 L1 F4 AC250V 6 3A T black white L F1 F2 F3 AC250V 6 3A T DSA R35 CT3 R4 white R33 SC L3 R30 U red white D1 1 R5 R32 red CNIT R6 CN2 3 1 2 C31 CN18V blue W 6 yellow CNS2 5 U...

Page 71: ...33 0 25 5 44 0 When Low noise mode is set the A C system s capacity is limited The system could return to normal operation from Low noise mode automatically in the case that the operation condition is severe 10 20 30 40 50 60 70 80 90 63 125 250 500 1k 2k 4k 8k NC 40 NC 30 NC 20 NC 60 NC 50 NC 70 Octave band central frequency Hz Octave band sound level dB Approximate minimum audible limit on conti...

Page 72: ...B 25 CDB 77 FDB 27 CDB 80 FDB 5 23 0 32 5 41 10 50 15 59 20 68 25 77 30 86 35 95 40 104 45 113 CDB FDB Outdoor Temperature 0 6 0 8 0 9 1 0 1 2 1 1 0 7 0 6 0 5 0 4 Ratio of power input 1 3 1 4 1 2 1 0 0 9 0 8 0 7 1 1 Ratio of cooling capacity Ratio of cooling capacity and power input Indoor Temperature 24 CWB 75 FWB 22 CWB 72 FWB 20 CWB 68 FWB 18 CWB 64 FWB 16 CWB 61 FWB 15 CWB 59 FWB 24 CWB 75 FWB...

Page 73: ... 0 5 0 7 0 4 1 0 Ratio of heating capacity Ratio of heating capacity and power input 4 5 14 23 32 41 50 59 20 15 10 5 0 5 10 15 FWB CWB Outdoor Temperature Indoor Temperature 24 CWB 75 FWB 22 CWB 72 FWB 20 CWB 68 FWB 18 CWB 64 FWB 16 CWB 61 FWB 15 CWB 59 FWB 24 CWB 75 FWB 22 CWB 72 FWB 20 CWB 68 FWB 18 CWB 64 FWB 16 CWB 61 FWB 15 CWB 59 FWB 15 CDB 59 FDB 20 CDB 68 FDB 25 CDB 77 FDB 27 CDB 80 FDB 1...

Page 74: ...4 5 14 23 32 41 50 59 20 15 10 5 0 5 10 15 68 20 77 25 86 30 FWB CWB Outdoor Temperature HEX unit inlet water temperature HEX unit inlet water temperature 35 C 95 F 30 C 86 F 25 C 77 F 20 C 68 F 15 C 59 F 10 C 50 F 35 C 95 F 30 C 86 F 25 C 77 F 20 C 68 F 15 C 59 F 10 C 50 F 10 C 50 F 20 C 68 F 30 C 86 F 35 C 95 F 40 C 104 F 10 C 50 F 20 C 68 F 30 C 86 F 35 C 95 F 40 C 104 F Nominal Cooling Capacit...

Page 75: ... booster unit input Ratio of booster power input 4 5 14 23 32 41 50 59 20 15 10 5 0 5 10 15 68 20 77 25 86 30 FWB CWB Outdoor Temperature Booster unit inlet water temperature Booster unit inlet water temperature 10 C 50 F 20 C 68 F 30 C 86 F 40 C 104 F 50 C 122 F 60 C 140 F 65 C 149 F 10 C 50 F 65 C 149 F 30 C 86 F 40 C 104 F 50 C 122 F 60 C 140 F 20 C 68 F 10 C 50 F 20 C 68 F 30 C 86 F 40 C 104 F...

Page 76: ...rved so as to ensure the system having enough capacity to meet the conditions Capacity kW Input kW Total capacity of indoor units 15 0 10 0 10 0 20 0 25 0 30 0 35 0 2 0 6 0 8 0 4 0 100 200 300 400 100 200 300 400 500 Capacity kW Input kW Total capacity of indoor units 10 0 20 0 30 0 40 0 50 0 2 0 6 0 4 0 10 0 12 0 8 0 Cooling Heating Cooling Heating Cooling Heating RP300 RP200 RP250 PURY RP200 250...

Page 77: ...uivalent length of piping 6 3 1 Cooling capacity correction Piping equivalent length m 1 0 90 0 80 0 95 0 85 0 75 0 65 0 70 Cooling capacity correction factor PURY RP200YJM B BS Total capacity of indoor unit 100 150 200 300 0 20 40 60 80 100 120 Piping equivalent length m 1 0 90 0 80 0 95 0 85 0 75 0 65 0 70 Cooling capacity correction factor PURY RP250YJM B BS Total capacity of indoor unit 125 18...

Page 78: ...ent length m 1 00 0 90 0 95 0 85 PURY RP200YJM B BS 0 20 40 60 80 100 120 Heating capacity correction factor Piping equivalent length m 1 00 0 90 0 95 0 85 PURY RP250YJM B BS 0 20 40 60 80 100 120 Heating capacity correction factor Piping equivalent length m 1 00 0 90 0 95 0 85 PURY RP300YJM B BS 0 20 40 60 80 100 120 ...

Page 79: ...indoor unit sizes from P100 to P140 are connected to only 1port on the BC controller set BC controller DIP SW 4 6 to its OFF position the cooling capacity of the indoor unit should be multiplied by a correction factor of 0 97 6 5 Correction at frost and defrost Due to frost at the outdoor heat exchanger and the automatic defrost operation the heating capacity of the outdoor unit can be calculated ...

Page 80: ... 113 122 Indoor temperature Outdoor temperature 30 25 20 15 10 5 86 77 68 59 50 41 86 77 68 59 50 41 20 15 10 5 0 5 10 15 20 25 30 35 40 45 50 Indoor temperature Outdoor temperature Outdoor temperature 5 to 21 CDB 23 to 70 FDB 6 to 15 5 CWB 21 to 60 FWB 15 to 24 CWB 59 to 75 FWB 15 to 27 CDB 59 to 81 FDB Indoor temperature Cooling Heating Combination of cooling heating operation Cooling main or He...

Page 81: ...erature and defrost heating Find the piping length correction factor from the diagram that corresponds to the total indoor unit capacity N 4 Make sure the maximum outdoor unit capacity Qm is equal to or greater than the total thermal load Qi If Qm is smaller than Qi reconsider the outdoor unit capacity X so that Qm Qi will hold true 5 After selecting indoor and outdoor units calculate the apportio...

Page 82: ...y x return air temperature correction factor The standard outside air temperatures used to obtain the return air temperature correction factor is 35ºCDB for cooling and 6ºCWB for heating If non standard size pipes are connected use the pipe diameter correction factors for the main pipes merge pipes and branch pipes When deciding the outside air temperature to calculate unit capacity requirements t...

Page 83: ... bulb temperature of 20ºC defrost correction factor is 0 965 piping length is 50 m and capacity correction factor is 0 975 The result shows that the Maximum outdoor unit capacity Qm 35 2 kW exceeds the heating load Qi 29 kW c You can now check to see if this value will meet the capacity requirement for each indoor unit by using the following formula 35 2 x 125 250 x 0 96 16 8 kW where the indoor u...

Page 84: ...0 model outdoor unit can be selected a The standard capacity Qs of the tentatively selected during cooling load calculation 300 model outdoor unit is 37 5 kW The standard capacity Qs is corrected for indoor outside air temperatures and piping length to obtain the maximum outdoor unit capacity Qm as follows Qm 37 5 x 1 00 x 0 975 x 0 975 x 0 98 34 9 kW The result shows that the Maximum outdoor unit...

Page 85: ...ing and heating Select the outdoor unit capacity X Select the outdoor unit one rank higher in capacity Apportion the corrected outdoor unit capacity Qm to each indoor unit Multiply the apportioned capacity by the indoor unit temperature correction factor and make sure it is equal to or greater than the thermal load Thermal load Qi Corrected capacity Qm YES NO Correct the standard outdoor unit capa...

Page 86: ...m Ø19 05 Ø22 2 Ø25 4 1 0 90 0 80 0 60 0 70 Pipe diameter correction factor PURY RP200YJM B 0 20 40 60 80 100 Equivalent main piping length m Ø22 2 Ø25 4 1 0 90 0 80 0 60 0 70 Pipe diameter correction factor PURY RP250YJM B 0 20 40 60 80 100 Equivalent main piping length m Ø22 2 Ø25 4 1 0 90 0 80 0 60 0 70 Pipe diameter correction factor PURY RP300YJM B 0 20 40 60 80 100 ...

Page 87: ...ipe diameter correction factor P50 0 10 40 20 30 Ø25 4 Ø22 2 Branch piping length m 1 0 90 0 80 Pipe diameter correction factor P250 0 10 40 20 30 Ø15 88 Branch piping length m 1 0 90 0 80 Pipe diameter correction factor P100 P125 P140 0 10 40 20 30 Ø22 2 Ø19 05 Branch piping length m 1 0 90 0 80 Pipe diameter correction factor P200 0 10 40 20 30 ...

Page 88: ...diameter correction factor Ø28 58 P331 P400 0 10 40 20 30 Equivalent main piping length m Ø22 2 Ø19 05 1 0 90 0 80 Pipe diameter correction factor P161 P200 0 10 40 20 30 Equivalent main piping length m Ø28 58 1 0 90 0 80 Pipe diameter correction factor P401 P630 0 10 40 20 30 Equivalent main piping length m Ø22 2 1 0 90 0 80 Pipe diameter correction factor P201 P300 0 10 40 20 30 Equivalent main ...

Page 89: ...7 UNIT SELECTION OUTDOOR UNITS 86 Equivalent main piping length m Ø34 93 1 0 90 0 80 Pipe diameter correction factor P651 P800 0 10 40 20 30 ...

Page 90: ... 4 way flow type 134 5 1 Cooling capacity with PUHY PURY RP200 250YJM 134 5 2 Cooling capacity with PUHY RP300 400Y S JM PURY RP300YJM 136 5 3 Cooling capacity with PUHY RP450 650YSJM 138 5 4 Cooling capacity with PUHY RP700 800YSJM 140 5 5 Cooling capacity with PUHY RP850 900YSJM 142 6 Cooling Ceiling suspended 144 6 1 Cooling capacity with PUHY PURY RP200 250YJM 144 6 2 Cooling capacity with PUH...

Page 91: ...riority mode 181 9 9 Heating capacity with PUHY RP700 800YSJM COP priority mode 182 9 10 Heating capacity with PUHY RP850 900YSJM COP priority mode 183 10 Cooling Ceiling concealed Fresh air intake 184 10 1 Cooling capacity 184 10 2 Outlet air temp cooled 185 11 Heating Ceiling concealed Fresh air intake 186 11 1 Heating capacity 186 11 2 Outlet air temp heated 187 ...

Page 92: ... 9 22 5 7 6 5 6 7 9 5 8 8 4 5 7 8 7 6 1 8 9 6 0 9 5 6 0 10 1 5 9 25 0 7 6 5 6 7 9 5 8 8 4 5 7 8 6 6 1 8 9 6 0 9 4 5 9 10 0 5 8 27 5 7 6 5 6 7 8 5 7 8 3 5 7 8 5 6 0 8 7 5 9 9 2 5 8 9 8 5 8 30 0 7 4 5 5 7 7 5 7 8 1 5 6 8 3 5 9 8 5 5 9 9 0 5 8 9 6 5 7 32 5 7 3 5 4 7 5 5 6 8 0 5 5 8 2 5 8 8 4 5 8 8 8 5 7 9 4 5 6 35 0 7 2 5 4 7 4 5 5 7 8 5 5 8 0 5 8 8 2 5 7 8 6 5 6 9 2 5 5 37 5 7 0 5 3 7 2 5 5 7 7 5 4 ...

Page 93: ... 0 16 1 22 3 16 0 22 9 16 9 23 5 16 8 24 7 16 5 26 2 16 2 35 0 20 1 15 5 20 7 16 0 21 9 15 8 22 4 16 7 23 0 16 6 24 2 16 3 25 7 16 1 37 5 19 7 15 3 20 3 15 8 21 4 15 6 22 0 16 5 22 6 16 4 23 7 16 1 25 1 15 9 40 0 19 3 15 1 19 9 15 6 21 0 15 4 21 6 16 4 22 1 16 2 23 2 15 9 24 6 15 7 43 0 18 8 14 9 19 4 15 4 20 5 15 2 21 1 16 1 21 6 16 0 22 6 15 7 23 9 15 5 250 28 0 20 0 26 6 20 0 27 6 20 7 29 4 20 ...

Page 94: ...0 3 0 2 2 3 1 2 1 3 3 2 1 3 5 2 1 22 5 2 7 2 0 2 8 2 1 2 9 2 0 3 0 2 2 3 1 2 1 3 3 2 1 3 5 2 1 25 0 2 7 2 0 2 8 2 1 2 9 2 0 3 0 2 2 3 1 2 1 3 3 2 1 3 5 2 1 27 5 2 7 2 0 2 7 2 0 2 9 2 0 3 0 2 1 3 0 2 1 3 2 2 1 3 4 2 1 30 0 2 6 2 0 2 7 2 0 2 8 2 0 2 9 2 1 3 0 2 1 3 2 2 1 3 3 2 0 32 5 2 6 1 9 2 6 2 0 2 8 2 0 2 9 2 1 2 9 2 1 3 1 2 0 3 3 2 0 35 0 2 5 1 9 2 6 2 0 2 7 1 9 2 8 2 1 2 9 2 0 3 0 2 0 3 2 2 0 ...

Page 95: ...7 3 9 2 8 4 0 2 8 4 3 2 8 4 6 2 7 22 5 3 4 2 6 3 5 2 7 3 8 2 7 3 9 2 8 4 0 2 8 4 3 2 8 4 6 2 7 25 0 3 4 2 6 3 5 2 7 3 8 2 7 3 9 2 8 4 0 2 8 4 2 2 7 4 5 2 7 27 5 3 4 2 6 3 5 2 7 3 7 2 6 3 8 2 8 3 9 2 8 4 1 2 7 4 4 2 7 30 0 3 3 2 5 3 4 2 6 3 6 2 6 3 7 2 7 3 8 2 7 4 1 2 7 4 3 2 6 32 5 3 3 2 5 3 4 2 6 3 6 2 6 3 7 2 7 3 8 2 7 4 0 2 6 4 2 2 6 35 0 3 2 2 5 3 3 2 6 3 5 2 5 3 6 2 7 3 7 2 7 3 9 2 6 4 1 2 6 ...

Page 96: ...6 1 9 1 6 1 9 6 6 0 10 2 5 9 25 0 7 6 5 6 7 8 5 8 8 4 5 7 8 6 6 1 8 9 6 0 9 4 5 9 10 0 5 9 27 5 7 5 5 5 7 7 5 7 8 2 5 6 8 5 6 0 8 7 5 9 9 3 5 9 9 8 5 8 30 0 7 4 5 5 7 5 5 6 8 0 5 6 8 3 5 9 8 6 5 9 9 1 5 8 9 6 5 7 32 5 7 3 5 4 7 4 5 5 7 9 5 5 8 1 5 8 8 4 5 8 8 9 5 7 9 4 5 6 35 0 7 1 5 4 7 2 5 5 7 7 5 4 8 0 5 8 8 2 5 7 8 7 5 7 9 2 5 6 37 5 7 0 5 3 7 1 5 4 7 5 5 4 7 8 5 7 8 0 5 7 8 5 5 6 9 0 5 5 40 0...

Page 97: ... 7 16 0 22 0 15 8 22 8 16 9 23 5 16 8 24 9 16 6 26 4 16 3 35 0 20 0 15 4 20 3 15 8 21 6 15 7 22 4 16 7 23 0 16 6 24 4 16 4 25 8 16 1 37 5 19 6 15 3 19 9 15 6 21 1 15 5 21 8 16 5 22 5 16 4 23 9 16 2 25 3 15 9 40 0 19 3 15 1 19 4 15 4 20 7 15 3 21 3 16 3 22 0 16 2 23 4 16 0 24 8 15 7 43 0 18 9 14 9 18 9 15 2 20 1 15 0 20 8 16 0 21 4 16 0 22 8 15 8 24 1 15 5 250 28 0 20 0 27 2 20 3 28 1 20 9 30 3 20 ...

Page 98: ...1 3 1 2 2 3 2 2 2 3 4 2 2 3 6 2 1 22 5 2 7 2 0 2 8 2 1 3 0 2 1 3 1 2 2 3 2 2 2 3 4 2 1 3 6 2 1 25 0 2 7 2 0 2 7 2 0 2 9 2 0 3 0 2 2 3 1 2 1 3 3 2 1 3 5 2 1 27 5 2 6 2 0 2 7 2 0 2 9 2 0 3 0 2 1 3 1 2 1 3 2 2 1 3 4 2 1 30 0 2 6 1 9 2 6 2 0 2 8 2 0 2 9 2 1 3 0 2 1 3 2 2 1 3 4 2 0 32 5 2 5 1 9 2 6 2 0 2 8 2 0 2 8 2 1 2 9 2 1 3 1 2 0 3 3 2 0 35 0 2 5 1 9 2 5 1 9 2 7 1 9 2 8 2 1 2 9 2 0 3 0 2 0 3 2 2 0 ...

Page 99: ...7 4 0 2 9 4 2 2 9 4 4 2 8 4 7 2 8 22 5 3 5 2 6 3 6 2 7 3 8 2 7 4 0 2 8 4 1 2 8 4 3 2 8 4 6 2 7 25 0 3 4 2 6 3 5 2 7 3 8 2 6 3 9 2 8 4 0 2 8 4 2 2 8 4 5 2 7 27 5 3 4 2 6 3 5 2 6 3 7 2 6 3 8 2 8 3 9 2 8 4 2 2 7 4 4 2 7 30 0 3 3 2 5 3 4 2 6 3 6 2 6 3 7 2 7 3 8 2 7 4 1 2 7 4 3 2 7 32 5 3 3 2 5 3 3 2 6 3 5 2 5 3 7 2 7 3 8 2 7 4 0 2 7 4 2 2 6 35 0 3 2 2 5 3 3 2 5 3 5 2 5 3 6 2 7 3 7 2 7 3 9 2 6 4 2 2 6 ...

Page 100: ... 0 9 4 5 9 10 0 5 8 25 0 7 4 5 5 7 6 5 6 8 1 5 6 8 4 6 0 8 7 5 9 9 3 5 9 9 9 5 8 27 5 7 3 5 5 7 5 5 6 8 1 5 6 8 3 5 9 8 6 5 9 9 2 5 8 9 8 5 8 30 0 7 3 5 4 7 4 5 6 8 0 5 5 8 2 5 9 8 5 5 9 9 1 5 8 9 7 5 7 32 5 7 2 5 4 7 3 5 5 7 9 5 5 8 2 5 8 8 4 5 8 9 0 5 8 9 6 5 7 35 0 7 1 5 4 7 2 5 5 7 8 5 5 8 0 5 8 8 3 5 8 8 9 5 7 9 5 5 7 37 5 7 0 5 3 7 2 5 4 7 7 5 4 8 0 5 8 8 3 5 7 8 8 5 7 9 4 5 6 40 0 7 0 5 3 7...

Page 101: ... 5 15 9 22 1 15 9 22 8 16 9 23 6 16 8 25 2 16 7 26 9 16 5 35 0 19 9 15 4 20 3 15 8 21 8 15 7 22 4 16 7 23 4 16 7 25 0 16 6 26 7 16 4 37 5 19 7 15 3 20 0 15 7 21 5 15 6 22 3 16 7 23 1 16 6 24 7 16 5 26 4 16 3 40 0 19 5 15 2 19 8 15 5 21 3 15 5 22 1 16 6 22 8 16 5 24 5 16 4 26 2 16 2 43 0 19 2 15 1 19 5 15 4 21 0 15 4 21 8 16 4 22 6 16 4 24 2 16 3 25 9 16 1 250 28 0 20 0 26 5 19 9 27 3 20 5 29 2 20 ...

Page 102: ...0 3 0 2 1 3 1 2 1 3 3 2 1 3 5 2 1 22 5 2 6 2 0 2 7 2 0 2 9 2 0 3 0 2 1 3 1 2 1 3 3 2 1 3 5 2 1 25 0 2 6 2 0 2 7 2 0 2 9 2 0 2 9 2 1 3 0 2 1 3 2 2 1 3 5 2 1 27 5 2 6 1 9 2 6 2 0 2 8 2 0 2 9 2 1 3 0 2 1 3 2 2 1 3 4 2 1 30 0 2 5 1 9 2 6 2 0 2 8 2 0 2 9 2 1 3 0 2 1 3 2 2 1 3 4 2 0 32 5 2 5 1 9 2 6 2 0 2 8 2 0 2 9 2 1 3 0 2 1 3 2 2 1 3 4 2 0 35 0 2 5 1 9 2 5 1 9 2 7 1 9 2 8 2 1 2 9 2 1 3 1 2 0 3 3 2 0 ...

Page 103: ...6 3 9 2 8 4 0 2 8 4 3 2 8 4 5 2 7 22 5 3 4 2 6 3 5 2 6 3 7 2 6 3 8 2 8 4 0 2 8 4 2 2 7 4 5 2 7 25 0 3 3 2 5 3 4 2 6 3 7 2 6 3 8 2 8 3 9 2 8 4 2 2 7 4 4 2 7 27 5 3 3 2 5 3 4 2 6 3 6 2 6 3 8 2 7 3 9 2 7 4 1 2 7 4 4 2 7 30 0 3 3 2 5 3 3 2 6 3 6 2 6 3 7 2 7 3 8 2 7 4 1 2 7 4 4 2 7 32 5 3 2 2 5 3 3 2 6 3 5 2 5 3 7 2 7 3 8 2 7 4 1 2 7 4 3 2 7 35 0 3 2 2 5 3 3 2 5 3 5 2 5 3 6 2 7 3 8 2 7 4 0 2 7 4 3 2 6 ...

Page 104: ... 6 1 9 6 6 0 10 3 5 9 25 0 7 5 5 5 7 7 5 7 8 3 5 7 8 6 6 0 8 9 6 0 9 5 6 0 10 1 5 9 27 5 7 3 5 5 7 6 5 6 8 1 5 6 8 4 6 0 8 7 5 9 9 3 5 9 9 9 5 8 30 0 7 2 5 4 7 4 5 6 8 0 5 6 8 3 5 9 8 6 5 9 9 1 5 8 9 7 5 7 32 5 7 1 5 3 7 3 5 5 7 8 5 5 8 1 5 8 8 4 5 8 9 0 5 8 9 5 5 7 35 0 6 9 5 3 7 2 5 4 7 7 5 4 8 0 5 8 8 2 5 7 8 8 5 7 9 3 5 6 37 5 6 8 5 2 7 0 5 4 7 5 5 4 7 8 5 7 8 1 5 7 8 6 5 6 9 2 5 5 40 0 6 7 5 ...

Page 105: ...0 5 15 9 22 0 15 8 22 7 16 9 23 5 16 8 25 1 16 6 26 7 16 4 35 0 19 5 15 2 20 1 15 7 21 5 15 6 22 4 16 7 23 1 16 6 24 6 16 4 26 2 16 2 37 5 19 1 15 0 19 7 15 5 21 1 15 5 21 9 16 5 22 6 16 4 24 1 16 3 25 7 16 1 40 0 18 7 14 9 19 3 15 3 20 7 15 3 21 4 16 3 22 2 16 2 23 7 16 1 25 2 15 9 43 0 18 3 14 6 18 8 15 1 20 2 15 1 20 9 16 1 21 6 16 0 23 1 15 9 24 6 15 7 250 28 0 20 0 27 0 20 2 28 0 20 9 30 1 20...

Page 106: ... 1 3 1 2 2 3 2 2 2 3 4 2 2 3 7 2 1 22 5 2 7 2 0 2 8 2 1 3 0 2 0 3 1 2 2 3 2 2 2 3 4 2 1 3 6 2 1 25 0 2 6 2 0 2 7 2 0 2 9 2 0 3 0 2 1 3 1 2 1 3 3 2 1 3 5 2 1 27 5 2 6 1 9 2 7 2 0 2 9 2 0 3 0 2 1 3 1 2 1 3 3 2 1 3 5 2 1 30 0 2 5 1 9 2 6 2 0 2 8 2 0 2 9 2 1 3 0 2 1 3 2 2 1 3 4 2 0 32 5 2 5 1 9 2 6 2 0 2 7 2 0 2 8 2 1 2 9 2 1 3 1 2 0 3 3 2 0 35 0 2 4 1 9 2 5 1 9 2 7 1 9 2 8 2 1 2 9 2 0 3 1 2 0 3 3 2 0...

Page 107: ...7 4 0 2 9 4 1 2 8 4 4 2 8 4 7 2 8 22 5 3 4 2 6 3 5 2 7 3 8 2 7 3 9 2 8 4 1 2 8 4 3 2 8 4 6 2 8 25 0 3 4 2 6 3 5 2 6 3 7 2 6 3 9 2 8 4 0 2 8 4 3 2 8 4 5 2 7 27 5 3 3 2 5 3 4 2 6 3 7 2 6 3 8 2 8 3 9 2 8 4 2 2 7 4 5 2 7 30 0 3 2 2 5 3 4 2 6 3 6 2 6 3 7 2 7 3 9 2 7 4 1 2 7 4 4 2 7 32 5 3 2 2 5 3 3 2 6 3 5 2 5 3 7 2 7 3 8 2 7 4 0 2 7 4 3 2 6 35 0 3 1 2 4 3 2 2 5 3 5 2 5 3 6 2 7 3 7 2 7 4 0 2 6 4 2 2 6 ...

Page 108: ... 0 9 4 5 9 10 0 5 8 25 0 7 4 5 5 7 6 5 6 8 1 5 6 8 4 6 0 8 7 5 9 9 3 5 9 9 9 5 8 27 5 7 3 5 5 7 5 5 6 8 1 5 6 8 3 5 9 8 6 5 9 9 2 5 8 9 8 5 8 30 0 7 3 5 4 7 4 5 6 8 0 5 5 8 2 5 9 8 5 5 9 9 1 5 8 9 7 5 7 32 5 7 2 5 4 7 3 5 5 7 9 5 5 8 2 5 8 8 4 5 8 9 0 5 8 9 6 5 7 35 0 7 1 5 4 7 2 5 5 7 8 5 5 8 0 5 8 8 3 5 8 8 9 5 7 9 5 5 7 37 5 7 0 5 3 7 2 5 4 7 7 5 4 8 0 5 8 8 3 5 7 8 8 5 7 9 4 5 6 40 0 7 0 5 3 7...

Page 109: ...0 5 15 9 22 1 15 9 22 8 16 9 23 6 16 8 25 2 16 7 26 9 16 5 35 0 19 9 15 4 20 3 15 8 21 8 15 7 22 4 16 7 23 4 16 7 25 0 16 6 26 7 16 4 37 5 19 7 15 3 20 0 15 7 21 5 15 6 22 3 16 7 23 1 16 6 24 7 16 5 26 4 16 3 40 0 19 5 15 2 19 8 15 5 21 3 15 5 22 1 16 6 22 8 16 5 24 5 16 4 26 2 16 2 43 0 19 2 15 1 19 5 15 4 21 0 15 4 21 8 16 4 22 6 16 4 24 2 16 3 25 9 16 1 250 28 0 20 0 26 5 19 9 27 3 20 5 29 2 20...

Page 110: ... 0 3 0 2 1 3 1 2 1 3 3 2 1 3 5 2 1 22 5 2 6 2 0 2 7 2 0 2 9 2 0 3 0 2 1 3 1 2 1 3 3 2 1 3 5 2 1 25 0 2 6 2 0 2 7 2 0 2 9 2 0 2 9 2 1 3 0 2 1 3 2 2 1 3 5 2 1 27 5 2 6 1 9 2 6 2 0 2 8 2 0 2 9 2 1 3 0 2 1 3 2 2 1 3 4 2 1 30 0 2 5 1 9 2 6 2 0 2 8 2 0 2 9 2 1 3 0 2 1 3 2 2 1 3 4 2 0 32 5 2 5 1 9 2 6 2 0 2 8 2 0 2 9 2 1 3 0 2 1 3 2 2 1 3 4 2 0 35 0 2 5 1 9 2 5 1 9 2 7 1 9 2 8 2 1 2 9 2 1 3 1 2 0 3 3 2 0...

Page 111: ...6 3 9 2 8 4 0 2 8 4 3 2 8 4 5 2 7 22 5 3 4 2 6 3 5 2 6 3 7 2 6 3 8 2 8 4 0 2 8 4 2 2 7 4 5 2 7 25 0 3 3 2 5 3 4 2 6 3 7 2 6 3 8 2 8 3 9 2 8 4 2 2 7 4 4 2 7 27 5 3 3 2 5 3 4 2 6 3 6 2 6 3 8 2 7 3 9 2 7 4 1 2 7 4 4 2 7 30 0 3 3 2 5 3 3 2 6 3 6 2 6 3 7 2 7 3 8 2 7 4 1 2 7 4 4 2 7 32 5 3 2 2 5 3 3 2 6 3 5 2 5 3 7 2 7 3 8 2 7 4 1 2 7 4 3 2 7 35 0 3 2 2 5 3 3 2 5 3 5 2 5 3 6 2 7 3 8 2 7 4 0 2 7 4 3 2 6 ...

Page 112: ...2 5 3 8 2 4 40 4 5 20 0 4 3 3 4 4 4 3 6 4 7 3 5 4 9 3 8 5 0 3 7 5 3 3 7 5 7 3 7 22 5 4 3 3 4 4 4 3 6 4 7 3 5 4 9 3 8 5 0 3 7 5 3 3 7 5 7 3 7 25 0 4 3 3 4 4 4 3 6 4 7 3 5 4 9 3 8 5 0 3 7 5 3 3 7 5 6 3 6 27 5 4 3 3 4 4 4 3 5 4 6 3 5 4 8 3 7 4 9 3 7 5 2 3 6 5 5 3 6 30 0 4 2 3 4 4 3 3 5 4 6 3 5 4 7 3 7 4 8 3 7 5 1 3 6 5 4 3 5 32 5 4 1 3 3 4 2 3 5 4 5 3 4 4 6 3 6 4 7 3 6 5 0 3 6 5 3 3 5 35 0 4 0 3 3 4 ...

Page 113: ...2 11 2 15 6 11 1 16 6 11 0 17 7 10 8 25 0 13 3 10 2 13 8 10 6 14 7 10 5 15 1 11 1 15 5 11 0 16 4 10 9 17 4 10 7 27 5 13 3 10 2 13 6 10 5 14 4 10 4 14 8 11 0 15 2 10 9 16 1 10 8 17 1 10 6 30 0 13 0 10 1 13 4 10 4 14 2 10 3 14 6 10 9 14 9 10 8 15 8 10 6 16 7 10 5 32 5 12 8 10 0 13 2 10 3 13 9 10 2 14 3 10 8 14 7 10 7 15 4 10 5 16 4 10 4 35 0 12 5 9 9 12 9 10 2 13 7 10 1 14 0 10 7 14 4 10 6 15 1 10 4...

Page 114: ...0 4 4 3 5 4 5 3 6 4 9 3 6 5 0 3 8 5 2 3 8 5 5 3 8 5 8 3 7 22 5 4 4 3 5 4 5 3 6 4 8 3 6 4 9 3 8 5 1 3 8 5 4 3 7 5 7 3 7 25 0 4 3 3 4 4 4 3 5 4 7 3 5 4 9 3 8 5 0 3 7 5 3 3 7 5 6 3 6 27 5 4 2 3 4 4 3 3 5 4 6 3 5 4 8 3 7 4 9 3 7 5 2 3 6 5 5 3 6 30 0 4 1 3 4 4 2 3 5 4 5 3 4 4 7 3 7 4 8 3 7 5 1 3 6 5 4 3 6 32 5 4 1 3 3 4 2 3 4 4 4 3 4 4 6 3 6 4 7 3 6 5 0 3 6 5 3 3 5 35 0 4 0 3 3 4 1 3 4 4 3 3 4 4 5 3 6 ...

Page 115: ... 4 11 3 15 9 11 2 16 8 11 1 17 8 10 9 25 0 13 3 10 3 13 7 10 6 14 6 10 5 15 1 11 1 15 6 11 1 16 5 10 9 17 5 10 8 27 5 13 1 10 2 13 5 10 4 14 3 10 4 14 8 11 0 15 3 11 0 16 2 10 8 17 2 10 7 30 0 12 9 10 0 13 2 10 3 14 1 10 2 14 5 10 9 15 0 10 8 15 9 10 7 16 8 10 5 32 5 12 7 9 9 12 9 10 2 13 8 10 1 14 2 10 8 14 7 10 7 15 6 10 6 16 5 10 4 35 0 12 5 9 8 12 7 10 1 13 5 10 0 14 0 10 7 14 4 10 6 15 2 10 5...

Page 116: ...4 4 4 3 5 4 7 3 5 4 8 3 7 5 0 3 7 5 3 3 7 5 7 3 6 22 5 4 2 3 4 4 3 3 5 4 6 3 5 4 8 3 7 4 9 3 7 5 3 3 7 5 6 3 6 25 0 4 2 3 4 4 3 3 5 4 6 3 5 4 7 3 7 4 9 3 7 5 2 3 7 5 6 3 6 27 5 4 1 3 4 4 2 3 5 4 5 3 4 4 7 3 7 4 8 3 7 5 2 3 6 5 5 3 6 30 0 4 1 3 3 4 2 3 4 4 5 3 4 4 6 3 7 4 8 3 6 5 1 3 6 5 5 3 6 32 5 4 0 3 3 4 1 3 4 4 4 3 4 4 6 3 6 4 7 3 6 5 1 3 6 5 4 3 6 35 0 4 0 3 3 4 1 3 4 4 4 3 4 4 5 3 6 4 7 3 6 ...

Page 117: ...9 11 1 15 4 11 0 16 4 10 9 17 4 10 7 25 0 13 0 10 1 13 3 10 4 14 3 10 3 14 7 11 0 15 2 10 9 16 2 10 8 17 3 10 7 27 5 12 8 10 0 13 2 10 3 14 1 10 2 14 6 10 9 15 1 10 9 16 1 10 8 17 1 10 6 30 0 12 7 9 9 13 0 10 2 13 9 10 2 14 4 10 9 14 9 10 8 15 9 10 7 17 0 10 6 32 5 12 6 9 9 12 8 10 1 13 8 10 1 14 3 10 8 14 8 10 7 15 8 10 7 16 8 10 5 35 0 12 4 9 8 12 7 10 1 13 6 10 0 14 0 10 7 14 6 10 7 15 6 10 6 1...

Page 118: ...5 4 5 3 6 4 8 3 6 5 0 3 8 5 2 3 8 5 5 3 8 5 9 3 7 22 5 4 3 3 4 4 4 3 6 4 7 3 5 4 9 3 8 5 1 3 8 5 4 3 7 5 8 3 7 25 0 4 2 3 4 4 3 3 5 4 7 3 5 4 8 3 7 5 0 3 7 5 3 3 7 5 7 3 6 27 5 4 1 3 4 4 3 3 5 4 6 3 5 4 7 3 7 4 9 3 7 5 2 3 7 5 6 3 6 30 0 4 1 3 3 4 2 3 4 4 5 3 4 4 7 3 7 4 8 3 7 5 1 3 6 5 5 3 6 32 5 4 0 3 3 4 1 3 4 4 4 3 4 4 6 3 6 4 7 3 6 5 0 3 6 5 4 3 5 35 0 3 9 3 3 4 0 3 4 4 3 3 4 4 5 3 6 4 6 3 6 ...

Page 119: ... 3 11 2 15 8 11 2 16 9 11 1 17 9 10 9 25 0 13 1 10 1 13 5 10 5 14 5 10 4 15 0 11 1 15 5 11 1 16 6 11 0 17 6 10 8 27 5 12 8 10 0 13 3 10 3 14 3 10 3 14 8 11 0 15 3 11 0 16 3 10 8 17 3 10 7 30 0 12 6 9 9 13 0 10 2 14 0 10 2 14 5 10 9 15 0 10 8 16 0 10 7 17 0 10 6 32 5 12 4 9 8 12 8 10 1 13 7 10 1 14 2 10 8 14 7 10 7 15 7 10 6 16 7 10 5 35 0 12 2 9 7 12 5 10 0 13 5 10 0 14 0 10 7 14 4 10 6 15 4 10 5 ...

Page 120: ...4 4 4 3 5 4 7 3 5 4 8 3 7 5 0 3 7 5 3 3 7 5 7 3 6 22 5 4 2 3 4 4 3 3 5 4 6 3 5 4 8 3 7 4 9 3 7 5 3 3 7 5 6 3 6 25 0 4 2 3 4 4 3 3 5 4 6 3 5 4 7 3 7 4 9 3 7 5 2 3 7 5 6 3 6 27 5 4 1 3 4 4 2 3 5 4 5 3 4 4 7 3 7 4 8 3 7 5 2 3 6 5 5 3 6 30 0 4 1 3 3 4 2 3 4 4 5 3 4 4 6 3 7 4 8 3 6 5 1 3 6 5 5 3 6 32 5 4 0 3 3 4 1 3 4 4 4 3 4 4 6 3 6 4 7 3 6 5 1 3 6 5 4 3 6 35 0 4 0 3 3 4 1 3 4 4 4 3 4 4 5 3 6 4 7 3 6 ...

Page 121: ...9 11 1 15 4 11 0 16 4 10 9 17 4 10 7 25 0 13 0 10 1 13 3 10 4 14 3 10 3 14 7 11 0 15 2 10 9 16 2 10 8 17 3 10 7 27 5 12 8 10 0 13 2 10 3 14 1 10 2 14 6 10 9 15 1 10 9 16 1 10 8 17 1 10 6 30 0 12 7 9 9 13 0 10 2 13 9 10 2 14 4 10 9 14 9 10 8 15 9 10 7 17 0 10 6 32 5 12 6 9 9 12 8 10 1 13 8 10 1 14 3 10 8 14 8 10 7 15 8 10 7 16 8 10 5 35 0 12 4 9 8 12 7 10 1 13 6 10 0 14 0 10 7 14 6 10 7 15 6 10 6 1...

Page 122: ... 3 32 5 2 6 2 2 2 6 2 3 2 8 2 2 2 9 2 4 2 9 2 4 3 1 2 3 3 3 2 3 35 0 2 5 2 2 2 6 2 2 2 7 2 2 2 8 2 4 2 9 2 3 3 0 2 3 3 2 2 3 37 5 2 5 2 1 2 5 2 2 2 7 2 2 2 8 2 3 2 8 2 3 3 0 2 3 3 1 2 2 40 0 2 4 2 1 2 5 2 2 2 6 2 2 2 7 2 3 2 8 2 3 2 9 2 3 3 1 2 2 43 0 2 4 2 1 2 4 2 2 2 6 2 1 2 6 2 3 2 7 2 3 2 8 2 2 3 0 2 2 32 3 6 20 0 3 4 2 6 3 5 2 6 3 8 2 6 3 9 2 8 4 0 2 8 4 3 2 7 4 6 2 7 22 5 3 4 2 6 3 5 2 6 3 8...

Page 123: ...2 6 2 2 2 8 2 2 2 8 2 4 2 9 2 4 3 1 2 3 3 3 2 3 35 0 2 5 2 1 2 5 2 2 2 7 2 2 2 8 2 4 2 9 2 3 3 0 2 3 3 2 2 3 37 5 2 5 2 1 2 5 2 2 2 6 2 2 2 7 2 3 2 8 2 3 3 0 2 3 3 2 2 3 40 0 2 4 2 1 2 4 2 2 2 6 2 1 2 7 2 3 2 8 2 3 2 9 2 3 3 1 2 2 43 0 2 4 2 1 2 4 2 1 2 5 2 1 2 6 2 3 2 7 2 3 2 8 2 2 3 0 2 2 32 3 6 20 0 3 5 2 6 3 6 2 7 3 9 2 7 4 0 2 8 4 2 2 8 4 4 2 8 4 7 2 8 22 5 3 5 2 6 3 6 2 7 3 8 2 7 4 0 2 8 4 1...

Page 124: ...2 8 2 2 2 9 2 4 3 0 2 4 3 2 2 3 3 4 2 3 35 0 2 5 2 1 2 5 2 2 2 7 2 2 2 8 2 4 2 9 2 4 3 1 2 3 3 3 2 3 37 5 2 5 2 1 2 5 2 2 2 7 2 2 2 8 2 4 2 9 2 3 3 1 2 3 3 3 2 3 40 0 2 4 2 1 2 5 2 2 2 7 2 2 2 8 2 3 2 9 2 3 3 1 2 3 3 3 2 3 43 0 2 4 2 1 2 4 2 2 2 6 2 2 2 7 2 3 2 8 2 3 3 0 2 3 3 2 2 3 32 3 6 20 0 3 4 2 6 3 5 2 6 3 7 2 6 3 9 2 8 4 0 2 8 4 3 2 7 4 5 2 7 22 5 3 4 2 5 3 5 2 6 3 7 2 6 3 8 2 8 4 0 2 7 4 2...

Page 125: ...2 7 2 2 2 8 2 4 2 9 2 4 3 1 2 3 3 3 2 3 35 0 2 4 2 1 2 5 2 2 2 7 2 2 2 8 2 4 2 9 2 3 3 1 2 3 3 3 2 3 37 5 2 4 2 1 2 5 2 2 2 6 2 2 2 7 2 3 2 8 2 3 3 0 2 3 3 2 2 3 40 0 2 3 2 1 2 4 2 2 2 6 2 1 2 7 2 3 2 8 2 3 3 0 2 3 3 1 2 3 43 0 2 3 2 1 2 4 2 1 2 5 2 1 2 6 2 3 2 7 2 3 2 9 2 3 3 1 2 2 32 3 6 20 0 3 5 2 6 3 6 2 7 3 9 2 7 4 0 2 8 4 1 2 8 4 4 2 8 4 7 2 8 22 5 3 4 2 6 3 5 2 6 3 8 2 6 3 9 2 8 4 1 2 8 4 3...

Page 126: ...2 8 2 2 2 9 2 4 3 0 2 4 3 2 2 3 3 4 2 3 35 0 2 5 2 1 2 5 2 2 2 7 2 2 2 8 2 4 2 9 2 4 3 1 2 3 3 3 2 3 37 5 2 5 2 1 2 5 2 2 2 7 2 2 2 8 2 4 2 9 2 3 3 1 2 3 3 3 2 3 40 0 2 4 2 1 2 5 2 2 2 7 2 2 2 8 2 3 2 9 2 3 3 1 2 3 3 3 2 3 43 0 2 4 2 1 2 4 2 2 2 6 2 2 2 7 2 3 2 8 2 3 3 0 2 3 3 2 2 3 32 3 6 20 0 3 4 2 6 3 5 2 6 3 7 2 6 3 9 2 8 4 0 2 8 4 3 2 7 4 5 2 7 22 5 3 4 2 5 3 5 2 6 3 7 2 6 3 8 2 8 4 0 2 7 4 2...

Page 127: ...0 0 4 3 3 0 4 4 3 1 4 7 3 1 4 9 3 2 5 0 3 2 5 3 3 1 5 7 3 1 22 5 4 3 3 0 4 4 3 1 4 7 3 1 4 9 3 2 5 0 3 2 5 3 3 1 5 7 3 1 25 0 4 3 3 0 4 4 3 1 4 7 3 1 4 9 3 2 5 0 3 2 5 3 3 1 5 6 3 1 27 5 4 3 3 0 4 4 3 1 4 6 3 0 4 8 3 2 4 9 3 1 5 2 3 1 5 5 3 0 30 0 4 2 2 9 4 3 3 0 4 6 3 0 4 7 3 1 4 8 3 1 5 1 3 0 5 4 3 0 32 5 4 1 2 9 4 2 3 0 4 5 2 9 4 6 3 1 4 7 3 1 5 0 3 0 5 3 3 0 35 0 4 0 2 9 4 1 2 9 4 4 2 9 4 5 3 ...

Page 128: ... 6 15 6 10 5 16 6 10 4 17 7 10 2 22 5 13 3 9 8 13 8 10 1 14 7 10 0 15 2 10 6 15 6 10 5 16 6 10 4 17 7 10 2 25 0 13 3 9 8 13 8 10 1 14 7 10 0 15 1 10 5 15 5 10 4 16 4 10 3 17 4 10 1 27 5 13 3 9 7 13 6 10 0 14 4 9 9 14 8 10 4 15 2 10 3 16 1 10 2 17 1 10 0 30 0 13 0 9 6 13 4 9 9 14 2 9 8 14 6 10 3 14 9 10 2 15 8 10 0 16 7 9 9 32 5 12 8 9 5 13 2 9 8 13 9 9 6 14 3 10 2 14 7 10 1 15 4 9 9 16 4 9 8 35 0 ...

Page 129: ... 1 4 9 3 1 5 0 3 3 5 2 3 3 5 5 3 2 5 8 3 2 22 5 4 4 3 0 4 5 3 1 4 8 3 1 4 9 3 2 5 1 3 2 5 4 3 2 5 7 3 1 25 0 4 3 3 0 4 4 3 1 4 7 3 0 4 9 3 2 5 0 3 2 5 3 3 1 5 6 3 1 27 5 4 2 3 0 4 3 3 0 4 6 3 0 4 8 3 2 4 9 3 1 5 2 3 1 5 5 3 1 30 0 4 1 2 9 4 2 3 0 4 5 3 0 4 7 3 1 4 8 3 1 5 1 3 1 5 4 3 0 32 5 4 1 2 9 4 2 2 9 4 4 2 9 4 6 3 1 4 7 3 1 5 0 3 0 5 3 3 0 35 0 4 0 2 9 4 1 2 9 4 3 2 9 4 5 3 0 4 6 3 0 4 9 3 0...

Page 130: ...8 16 2 10 7 17 2 10 6 18 2 10 4 22 5 13 6 9 9 14 0 10 2 14 9 10 1 15 4 10 7 15 9 10 6 16 8 10 5 17 8 10 3 25 0 13 3 9 8 13 7 10 0 14 6 10 0 15 1 10 5 15 6 10 5 16 5 10 3 17 5 10 2 27 5 13 1 9 7 13 5 9 9 14 3 9 8 14 8 10 4 15 3 10 3 16 2 10 2 17 2 10 1 30 0 12 9 9 6 13 2 9 8 14 1 9 7 14 5 10 3 15 0 10 2 15 9 10 1 16 8 9 9 32 5 12 7 9 4 12 9 9 6 13 8 9 6 14 2 10 1 14 7 10 1 15 6 10 0 16 5 9 8 35 0 1...

Page 131: ... 0 4 8 3 2 5 0 3 2 5 3 3 1 5 7 3 1 22 5 4 2 3 0 4 3 3 0 4 6 3 0 4 8 3 2 4 9 3 2 5 3 3 1 5 6 3 1 25 0 4 2 2 9 4 3 3 0 4 6 3 0 4 7 3 1 4 9 3 1 5 2 3 1 5 6 3 1 27 5 4 1 2 9 4 2 3 0 4 5 3 0 4 7 3 1 4 8 3 1 5 2 3 1 5 5 3 0 30 0 4 1 2 9 4 2 2 9 4 5 2 9 4 6 3 1 4 8 3 1 5 1 3 1 5 5 3 0 32 5 4 0 2 9 4 1 2 9 4 4 2 9 4 6 3 1 4 7 3 1 5 1 3 0 5 4 3 0 35 0 4 0 2 8 4 1 2 9 4 4 2 9 4 5 3 0 4 7 3 0 5 0 3 0 5 4 3 0...

Page 132: ... 15 5 10 5 16 5 10 3 17 6 10 2 22 5 13 1 9 7 13 5 9 9 14 4 9 9 14 9 10 4 15 4 10 4 16 4 10 3 17 4 10 2 25 0 13 0 9 6 13 3 9 8 14 3 9 8 14 7 10 4 15 2 10 3 16 2 10 2 17 3 10 1 27 5 12 8 9 5 13 2 9 8 14 1 9 7 14 6 10 3 15 1 10 3 16 1 10 2 17 1 10 0 30 0 12 7 9 5 13 0 9 7 13 9 9 6 14 4 10 2 14 9 10 2 15 9 10 1 17 0 10 0 32 5 12 6 9 4 12 8 9 6 13 8 9 6 14 3 10 2 14 8 10 1 15 8 10 0 16 8 9 9 35 0 12 4 ...

Page 133: ... 1 5 0 3 3 5 2 3 3 5 5 3 2 5 9 3 2 22 5 4 3 3 0 4 4 3 1 4 7 3 1 4 9 3 2 5 1 3 2 5 4 3 2 5 8 3 1 25 0 4 2 3 0 4 3 3 0 4 7 3 0 4 8 3 2 5 0 3 2 5 3 3 2 5 7 3 1 27 5 4 1 2 9 4 3 3 0 4 6 3 0 4 7 3 1 4 9 3 1 5 2 3 1 5 6 3 1 30 0 4 1 2 9 4 2 3 0 4 5 2 9 4 7 3 1 4 8 3 1 5 1 3 1 5 5 3 0 32 5 4 0 2 8 4 1 2 9 4 4 2 9 4 6 3 1 4 7 3 1 5 0 3 0 5 4 3 0 35 0 3 9 2 8 4 0 2 9 4 3 2 9 4 5 3 0 4 6 3 0 4 9 3 0 5 3 3 0...

Page 134: ...7 16 1 10 7 17 2 10 6 18 3 10 5 22 5 13 3 9 8 13 8 10 1 14 8 10 0 15 3 10 6 15 8 10 6 16 9 10 5 17 9 10 3 25 0 13 1 9 6 13 5 9 9 14 5 9 9 15 0 10 5 15 5 10 5 16 6 10 4 17 6 10 2 27 5 12 8 9 5 13 3 9 8 14 3 9 8 14 8 10 4 15 3 10 3 16 3 10 2 17 3 10 1 30 0 12 6 9 4 13 0 9 7 14 0 9 7 14 5 10 3 15 0 10 2 16 0 10 1 17 0 10 0 32 5 12 4 9 3 12 8 9 6 13 7 9 6 14 2 10 1 14 7 10 1 15 7 10 0 16 7 9 9 35 0 12...

Page 135: ... 0 4 8 3 2 5 0 3 2 5 3 3 1 5 7 3 1 22 5 4 2 3 0 4 3 3 0 4 6 3 0 4 8 3 2 4 9 3 2 5 3 3 1 5 6 3 1 25 0 4 2 2 9 4 3 3 0 4 6 3 0 4 7 3 1 4 9 3 1 5 2 3 1 5 6 3 1 27 5 4 1 2 9 4 2 3 0 4 5 3 0 4 7 3 1 4 8 3 1 5 2 3 1 5 5 3 0 30 0 4 1 2 9 4 2 2 9 4 5 2 9 4 6 3 1 4 8 3 1 5 1 3 1 5 5 3 0 32 5 4 0 2 9 4 1 2 9 4 4 2 9 4 6 3 1 4 7 3 1 5 1 3 0 5 4 3 0 35 0 4 0 2 8 4 1 2 9 4 4 2 9 4 5 3 0 4 7 3 0 5 0 3 0 5 4 3 0...

Page 136: ... 15 5 10 5 16 5 10 3 17 6 10 2 22 5 13 1 9 7 13 5 9 9 14 4 9 9 14 9 10 4 15 4 10 4 16 4 10 3 17 4 10 2 25 0 13 0 9 6 13 3 9 8 14 3 9 8 14 7 10 4 15 2 10 3 16 2 10 2 17 3 10 1 27 5 12 8 9 5 13 2 9 8 14 1 9 7 14 6 10 3 15 1 10 3 16 1 10 2 17 1 10 0 30 0 12 7 9 5 13 0 9 7 13 9 9 6 14 4 10 2 14 9 10 2 15 9 10 1 17 0 10 0 32 5 12 6 9 4 12 8 9 6 13 8 9 6 14 3 10 2 14 8 10 1 15 8 10 0 16 8 9 9 35 0 12 4 ...

Page 137: ... 2 32 5 2 6 2 1 2 6 2 2 2 8 2 1 2 9 2 3 2 9 2 3 3 1 2 2 3 3 2 2 35 0 2 5 2 1 2 6 2 1 2 7 2 1 2 8 2 3 2 9 2 2 3 0 2 2 3 2 2 2 37 5 2 5 2 0 2 5 2 1 2 7 2 1 2 8 2 2 2 8 2 2 3 0 2 2 3 1 2 1 40 0 2 4 2 0 2 5 2 1 2 6 2 1 2 7 2 2 2 8 2 2 2 9 2 2 3 1 2 1 43 0 2 4 2 0 2 4 2 1 2 6 2 0 2 6 2 2 2 7 2 2 2 8 2 1 3 0 2 1 32 3 6 20 0 3 4 2 6 3 5 2 7 3 8 2 7 3 9 2 8 4 0 2 8 4 3 2 8 4 6 2 8 22 5 3 4 2 6 3 5 2 7 3 8...

Page 138: ... 2 25 0 6 7 4 9 7 0 5 1 7 5 5 0 7 7 5 3 7 9 5 3 8 3 5 2 8 8 5 1 27 5 6 7 4 9 6 9 5 0 7 3 5 0 7 5 5 2 7 7 5 2 8 1 5 1 8 7 5 0 30 0 6 6 4 8 6 8 5 0 7 2 4 9 7 4 5 2 7 6 5 1 8 0 5 0 8 5 5 0 32 5 6 5 4 8 6 7 4 9 7 1 4 8 7 2 5 1 7 4 5 1 7 8 5 0 8 3 4 9 35 0 6 4 4 7 6 5 4 8 6 9 4 8 7 1 5 0 7 3 5 0 7 7 4 9 8 1 4 8 37 5 6 2 4 7 6 4 4 8 6 8 4 7 7 0 5 0 7 2 5 0 7 5 4 9 8 0 4 8 40 0 6 1 4 6 6 3 4 7 6 7 4 7 6 ...

Page 139: ...2 6 2 1 2 8 2 1 2 8 2 3 2 9 2 3 3 1 2 2 3 3 2 2 35 0 2 5 2 1 2 5 2 1 2 7 2 1 2 8 2 3 2 9 2 2 3 0 2 2 3 2 2 2 37 5 2 5 2 0 2 5 2 1 2 6 2 1 2 7 2 2 2 8 2 2 3 0 2 2 3 2 2 2 40 0 2 4 2 0 2 4 2 1 2 6 2 1 2 7 2 2 2 8 2 2 2 9 2 2 3 1 2 1 43 0 2 4 2 0 2 4 2 0 2 5 2 0 2 6 2 2 2 7 2 2 2 8 2 1 3 0 2 1 32 3 6 20 0 3 5 2 6 3 6 2 7 3 9 2 7 4 0 2 9 4 2 2 9 4 4 2 8 4 7 2 8 22 5 3 5 2 6 3 6 2 7 3 8 2 7 4 0 2 9 4 1...

Page 140: ... 25 0 6 8 4 9 7 0 5 0 7 4 5 0 7 7 5 3 7 9 5 3 8 4 5 2 8 9 5 1 27 5 6 7 4 9 6 8 5 0 7 3 4 9 7 5 5 2 7 7 5 2 8 2 5 1 8 7 5 1 30 0 6 5 4 8 6 7 4 9 7 1 4 9 7 4 5 2 7 6 5 1 8 1 5 1 8 5 5 0 32 5 6 4 4 8 6 6 4 9 7 0 4 8 7 2 5 1 7 4 5 1 7 9 5 0 8 4 4 9 35 0 6 3 4 7 6 4 4 8 6 8 4 8 7 1 5 0 7 3 5 0 7 7 4 9 8 2 4 9 37 5 6 2 4 6 6 3 4 7 6 7 4 7 6 9 5 0 7 1 4 9 7 6 4 9 8 0 4 8 40 0 6 1 4 6 6 2 4 7 6 6 4 6 6 8 ...

Page 141: ...2 8 2 1 2 9 2 3 3 0 2 3 3 2 2 2 3 4 2 2 35 0 2 5 2 1 2 5 2 1 2 7 2 1 2 8 2 3 2 9 2 3 3 1 2 2 3 3 2 2 37 5 2 5 2 0 2 5 2 1 2 7 2 1 2 8 2 2 2 9 2 2 3 1 2 2 3 3 2 2 40 0 2 4 2 0 2 5 2 1 2 7 2 1 2 8 2 2 2 9 2 2 3 1 2 2 3 3 2 2 43 0 2 4 2 0 2 4 2 1 2 6 2 1 2 7 2 2 2 8 2 2 3 0 2 2 3 2 2 2 32 3 6 20 0 3 4 2 6 3 5 2 7 3 7 2 7 3 9 2 8 4 0 2 8 4 3 2 8 4 5 2 7 22 5 3 4 2 6 3 5 2 7 3 7 2 6 3 8 2 8 4 0 2 8 4 2...

Page 142: ...5 1 25 0 6 6 4 8 6 8 4 9 7 2 4 9 7 5 5 2 7 7 5 2 8 2 5 1 8 8 5 1 27 5 6 5 4 8 6 7 4 9 7 2 4 9 7 4 5 2 7 6 5 2 8 2 5 1 8 7 5 0 30 0 6 4 4 8 6 6 4 9 7 1 4 9 7 3 5 1 7 6 5 1 8 1 5 1 8 6 5 0 32 5 6 4 4 7 6 5 4 8 7 0 4 8 7 2 5 1 7 5 5 1 8 0 5 0 8 5 5 0 35 0 6 3 4 7 6 4 4 8 6 9 4 8 7 1 5 0 7 4 5 1 7 9 5 0 8 5 5 0 37 5 6 2 4 7 6 3 4 8 6 8 4 7 7 1 5 0 7 3 5 0 7 8 5 0 8 4 4 9 40 0 6 2 4 6 6 3 4 7 6 7 4 7 7...

Page 143: ...2 7 2 1 2 8 2 3 2 9 2 3 3 1 2 2 3 3 2 2 35 0 2 4 2 0 2 5 2 1 2 7 2 1 2 8 2 3 2 9 2 2 3 1 2 2 3 3 2 2 37 5 2 4 2 0 2 5 2 1 2 6 2 1 2 7 2 2 2 8 2 2 3 0 2 2 3 2 2 2 40 0 2 3 2 0 2 4 2 1 2 6 2 1 2 7 2 2 2 8 2 2 3 0 2 2 3 1 2 1 43 0 2 3 2 0 2 4 2 0 2 5 2 0 2 6 2 2 2 7 2 2 2 9 2 1 3 1 2 1 32 3 6 20 0 3 5 2 6 3 6 2 7 3 9 2 7 4 0 2 9 4 1 2 9 4 4 2 8 4 7 2 8 22 5 3 4 2 6 3 5 2 7 3 8 2 7 3 9 2 8 4 1 2 8 4 3...

Page 144: ...2 25 0 6 6 4 9 6 9 5 0 7 4 5 0 7 6 5 3 7 9 5 3 8 4 5 2 8 9 5 1 27 5 6 5 4 8 6 7 4 9 7 2 4 9 7 5 5 2 7 7 5 2 8 3 5 1 8 8 5 1 30 0 6 4 4 7 6 6 4 9 7 1 4 9 7 3 5 2 7 6 5 1 8 1 5 1 8 6 5 0 32 5 6 3 4 7 6 5 4 8 7 0 4 8 7 2 5 1 7 5 5 1 7 9 5 0 8 5 5 0 35 0 6 2 4 6 6 4 4 8 6 8 4 7 7 1 5 0 7 3 5 0 7 8 5 0 8 3 4 9 37 5 6 1 4 6 6 2 4 7 6 7 4 7 6 9 5 0 7 2 5 0 7 6 4 9 8 1 4 8 40 0 5 9 4 5 6 1 4 6 6 6 4 6 6 8...

Page 145: ...2 8 2 1 2 9 2 3 3 0 2 3 3 2 2 2 3 4 2 2 35 0 2 5 2 1 2 5 2 1 2 7 2 1 2 8 2 3 2 9 2 3 3 1 2 2 3 3 2 2 37 5 2 5 2 0 2 5 2 1 2 7 2 1 2 8 2 2 2 9 2 2 3 1 2 2 3 3 2 2 40 0 2 4 2 0 2 5 2 1 2 7 2 1 2 8 2 2 2 9 2 2 3 1 2 2 3 3 2 2 43 0 2 4 2 0 2 4 2 1 2 6 2 1 2 7 2 2 2 8 2 2 3 0 2 2 3 2 2 2 32 3 6 20 0 3 4 2 6 3 5 2 7 3 7 2 7 3 9 2 8 4 0 2 8 4 3 2 8 4 5 2 7 22 5 3 4 2 6 3 5 2 7 3 7 2 6 3 8 2 8 4 0 2 8 4 2...

Page 146: ...5 1 25 0 6 6 4 8 6 8 4 9 7 2 4 9 7 5 5 2 7 7 5 2 8 2 5 1 8 8 5 1 27 5 6 5 4 8 6 7 4 9 7 2 4 9 7 4 5 2 7 6 5 2 8 2 5 1 8 7 5 0 30 0 6 4 4 8 6 6 4 9 7 1 4 9 7 3 5 1 7 6 5 1 8 1 5 1 8 6 5 0 32 5 6 4 4 7 6 5 4 8 7 0 4 8 7 2 5 1 7 5 5 1 8 0 5 0 8 5 5 0 35 0 6 3 4 7 6 4 4 8 6 9 4 8 7 1 5 0 7 4 5 1 7 9 5 0 8 5 5 0 37 5 6 2 4 7 6 3 4 8 6 8 4 7 7 1 5 0 7 3 5 0 7 8 5 0 8 4 4 9 40 0 6 2 4 6 6 3 4 7 6 7 4 7 7...

Page 147: ...6 9 4 7 7 1 4 9 7 3 4 9 7 7 4 8 8 1 4 7 37 5 6 2 4 5 6 4 4 6 6 8 4 6 7 0 4 8 7 2 4 8 7 5 4 7 8 0 4 6 40 0 6 1 4 5 6 3 4 6 6 7 4 5 6 8 4 8 7 0 4 7 7 4 4 6 7 8 4 6 43 0 6 0 4 4 6 1 4 5 6 5 4 5 6 7 4 7 6 9 4 7 7 2 4 6 7 6 4 5 100 11 2 20 0 10 6 7 4 11 0 7 6 11 8 7 6 12 1 8 0 12 5 7 9 13 2 7 8 14 2 7 8 22 5 10 6 7 4 11 0 7 6 11 8 7 6 12 1 8 0 12 5 7 9 13 2 7 8 14 2 7 8 25 0 10 6 7 4 11 0 7 6 11 8 7 6 ...

Page 148: ...1 4 9 7 3 4 8 7 7 4 8 8 2 4 7 37 5 6 2 4 5 6 3 4 6 6 7 4 5 6 9 4 8 7 1 4 8 7 6 4 7 8 0 4 6 40 0 6 1 4 5 6 2 4 5 6 6 4 5 6 8 4 7 7 0 4 7 7 4 4 7 7 8 4 6 43 0 6 0 4 4 6 0 4 4 6 4 4 4 6 6 4 7 6 8 4 6 7 2 4 6 7 6 4 5 100 11 2 20 0 10 9 7 6 11 3 7 8 12 1 7 8 12 5 8 2 12 9 8 1 13 7 8 0 14 5 7 9 22 5 10 8 7 5 11 2 7 7 11 9 7 7 12 3 8 1 12 7 8 0 13 5 7 9 14 3 7 8 25 0 10 7 7 5 11 0 7 6 11 7 7 6 12 1 8 0 1...

Page 149: ... 7 4 4 9 7 9 4 9 8 5 4 8 37 5 6 2 4 5 6 3 4 6 6 8 4 6 7 1 4 9 7 3 4 9 7 8 4 8 8 4 4 8 40 0 6 2 4 5 6 3 4 6 6 7 4 6 7 0 4 8 7 2 4 8 7 8 4 8 8 3 4 8 43 0 6 1 4 5 6 2 4 5 6 7 4 5 6 9 4 8 7 1 4 8 7 7 4 8 8 2 4 7 100 11 2 20 0 10 6 7 4 10 9 7 6 11 7 7 6 12 0 7 9 12 4 7 9 13 2 7 8 14 1 7 7 22 5 10 5 7 3 10 8 7 5 11 5 7 5 11 9 7 9 12 3 7 8 13 1 7 8 13 9 7 7 25 0 10 4 7 3 10 6 7 5 11 4 7 4 11 8 7 8 12 2 7...

Page 150: ... 3 4 9 7 8 4 8 8 3 4 7 37 5 6 1 4 4 6 2 4 6 6 7 4 5 6 9 4 8 7 2 4 8 7 6 4 8 8 1 4 7 40 0 5 9 4 4 6 1 4 5 6 6 4 5 6 8 4 8 7 0 4 7 7 5 4 7 8 0 4 6 43 0 5 8 4 3 6 0 4 4 6 4 4 4 6 6 4 7 6 9 4 7 7 3 4 6 7 8 4 6 100 11 2 20 0 10 8 7 5 11 2 7 7 12 0 7 7 12 5 8 1 12 9 8 1 13 7 8 0 14 6 7 9 22 5 10 6 7 4 11 0 7 6 11 8 7 6 12 2 8 0 12 6 8 0 13 5 7 9 14 4 7 8 25 0 10 5 7 3 10 8 7 5 11 6 7 5 12 0 7 9 12 4 7 9...

Page 151: ... 7 4 4 9 7 9 4 9 8 5 4 8 37 5 6 2 4 5 6 3 4 6 6 8 4 6 7 1 4 9 7 3 4 9 7 8 4 8 8 4 4 8 40 0 6 2 4 5 6 3 4 6 6 7 4 6 7 0 4 8 7 2 4 8 7 8 4 8 8 3 4 8 43 0 6 1 4 5 6 2 4 5 6 7 4 5 6 9 4 8 7 1 4 8 7 7 4 8 8 2 4 7 100 11 2 20 0 10 6 7 4 10 9 7 6 11 7 7 6 12 0 7 9 12 4 7 9 13 2 7 8 14 1 7 7 22 5 10 5 7 3 10 8 7 5 11 5 7 5 11 9 7 9 12 3 7 8 13 1 7 8 13 9 7 7 25 0 10 4 7 3 10 6 7 5 11 4 7 4 11 8 7 8 12 2 7...

Page 152: ... 2 6 3 5 2 7 3 8 2 7 3 9 2 8 4 0 2 8 4 3 2 8 4 6 2 8 22 5 3 4 2 6 3 5 2 7 3 8 2 7 3 9 2 8 4 0 2 8 4 3 2 8 4 6 2 8 25 0 3 4 2 6 3 5 2 7 3 8 2 7 3 9 2 8 4 0 2 8 4 2 2 8 4 5 2 7 27 5 3 4 2 6 3 5 2 7 3 7 2 7 3 8 2 8 3 9 2 8 4 1 2 7 4 4 2 7 30 0 3 3 2 6 3 4 2 7 3 6 2 6 3 7 2 8 3 8 2 8 4 1 2 7 4 3 2 7 32 5 3 3 2 5 3 4 2 6 3 6 2 6 3 7 2 8 3 8 2 7 4 0 2 7 4 2 2 6 35 0 3 2 2 5 3 3 2 6 3 5 2 6 3 6 2 7 3 7 2...

Page 153: ...11 7 7 9 12 4 7 7 13 1 7 6 35 0 10 0 7 3 10 3 7 5 10 9 7 4 11 2 7 8 11 5 7 8 12 1 7 6 12 8 7 5 37 5 9 8 7 2 10 1 7 4 10 7 7 3 11 0 7 7 11 3 7 7 11 9 7 5 12 6 7 4 40 0 9 6 7 1 9 9 7 3 10 5 7 2 10 8 7 6 11 1 7 6 11 6 7 4 12 3 7 3 43 0 9 4 7 0 9 7 7 2 10 2 7 1 10 5 7 5 10 8 7 5 11 3 7 3 12 0 7 2 PKFY P VBM E VHM E VKM E CA Capacity kW SHC Sensible Heat Capacity kW Model Outdoor Indoor air temp size a...

Page 154: ...3 6 2 7 3 9 2 7 4 0 2 9 4 2 2 9 4 4 2 9 4 7 2 8 22 5 3 5 2 6 3 6 2 7 3 8 2 7 4 0 2 9 4 1 2 9 4 3 2 8 4 6 2 8 25 0 3 4 2 6 3 5 2 7 3 8 2 7 3 9 2 8 4 0 2 8 4 2 2 8 4 5 2 7 27 5 3 4 2 6 3 5 2 7 3 7 2 6 3 8 2 8 3 9 2 8 4 2 2 8 4 4 2 7 30 0 3 3 2 6 3 4 2 6 3 6 2 6 3 7 2 8 3 8 2 8 4 1 2 7 4 3 2 7 32 5 3 3 2 5 3 3 2 6 3 5 2 6 3 7 2 7 3 8 2 7 4 0 2 7 4 2 2 7 35 0 3 2 2 5 3 3 2 6 3 5 2 5 3 6 2 7 3 7 2 7 3 ...

Page 155: ...11 7 7 9 12 4 7 8 13 2 7 6 35 0 10 0 7 3 10 1 7 4 10 8 7 4 11 2 7 8 11 5 7 8 12 2 7 6 12 9 7 5 37 5 9 8 7 2 9 9 7 3 10 6 7 3 10 9 7 7 11 2 7 6 11 9 7 5 12 6 7 4 40 0 9 6 7 1 9 7 7 2 10 3 7 2 10 7 7 6 11 0 7 5 11 7 7 4 12 4 7 3 43 0 9 4 7 0 9 5 7 1 10 1 7 0 10 4 7 5 10 7 7 4 11 4 7 3 12 1 7 2 PKFY P VBM E VHM E VKM E CA Capacity kW SHC Sensible Heat Capacity kW Model Outdoor Indoor air temp size ai...

Page 156: ...3 7 2 7 3 9 2 8 4 0 2 8 4 3 2 8 4 5 2 8 22 5 3 4 2 6 3 5 2 7 3 7 2 7 3 8 2 8 4 0 2 8 4 2 2 8 4 5 2 7 25 0 3 3 2 6 3 4 2 6 3 7 2 6 3 8 2 8 3 9 2 8 4 2 2 8 4 4 2 7 27 5 3 3 2 6 3 4 2 6 3 6 2 6 3 8 2 8 3 9 2 8 4 1 2 7 4 4 2 7 30 0 3 3 2 5 3 3 2 6 3 6 2 6 3 7 2 8 3 8 2 8 4 1 2 7 4 4 2 7 32 5 3 2 2 5 3 3 2 6 3 5 2 6 3 7 2 8 3 8 2 7 4 1 2 7 4 3 2 7 35 0 3 2 2 5 3 3 2 6 3 5 2 6 3 6 2 7 3 8 2 7 4 0 2 7 4 ...

Page 157: ...11 8 7 9 12 6 7 8 13 5 7 7 35 0 9 9 7 3 10 1 7 4 10 9 7 4 11 2 7 8 11 7 7 8 12 5 7 8 13 3 7 7 37 5 9 8 7 2 10 0 7 4 10 8 7 4 11 2 7 8 11 6 7 8 12 4 7 7 13 2 7 6 40 0 9 7 7 2 9 9 7 3 10 6 7 3 11 0 7 7 11 4 7 7 12 2 7 7 13 1 7 6 43 0 9 6 7 1 9 7 7 2 10 5 7 2 10 9 7 7 11 3 7 7 12 1 7 6 12 9 7 5 PKFY P VBM E VHM E VKM E CA Capacity kW SHC Sensible Heat Capacity kW Model Outdoor Indoor air temp size ai...

Page 158: ...3 9 2 7 4 0 2 9 4 1 2 9 4 4 2 9 4 7 2 8 22 5 3 4 2 6 3 5 2 7 3 8 2 7 3 9 2 9 4 1 2 9 4 3 2 8 4 6 2 8 25 0 3 4 2 6 3 5 2 7 3 7 2 7 3 9 2 8 4 0 2 8 4 3 2 8 4 5 2 8 27 5 3 3 2 6 3 4 2 6 3 7 2 6 3 8 2 8 3 9 2 8 4 2 2 8 4 5 2 7 30 0 3 2 2 5 3 4 2 6 3 6 2 6 3 7 2 8 3 9 2 8 4 1 2 7 4 4 2 7 32 5 3 2 2 5 3 3 2 6 3 5 2 6 3 7 2 7 3 8 2 7 4 0 2 7 4 3 2 7 35 0 3 1 2 5 3 2 2 6 3 5 2 5 3 6 2 7 3 7 2 7 4 0 2 7 4 ...

Page 159: ...11 8 7 9 12 5 7 8 13 3 7 7 35 0 9 7 7 2 10 0 7 4 10 8 7 4 11 2 7 8 11 5 7 8 12 3 7 7 13 1 7 6 37 5 9 5 7 1 9 8 7 3 10 6 7 3 10 9 7 7 11 3 7 7 12 1 7 6 12 8 7 5 40 0 9 4 7 0 9 6 7 2 10 4 7 2 10 7 7 6 11 1 7 6 11 8 7 5 12 6 7 4 43 0 9 2 6 9 9 4 7 1 10 1 7 1 10 5 7 5 10 8 7 5 11 5 7 4 12 3 7 3 PKFY P VBM E VHM E VKM E CA Capacity kW SHC Sensible Heat Capacity kW Model Outdoor Indoor air temp size air...

Page 160: ...3 7 2 7 3 9 2 8 4 0 2 8 4 3 2 8 4 5 2 8 22 5 3 4 2 6 3 5 2 7 3 7 2 7 3 8 2 8 4 0 2 8 4 2 2 8 4 5 2 7 25 0 3 3 2 6 3 4 2 6 3 7 2 6 3 8 2 8 3 9 2 8 4 2 2 8 4 4 2 7 27 5 3 3 2 6 3 4 2 6 3 6 2 6 3 8 2 8 3 9 2 8 4 1 2 7 4 4 2 7 30 0 3 3 2 5 3 3 2 6 3 6 2 6 3 7 2 8 3 8 2 8 4 1 2 7 4 4 2 7 32 5 3 2 2 5 3 3 2 6 3 5 2 6 3 7 2 8 3 8 2 7 4 1 2 7 4 3 2 7 35 0 3 2 2 5 3 3 2 6 3 5 2 6 3 6 2 7 3 8 2 7 4 0 2 7 4 ...

Page 161: ...11 8 7 9 12 6 7 8 13 5 7 7 35 0 9 9 7 3 10 1 7 4 10 9 7 4 11 2 7 8 11 7 7 8 12 5 7 8 13 3 7 7 37 5 9 8 7 2 10 0 7 4 10 8 7 4 11 2 7 8 11 6 7 8 12 4 7 7 13 2 7 6 40 0 9 7 7 2 9 9 7 3 10 6 7 3 11 0 7 7 11 4 7 7 12 2 7 7 13 1 7 6 43 0 9 6 7 1 9 7 7 2 10 5 7 2 10 9 7 7 11 3 7 7 12 1 7 6 12 9 7 5 PKFY P VBM E VHM E VKM E CA Capacity kW SHC Sensible Heat Capacity kW Model Outdoor Indoor air temp size ai...

Page 162: ...0 2 1 3 2 2 1 3 3 2 0 32 5 2 6 1 9 2 6 2 0 2 8 2 0 2 9 2 1 2 9 2 1 3 1 2 0 3 3 2 0 35 0 2 5 1 9 2 6 2 0 2 7 1 9 2 8 2 1 2 9 2 0 3 0 2 0 3 2 2 0 37 5 2 5 1 9 2 5 1 9 2 7 1 9 2 8 2 0 2 8 2 0 3 0 2 0 3 1 2 0 40 0 2 4 1 9 2 5 1 9 2 6 1 9 2 7 2 0 2 8 2 0 2 9 2 0 3 1 1 9 43 0 2 4 1 8 2 4 1 9 2 6 1 9 2 6 2 0 2 7 2 0 2 8 1 9 3 0 1 9 32 3 6 20 0 3 4 2 4 3 5 2 5 3 8 2 5 3 9 2 6 4 0 2 6 4 3 2 6 4 6 2 5 22 5 ...

Page 163: ... 7 2 6 3 8 2 6 4 0 2 5 4 2 2 5 35 0 3 2 2 4 3 3 2 4 3 5 2 4 3 6 2 5 3 7 2 5 3 9 2 5 4 1 2 4 37 5 3 2 2 3 3 3 2 4 3 4 2 4 3 5 2 5 3 6 2 5 3 8 2 5 4 0 2 4 40 0 3 1 2 3 3 2 2 4 3 4 2 4 3 5 2 5 3 6 2 5 3 7 2 4 3 9 2 4 43 0 3 0 2 3 3 1 2 3 3 3 2 3 3 4 2 5 3 5 2 4 3 6 2 4 3 8 2 3 40 4 5 20 0 4 3 3 1 4 4 3 2 4 7 3 2 4 9 3 4 5 0 3 3 5 3 3 3 5 7 3 3 22 5 4 3 3 1 4 4 3 2 4 7 3 2 4 9 3 4 5 0 3 3 5 3 3 3 5 7 ...

Page 164: ...2 6 3 8 2 6 4 0 2 5 4 2 2 5 35 0 3 2 2 4 3 3 2 4 3 5 2 4 3 6 2 5 3 7 2 5 3 9 2 5 4 1 2 4 37 5 3 2 2 3 3 3 2 4 3 4 2 4 3 5 2 5 3 6 2 5 3 8 2 5 4 0 2 4 40 0 3 1 2 3 3 2 2 4 3 4 2 4 3 5 2 5 3 6 2 5 3 7 2 4 3 9 2 4 43 0 3 0 2 3 3 1 2 3 3 3 2 3 3 4 2 5 3 5 2 4 3 6 2 4 3 8 2 3 40 4 5 20 0 4 3 3 1 4 4 3 2 4 7 3 2 4 9 3 4 5 0 3 3 5 3 3 3 5 7 3 3 22 5 4 3 3 1 4 4 3 2 4 7 3 2 4 9 3 4 5 0 3 3 5 3 3 3 5 7 3 3...

Page 165: ...5 2 5 1 9 2 6 2 0 2 8 2 0 2 8 2 1 2 9 2 1 3 1 2 0 3 3 2 0 35 0 2 5 1 9 2 5 1 9 2 7 1 9 2 8 2 1 2 9 2 0 3 0 2 0 3 2 2 0 37 5 2 5 1 9 2 5 1 9 2 6 1 9 2 7 2 0 2 8 2 0 3 0 2 0 3 2 2 0 40 0 2 4 1 9 2 4 1 9 2 6 1 9 2 7 2 0 2 8 2 0 2 9 2 0 3 1 1 9 43 0 2 4 1 8 2 4 1 9 2 5 1 9 2 6 2 0 2 7 2 0 2 8 1 9 3 0 1 9 32 3 6 20 0 3 5 2 5 3 6 2 5 3 9 2 5 4 0 2 7 4 2 2 7 4 4 2 6 4 7 2 6 22 5 3 5 2 5 3 6 2 5 3 8 2 5 4...

Page 166: ... 7 2 6 3 8 2 6 4 0 2 5 4 2 2 5 35 0 3 2 2 4 3 3 2 4 3 5 2 4 3 6 2 5 3 7 2 5 3 9 2 5 4 2 2 5 37 5 3 2 2 3 3 2 2 4 3 4 2 4 3 5 2 5 3 6 2 5 3 8 2 5 4 1 2 4 40 0 3 1 2 3 3 1 2 4 3 3 2 3 3 4 2 5 3 5 2 5 3 8 2 4 4 0 2 4 43 0 3 0 2 3 3 0 2 3 3 2 2 3 3 3 2 4 3 4 2 4 3 7 2 4 3 9 2 4 40 4 5 20 0 4 4 3 2 4 5 3 3 4 9 3 3 5 0 3 4 5 2 3 4 5 5 3 4 5 8 3 3 22 5 4 4 3 2 4 5 3 2 4 8 3 2 4 9 3 4 5 1 3 4 5 4 3 3 5 7 ...

Page 167: ...2 6 3 8 2 6 4 0 2 5 4 2 2 5 35 0 3 2 2 4 3 3 2 4 3 5 2 4 3 6 2 5 3 7 2 5 3 9 2 5 4 2 2 5 37 5 3 2 2 3 3 2 2 4 3 4 2 4 3 5 2 5 3 6 2 5 3 8 2 5 4 1 2 4 40 0 3 1 2 3 3 1 2 4 3 3 2 3 3 4 2 5 3 5 2 5 3 8 2 4 4 0 2 4 43 0 3 0 2 3 3 0 2 3 3 2 2 3 3 3 2 4 3 4 2 4 3 7 2 4 3 9 2 4 40 4 5 20 0 4 4 3 2 4 5 3 3 4 9 3 3 5 0 3 4 5 2 3 4 5 5 3 4 5 8 3 3 22 5 4 4 3 2 4 5 3 2 4 8 3 2 4 9 3 4 5 1 3 4 5 4 3 3 5 7 3 3...

Page 168: ...9 2 6 2 0 2 8 2 0 2 9 2 1 3 0 2 1 3 2 2 1 3 4 2 0 35 0 2 5 1 9 2 5 1 9 2 7 1 9 2 8 2 1 2 9 2 1 3 1 2 0 3 3 2 0 37 5 2 5 1 9 2 5 1 9 2 7 1 9 2 8 2 1 2 9 2 1 3 1 2 0 3 3 2 0 40 0 2 4 1 9 2 5 1 9 2 7 1 9 2 8 2 0 2 9 2 0 3 1 2 0 3 3 2 0 43 0 2 4 1 9 2 4 1 9 2 6 1 9 2 7 2 0 2 8 2 0 3 0 2 0 3 2 2 0 32 3 6 20 0 3 4 2 4 3 5 2 5 3 7 2 5 3 9 2 6 4 0 2 6 4 3 2 6 4 5 2 5 22 5 3 4 2 4 3 5 2 5 3 7 2 4 3 8 2 6 4...

Page 169: ... 7 2 6 3 8 2 6 4 1 2 5 4 3 2 5 35 0 3 2 2 4 3 3 2 4 3 5 2 4 3 6 2 5 3 8 2 6 4 0 2 5 4 3 2 5 37 5 3 2 2 3 3 2 2 4 3 5 2 4 3 6 2 5 3 7 2 5 4 0 2 5 4 2 2 5 40 0 3 1 2 3 3 2 2 4 3 4 2 4 3 5 2 5 3 7 2 5 3 9 2 5 4 2 2 5 43 0 3 1 2 3 3 1 2 4 3 4 2 4 3 5 2 5 3 6 2 5 3 9 2 5 4 2 2 5 40 4 5 20 0 4 3 3 1 4 4 3 2 4 7 3 2 4 8 3 4 5 0 3 3 5 3 3 3 5 7 3 3 22 5 4 2 3 1 4 3 3 2 4 6 3 1 4 8 3 3 4 9 3 3 5 3 3 3 5 6 ...

Page 170: ...2 6 3 8 2 6 4 1 2 5 4 3 2 5 35 0 3 2 2 4 3 3 2 4 3 5 2 4 3 6 2 5 3 8 2 6 4 0 2 5 4 3 2 5 37 5 3 2 2 3 3 2 2 4 3 5 2 4 3 6 2 5 3 7 2 5 4 0 2 5 4 2 2 5 40 0 3 1 2 3 3 2 2 4 3 4 2 4 3 5 2 5 3 7 2 5 3 9 2 5 4 2 2 5 43 0 3 1 2 3 3 1 2 4 3 4 2 4 3 5 2 5 3 6 2 5 3 9 2 5 4 2 2 5 40 4 5 20 0 4 3 3 1 4 4 3 2 4 7 3 2 4 8 3 4 5 0 3 3 5 3 3 3 5 7 3 3 22 5 4 2 3 1 4 3 3 2 4 6 3 1 4 8 3 3 4 9 3 3 5 3 3 3 5 6 3 2...

Page 171: ...9 2 6 2 0 2 7 2 0 2 8 2 1 2 9 2 1 3 1 2 1 3 3 2 0 35 0 2 4 1 9 2 5 1 9 2 7 1 9 2 8 2 1 2 9 2 0 3 1 2 0 3 3 2 0 37 5 2 4 1 9 2 5 1 9 2 6 1 9 2 7 2 0 2 8 2 0 3 0 2 0 3 2 2 0 40 0 2 3 1 8 2 4 1 9 2 6 1 9 2 7 2 0 2 8 2 0 3 0 2 0 3 1 2 0 43 0 2 3 1 8 2 4 1 9 2 5 1 9 2 6 2 0 2 7 2 0 2 9 2 0 3 1 1 9 32 3 6 20 0 3 5 2 5 3 6 2 5 3 9 2 5 4 0 2 7 4 1 2 6 4 4 2 6 4 7 2 6 22 5 3 4 2 4 3 5 2 5 3 8 2 5 3 9 2 6 4...

Page 172: ... 7 2 6 3 8 2 6 4 0 2 5 4 3 2 5 35 0 3 1 2 3 3 2 2 4 3 5 2 4 3 6 2 5 3 7 2 5 4 0 2 5 4 2 2 5 37 5 3 1 2 3 3 2 2 4 3 4 2 4 3 5 2 5 3 6 2 5 3 9 2 5 4 1 2 4 40 0 3 0 2 3 3 1 2 3 3 3 2 3 3 4 2 5 3 6 2 5 3 8 2 4 4 0 2 4 43 0 2 9 2 2 3 0 2 3 3 2 2 3 3 4 2 4 3 5 2 4 3 7 2 4 3 9 2 4 40 4 5 20 0 4 3 3 1 4 5 3 2 4 8 3 2 5 0 3 4 5 2 3 4 5 5 3 4 5 9 3 3 22 5 4 3 3 1 4 4 3 2 4 7 3 2 4 9 3 4 5 1 3 4 5 4 3 3 5 8 ...

Page 173: ...2 6 3 8 2 6 4 0 2 5 4 3 2 5 35 0 3 1 2 3 3 2 2 4 3 5 2 4 3 6 2 5 3 7 2 5 4 0 2 5 4 2 2 5 37 5 3 1 2 3 3 2 2 4 3 4 2 4 3 5 2 5 3 6 2 5 3 9 2 5 4 1 2 4 40 0 3 0 2 3 3 1 2 3 3 3 2 3 3 4 2 5 3 6 2 5 3 8 2 4 4 0 2 4 43 0 2 9 2 2 3 0 2 3 3 2 2 3 3 4 2 4 3 5 2 4 3 7 2 4 3 9 2 4 40 4 5 20 0 4 3 3 1 4 5 3 2 4 8 3 2 5 0 3 4 5 2 3 4 5 5 3 4 5 9 3 3 22 5 4 3 3 1 4 4 3 2 4 7 3 2 4 9 3 4 5 1 3 4 5 4 3 3 5 8 3 3...

Page 174: ...9 2 6 2 0 2 8 2 0 2 9 2 1 3 0 2 1 3 2 2 1 3 4 2 0 35 0 2 5 1 9 2 5 1 9 2 7 1 9 2 8 2 1 2 9 2 1 3 1 2 0 3 3 2 0 37 5 2 5 1 9 2 5 1 9 2 7 1 9 2 8 2 1 2 9 2 1 3 1 2 0 3 3 2 0 40 0 2 4 1 9 2 5 1 9 2 7 1 9 2 8 2 0 2 9 2 0 3 1 2 0 3 3 2 0 43 0 2 4 1 9 2 4 1 9 2 6 1 9 2 7 2 0 2 8 2 0 3 0 2 0 3 2 2 0 32 3 6 20 0 3 4 2 4 3 5 2 5 3 7 2 5 3 9 2 6 4 0 2 6 4 3 2 6 4 5 2 5 22 5 3 4 2 4 3 5 2 5 3 7 2 4 3 8 2 6 4...

Page 175: ... 7 2 6 3 8 2 6 4 1 2 5 4 3 2 5 35 0 3 2 2 4 3 3 2 4 3 5 2 4 3 6 2 5 3 8 2 6 4 0 2 5 4 3 2 5 37 5 3 2 2 3 3 2 2 4 3 5 2 4 3 6 2 5 3 7 2 5 4 0 2 5 4 2 2 5 40 0 3 1 2 3 3 2 2 4 3 4 2 4 3 5 2 5 3 7 2 5 3 9 2 5 4 2 2 5 43 0 3 1 2 3 3 1 2 4 3 4 2 4 3 5 2 5 3 6 2 5 3 9 2 5 4 2 2 5 40 4 5 20 0 4 3 3 1 4 4 3 2 4 7 3 2 4 8 3 4 5 0 3 3 5 3 3 3 5 7 3 3 22 5 4 2 3 1 4 3 3 2 4 6 3 1 4 8 3 3 4 9 3 3 5 3 3 3 5 6 ...

Page 176: ...2 6 3 8 2 6 4 1 2 5 4 3 2 5 35 0 3 2 2 4 3 3 2 4 3 5 2 4 3 6 2 5 3 8 2 6 4 0 2 5 4 3 2 5 37 5 3 2 2 3 3 2 2 4 3 5 2 4 3 6 2 5 3 7 2 5 4 0 2 5 4 2 2 5 40 0 3 1 2 3 3 2 2 4 3 4 2 4 3 5 2 5 3 7 2 5 3 9 2 5 4 2 2 5 43 0 3 1 2 3 3 1 2 4 3 4 2 4 3 5 2 5 3 6 2 5 3 9 2 5 4 2 2 5 40 4 5 20 0 4 3 3 1 4 4 3 2 4 7 3 2 4 8 3 4 5 0 3 3 5 3 3 3 5 7 3 3 22 5 4 2 3 1 4 3 3 2 4 6 3 1 4 8 3 3 4 9 3 3 5 3 3 3 5 6 3 2...

Page 177: ... 7 2 7 2 7 125 16 0 20 0 11 1 10 9 10 8 10 7 15 0 3 0 3 0 2 9 2 8 15 0 11 9 11 9 11 5 11 1 10 0 3 3 3 3 3 2 2 8 10 0 13 2 13 1 12 6 11 2 5 0 3 7 3 7 3 2 2 8 5 0 15 0 14 8 12 8 11 2 0 0 4 0 4 0 3 2 2 8 0 0 16 2 16 0 12 8 11 2 2 5 4 0 4 0 3 2 2 8 2 5 16 2 16 0 12 8 11 2 6 0 4 0 4 0 3 2 2 8 6 0 16 2 16 0 12 8 11 2 7 5 4 1 4 0 3 2 2 8 7 5 16 6 16 0 12 8 11 2 10 0 4 4 4 0 3 2 2 8 10 0 17 4 16 0 12 8 11...

Page 178: ...25 16 0 20 0 10 3 10 3 10 3 9 9 15 0 2 8 2 8 2 8 2 6 15 0 11 1 11 2 11 1 10 2 10 0 3 1 3 1 3 0 2 6 10 0 12 3 12 3 11 9 10 2 5 0 3 5 3 5 3 0 2 6 5 0 13 9 13 9 11 9 10 2 0 0 3 9 3 9 3 0 2 6 0 0 15 6 15 6 11 9 10 2 2 5 4 0 4 0 3 0 2 6 2 5 16 0 16 0 11 9 10 2 6 0 4 1 4 0 3 0 2 6 6 0 16 4 16 0 11 9 10 2 7 5 4 2 4 0 3 0 2 6 7 5 16 9 16 0 11 9 10 2 10 0 4 4 4 0 3 0 2 6 10 0 17 7 16 0 11 9 10 2 12 5 4 6 4...

Page 179: ...20 0 9 9 9 6 9 7 9 4 15 0 2 7 2 7 2 6 2 5 15 0 10 9 10 6 10 4 10 1 10 0 3 0 2 9 2 8 2 8 10 0 12 0 11 7 11 4 11 1 5 0 3 3 3 3 3 2 2 8 5 0 13 3 13 2 12 7 11 3 0 0 3 7 3 7 3 2 2 8 0 0 14 8 14 8 12 7 11 3 2 5 3 9 3 9 3 2 2 8 2 5 15 5 15 5 12 7 11 3 6 0 4 1 4 0 3 2 2 8 6 0 16 3 16 0 12 7 11 3 7 5 4 2 4 0 3 2 2 8 7 5 16 8 16 0 12 7 11 3 10 0 4 4 4 0 3 2 2 8 10 0 17 6 16 0 12 7 11 3 12 5 4 6 4 0 3 2 2 8 ...

Page 180: ...16 0 20 0 11 1 11 0 10 9 10 7 15 0 3 0 3 0 2 9 2 8 15 0 12 1 12 0 11 6 11 1 10 0 3 3 3 3 3 2 2 8 10 0 13 3 13 2 12 8 11 2 5 0 3 8 3 7 3 2 2 8 5 0 15 1 14 9 12 8 11 2 0 0 4 0 4 0 3 2 2 8 0 0 16 2 16 0 12 8 11 2 2 5 4 0 4 0 3 2 2 8 2 5 16 2 16 0 12 8 11 2 6 0 4 0 4 0 3 2 2 8 6 0 16 2 16 0 12 8 11 2 7 5 4 1 4 0 3 2 2 8 7 5 16 6 16 0 12 8 11 2 10 0 4 4 4 0 3 2 2 8 10 0 17 4 16 0 12 8 11 2 12 5 4 6 4 0...

Page 181: ...20 0 10 3 10 3 10 3 9 9 15 0 2 8 2 8 2 8 2 6 15 0 11 1 11 2 11 1 10 2 10 0 3 1 3 1 3 0 2 6 10 0 12 3 12 3 11 9 10 2 5 0 3 5 3 5 3 0 2 6 5 0 13 9 13 9 11 9 10 2 0 0 3 9 3 9 3 0 2 6 0 0 15 6 15 6 11 9 10 2 2 5 4 0 4 0 3 0 2 6 2 5 16 0 16 0 11 9 10 2 6 0 4 1 4 0 3 0 2 6 6 0 16 4 16 0 11 9 10 2 7 5 4 2 4 0 3 0 2 6 7 5 16 9 16 0 11 9 10 2 10 0 4 4 4 0 3 0 2 6 10 0 17 7 16 0 11 9 10 2 12 5 4 6 4 0 3 0 2...

Page 182: ... 0 2 0 2 0 125 16 0 20 0 8 2 8 0 8 0 7 9 15 0 2 5 2 4 2 4 2 4 15 0 9 9 9 8 9 6 9 4 10 0 2 9 2 9 2 8 2 7 10 0 11 7 11 5 11 2 11 0 5 0 3 3 3 3 3 2 2 8 5 0 13 4 13 2 12 8 11 2 0 0 3 8 3 7 3 2 2 8 0 0 15 1 15 0 12 8 11 2 2 5 4 0 4 0 3 2 2 8 2 5 16 0 15 8 12 8 11 2 6 0 4 1 4 0 3 2 2 8 6 0 16 6 16 0 12 8 11 2 7 5 4 3 4 0 3 2 2 8 7 5 17 2 16 0 12 8 11 2 10 0 4 6 4 0 3 2 2 8 10 0 18 2 16 0 12 8 11 2 12 5 ...

Page 183: ...2 0 2 0 2 0 125 16 0 20 0 8 0 8 0 8 2 7 8 15 0 2 4 2 4 2 4 2 3 15 0 9 6 9 6 9 6 9 3 10 0 2 8 2 8 2 7 2 6 10 0 11 2 11 1 10 9 10 2 5 0 3 2 3 2 3 0 2 6 5 0 12 8 12 6 11 9 10 2 0 0 3 6 3 5 3 0 2 6 0 0 14 4 14 2 11 9 10 2 2 5 3 8 3 7 3 0 2 6 2 5 15 3 14 9 11 9 10 2 6 0 4 1 4 0 3 0 2 6 6 0 16 4 16 0 11 9 10 2 7 5 4 2 4 0 3 0 2 6 7 5 16 9 16 0 11 9 10 2 10 0 4 4 4 0 3 0 2 6 10 0 17 7 16 0 11 9 10 2 12 5...

Page 184: ...2 0 125 16 0 20 0 8 5 8 2 8 1 8 0 15 0 2 5 2 4 2 4 2 3 15 0 10 0 9 8 9 5 9 3 10 0 2 9 2 8 2 7 2 6 10 0 11 5 11 3 10 9 10 6 5 0 3 3 3 2 3 1 2 8 5 0 13 1 12 8 12 2 11 3 0 0 3 7 3 6 3 2 2 8 0 0 14 6 14 4 12 7 11 3 2 5 3 8 3 8 3 2 2 8 2 5 15 4 15 1 12 7 11 3 6 0 4 1 4 0 3 2 2 8 6 0 16 5 16 0 12 7 11 3 7 5 4 2 4 0 3 2 2 8 7 5 16 9 16 0 12 7 11 3 10 0 4 4 4 0 3 2 2 8 10 0 17 7 16 0 12 7 11 3 12 5 4 6 4 ...

Page 185: ...2 0 125 16 0 20 0 8 2 8 0 8 1 7 9 15 0 2 4 2 4 2 4 2 3 15 0 9 7 9 6 9 5 9 3 10 0 2 8 2 8 2 7 2 7 10 0 11 3 11 1 10 9 10 7 5 0 3 2 3 2 3 1 2 9 5 0 12 9 12 7 12 3 11 8 0 0 3 6 3 6 3 2 2 9 0 0 14 5 14 2 12 7 11 8 2 5 3 8 3 8 3 2 2 9 2 5 15 3 15 0 12 7 11 8 6 0 4 1 4 0 3 2 2 9 6 0 16 4 16 0 12 7 11 7 7 5 4 2 4 0 3 2 2 9 7 5 16 9 16 0 12 7 11 7 10 0 4 4 4 0 3 2 2 9 10 0 17 7 16 0 12 7 11 7 12 5 4 6 4 0...

Page 186: ... 2 0 125 16 0 20 0 8 5 8 2 8 1 8 0 15 0 2 5 2 4 2 4 2 3 15 0 10 0 9 8 9 5 9 3 10 0 2 9 2 8 2 7 2 6 10 0 11 5 11 3 10 9 10 6 5 0 3 3 3 2 3 1 2 8 5 0 13 1 12 8 12 2 11 3 0 0 3 7 3 6 3 2 2 8 0 0 14 6 14 4 12 7 11 3 2 5 3 8 3 8 3 2 2 8 2 5 15 4 15 1 12 7 11 3 6 0 4 1 4 0 3 2 2 8 6 0 16 5 16 0 12 7 11 3 7 5 4 2 4 0 3 2 2 8 7 5 16 9 16 0 12 7 11 3 10 0 4 4 4 0 3 2 2 8 10 0 17 7 16 0 12 7 11 3 12 5 4 6 4...

Page 187: ...6 7 5 16 6 6 6 17 7 5 7 104 40 14 2 9 3 15 2 8 5 16 3 7 6 17 3 6 7 18 7 5 3 PEFY P200VMH E F Outdoor 59 F W B 63 F W B 68 FW B 73 F W B 79 F W B 82 F W B 86 F W B 90 F W B 95 F W B air temp 15 C W B 17 C W B 20 C W B 23 C W B 26 C W B 28 C W B 30 C W B 32 C W B 35 C W B F D B C D B CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC 70 21 10 9 7 9 13 1 7 5 73 23 11 0 9 0 13 1 8 5 16 1 7...

Page 188: ...4 4 14 4 16 4 16 4 18 6 18 6 99 37 14 6 14 5 16 7 16 6 18 8 18 8 21 2 21 1 104 40 14 9 14 8 17 0 16 9 19 2 19 1 21 5 21 5 25 2 25 2 PEFY P200VMH E F Outdoor 59 F W B 63 F W B 68 FW B 73 F W B 79 F W B 82 F W B 86 F W B 90 F W B 95 F W B air temp 15 C W B 17 C W B 20 C W B 23 C W B 26 C W B 28 C W B 30 C W B 32 C W B 35 C W B F D B C D B C D B C W B C D B C W B C D B C W B C D B C W B C D B C W B C...

Page 189: ...W B F D B C D B SHC SHC SHC SHC SHC SHC SHC SHC SHC 18 8 14 6 27 3 16 2 32 0 15 1 37 3 14 0 14 0 45 7 12 6 12 6 12 6 52 11 11 2 11 2 59 15 9 8 9 8 64 18 8 8 8 8 68 20 8 1 PEFY P200VMH E F Outdoor 16 F W B 23 F W B 27 F W B 32 F W B 36 F W B 39 F W B 43 F W B 50 F W B 57 F W B air temp 9 C W B 5 C W B 2 9 C W B 0 C W B 2 C W B 4 C W B 6 C W B 10 C W B 14 C W B F D B C D B SHC SHC SHC SHC SHC SHC SH...

Page 190: ...D B C D B C D B C D B 18 8 34 7 27 3 45 8 32 0 45 6 37 3 45 4 45 4 45 7 45 2 45 2 45 2 52 11 45 0 45 0 59 15 44 7 45 1 64 18 44 6 44 6 68 20 44 4 PEFY P200VMH E F Outdoor 16 F W B 23 F W B 27 F W B 32 F W B 36 F W B 39 F W B 43 F W B 50 F W B 57 F W B air temp 9 C W B 5 C W B 2 9 C W B 0 C W B 2 C W B 4 C W B 6 C W B 10 C W B 14 C W B F D B C D B C D B C D B C D B C D B C D B C D B C D B C D B C D...

Page 191: ...188 INDOOR UNITS ...

Page 192: ...sion cable specifications 201 2 3 System configuration restrictions 206 2 4 Address setting 209 3 Piping Design 222 3 1 Piping Design 222 3 2 Refrigerant charging calculation 228 4 Outdoor Installation 229 4 1 Requirement on installation site 229 4 2 Spacing 230 4 3 Piping direction 232 4 4 Weather countermeasure 237 4 5 Caution on selecting outdoor units 238 5 Caution for refrigerant leakage 239 ...

Page 193: ...Be sure to provide designated grounding work to outdoor unit Give some allowance to wiring for electrical part box of indoor and outdoor units because the box is sometimes removed at the time of service work Never connect 380 415V 220 240V power source to terminal block of transmission cable If connected electrical parts will be burnt out Use 2 core shield cable for transmission cable If transmiss...

Page 194: ...34 0 120 1 07 PLFY P VLMD E Power supply IFM Volts Hz Range 10 MCA A 50 60Hz Output kW FLA A 50 60Hz PLFY P20VLMD E 220 240V 50Hz 220 230V 60Hz Max 264V Min 198V 0 45 0 46 0 015 0 36 0 37 PLFY P25VLMD E 0 45 0 46 0 015 0 36 0 37 PLFY P32VLMD E 0 45 0 46 0 015 0 36 0 37 PLFY P40VLMD E 0 50 0 53 0 015 0 40 0 42 PLFY P50VLMD E 0 51 0 54 0 020 0 41 0 43 PLFY P63VLMD E 0 61 0 64 0 020 0 49 0 51 PLFY P8...

Page 195: ...1 86 PEFY P250VMH E 2 50 2 88 1 08 2 00 2 30 PEFY P VMA E Power supply IFM Volts Hz Range 10 MCA A Output kW FLA A PEFY P20VMA E 220 240V 50Hz 220 240V 60Hz Max 264V Min 198V 1 03 0 085 0 82 PEFY P25VMA E 1 03 0 085 0 82 PEFY P32VMA E 1 18 0 085 0 95 PEFY P40VMA E 1 43 0 085 1 14 PEFY P50VMA E 1 54 0 085 1 23 PEFY P63VMA E 2 22 0 121 1 78 PEFY P71VMA E 2 46 0 121 1 97 PEFY P80VMA E 2 47 0 121 1 98...

Page 196: ...0 056 0 29 PKFY P100VKM E 0 63 0 056 0 50 PCFY P VKM E Power supply IFM Volts Hz Range 10 MCA A Output kW FLA A PCFY P40VKM E 220 240V 50Hz 220V 60Hz Max 264V Min 198V 0 35 0 090 0 28 PCFY P63VKM E 0 41 0 095 0 33 PCFY P100VKM E 0 81 0 160 0 65 PCFY P125VKM E 0 95 0 160 0 76 PFFY P VKM E Power supply IFM Volts Hz Range 10 MCA A Output kW FLA A PFFY P20VKM E 220 240V 50Hz Max 264V Min 198V 0 25 0 0...

Page 197: ...VLRM E 0 50 0 51 0 035 0 40 0 41 PFFY P63VLRM E 0 58 0 59 0 050 0 46 0 47 PFFY P VLRMM E Power supply IFM Volts Hz Range 10 MCA A 50 60Hz Output kW FLA A 50 60Hz PFFY P20VLRMM E 220 240V 50Hz Max 264V Min 198V 0 59 0 58 0 096 0 47 0 46 PFFY P25VLRMM E 0 59 0 58 0 096 0 47 0 46 PFFY P32VLRMM E 0 69 0 69 0 096 0 55 0 55 PFFY P40VLRMM E 0 78 0 76 0 096 0 62 0 61 PFFY P50VLRMM E 0 80 0 79 0 096 0 64 0...

Page 198: ...6 8 0 92 PUHY RP550YSJM B BS PUHY RP250YJM B BS 42 1 6 8 0 92 29 5 28 0 27 0 28 0 26 6 25 6 PUHY RP300YJM B BS 8 2 0 92 PUHY RP600YSJM B BS PUHY RP300YJM B BS 44 7 8 2 0 92 31 3 29 8 28 7 32 4 30 8 29 7 PUHY RP300YJM B BS 8 2 0 92 PUHY RP650YSJM B BS PUHY RP300YJM B BS 50 9 8 2 0 92 35 6 33 8 32 6 36 6 34 8 33 5 PUHY RP350YJM B BS 9 9 0 92 PUHY RP700YSJM B BS PUHY RP200YJM B BS 53 6 4 8 0 92 37 5 ...

Page 199: ...diameter Make sure the power supply voltage does not drop more than 10 4 Specific wiring requirements should adhere to the wiring regulations of the region 5 Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord design 245 IEC57 For example use wiring such as YZW 6 A switch with at least 3 mm contact separation in each pole shall...

Page 200: ...n cable above 1 25mm2 shielded CVVS CPEVS MVVS among Outdoor units and system controllers is called centralized control transmission cable The shield wire of the centralized control transmission cable must be grounded at the Outdoor unit whose CN41 is changed to CN40 5 MA R C transmission cable 0 3 1 25mm2 must be less than 200m in length while ME R C transmission cable 0 3 1 25mm2 must be less th...

Page 201: ... control more than 1 indoor unit set address to Indoor unit and ME remote controller For the method refer to 2 4 Address Setting 8 Indoor board consumes power from TB3 The power balance should be considered according to System Design 2 3 System configuration restrictions 9 If Transmission booster is needed be sure to connect the shield wires to the both sides to the booster 10 The critical current...

Page 202: ...umes power from TB3 The power balance should be considered according to System Design 2 3 System configuration restrictions 9 If Transmission booster is needed be sure to connect the shield wires to the both sides to the booster 10 The critical current for choosing power source equipment is approximate 1 4 times of total rated current of the Outdoor unit s or Indoor unit s 11 Numbers shown with in...

Page 203: ...4VDC to AG 150A n 50m 164ft 0 75 2 0 mm2 AWG18 14 1 If the length from ME to Indoor exceed 10m use 1 25 mm2 AWG16 shielded cable but the total length should be counted into Max length via Outdoor OC OS1 OS2 Outdoor unit controller IC Indoor unit controller MA MA remote controller OC OS1 OS2 Outdoor unit controller IC Indoor unit controller ME ME remote controller M2 TB7 TB3 IC 52 M1M2 1 2 S TB5 TB...

Page 204: ... system controller after the completion of the refrigerant oil recovery operation Type of cable Cable size Remarks Sheathed 2 core cable unshielded CVV 2 Shielding wire 2 core CVVS CPEVS or MVVS Transmission cables ME Remote controller cables CVVS MVVS PVC insulated PVC jacketed shielded control cable CPEVS Connected with simple remote controller PE insulated PVC jacketed shielded communication ca...

Page 205: ...transmission lines reusability checklist Obtain the system configuration drawing fill out the checklist and make a decision based on them Use the flowcharts on the following pages to determine the reusability of the existing transmission lines 1 If the remote controller ME System controller length exceeds 10 m include the exceeded length in the calculation of the transmission line length indoor ou...

Page 206: ...Wiring for MA remote controller must be under 200m Checking the transmission cable Checking the transmission cable Checking the transmission cable Side Close to power supply unit Outdoor unit Power supply unit Non using wiring on the power supply side Outdoor unit Power supply unit should be connected to the shield terminal The non using wiring on the opposite side should be open and insulated Go ...

Page 207: ...5mm2 Change the centralized transmission line diameter to more than 1 25mm2 Length between power supply unit to outdoor unit and system controller Shielded wiring should be connected to the terminal at the power supply unit side outdoor unit Is the diameter of the current wiring thicker than the diameter read from chart A Is the system single refrigerant system Existing transmission line can be re...

Page 208: ...its Length of transmission line to the farthest unit m 0 75mm2 0 5mm2 MA remote controller Diagram B Checking the cable size 0 3mm2 1 25mm2 ME remote controller Number of indoor units Length of transmission line to the farthest unit m 0 5mm2 0 75mm2 0 3mm2 1 25mm2 0 50 100 150 200 0 5 10 15 20 ...

Page 209: ...nit Indoor unit LOSSNAY and OA processing unit GUF RD H and Controllers the transmission power situation for the M NET should be observed In some cases Transmission booster should be used Taking the power consumption of Indoor unit sized P20 P140 as 1 the equivalent power consumption or supply of others are listed at Table 2 3 1 and Table 2 3 2 RC Remote Controller If PAC SC51KUA is used to supply...

Page 210: ...KUA Maximum 3 System controllers can be connected to TB3 If there is more than 1 Outdoor unit it is necessary to replace power supply switch connector CN41 with CN40 on one Outdoor unit Maximum 3 System controllers can be connected to TB7 and receiving power from the Outdoor unit It is necessary to replace power supply switch connector CN41 with CN40 on one Outdoor unit Fig 2 3 3 A Fig 2 3 3 B Fig...

Page 211: ...y The expansion controller supplies power through TB3 which equals 6 indoor units refer to Table 2 3 2 2 3 5 Power supply to expansion controller 1 phase 100 240VAC power supply is needed The power supply unit PAC SC51KUA is not necessary when only BM ADAPTER is connected Yet make sure to move the power jumper from CN41 to CN40 on the BM ADAPTER 2 3 6 Power supply to BM ADAPTER 1 phase 100 240VAC ...

Page 212: ... as the main remote controller and the other as the sub remote controller No units with identical unit address shall exist in one whole air conditioner system If set erroneously the system can not operate The factory setting is Main 2 4 1 Switch operation 012 3 4 5 6 7 8 9 A B C D E F 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 PAR 21MAA The MA remote controller does not have the switches listed above...

Page 213: ... indoor unit in same refrigerant system 50 Assign sequential address numbers to the outdoor units in one refrigerant circuit system OC OS1 and OS2 are automatically detected Note 2 Please reset one of them to an address between 51 and 99 when two addresses overlap The address automatically becomes 100 if it is set as 01 50 Use the most recent address within the same group of indoor units Make the ...

Page 214: ... system having more than 1 outdoor unit because the central transmission power supply from TB7 of one of outdoor units is risking that the outdoor unit failure may let down the whole system controller system 2 4 3 1 MA remote controller Single refrigerant system No System Controller 1 Outdoor units OC OS1 and OS2 in one refrigerant circuit system are automatically detected OC OS1 and OS2 are ranke...

Page 215: ...order of their address Indoor unit MA R C MA R C MA R C Main Sub MA R C SRU Wireless R C 1 1 For Wireless R C and Signal receiver unit SRU channel 1 2 and 3 are selectable and should be set to same channel SC can be connected to TB3 side or TB7 side Should SC connected to TB7 side change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC 1 01 02 03 04 05 TB15 TB5 T...

Page 216: ...frigerant System For AG 150A 24V DC should be used with the PAC SC51KUA 1 202 01 02 03 30 TB15 TB5 TB5 TB5 TB2 Transmission Booster PAC SF46EPA TB5 TB15 TB15 TB3 TB15 MA R C Main Sub MA R C TB15 Indoor unit ME R C MA R C PZ 52SF E SRU Wireless R C 1 1 142 143 2 41 42 43 45 46 TB15 TB5 TB5 LOSSNAY TB5 TB5 TB5 TB15 1 For Wireless R C and Signal receiver unit SRU channel 1 2 and 3 are selectable and ...

Page 217: ... 1 PUHY Three outdoor units Two outdoor units One outdoor unit 2 4 3 5 ME remote controller Single refrigerant system System controller LOSSNAY 2 Address should be set to Indoor units LOSSNAY centralized controller ME remote controllers 3 For a system having more than 32 indoor unit P15 P140 confirm the need of Booster at 2 3 System configuration restrictions NOTE ME R C ME R C Indoor unit ME R C ...

Page 218: ...er in Multi Refrigerant System For AG 150A 24V DC should be used with the PAC SC51KUA 01 02 03 30 TB5 TB5 TB5 TB2 Transmission Booster PAC SF46EPA TB5 TB3 ME R C ME R C Indoor unit ME R C ME R C PZ 52SF E 142 144 145 195 130 180 143 1 41 42 43 44 45 TB5 TB5 LOSSNAY TB5 TB5 TB5 TM4 ME R C 141 203 ME R C 101 SC 2 SC 2 202 ME R C 102 Group 2 Group 1 Group 21 Group 32 Group 33 PZ 60 DR E 46 LOSSNAY Gr...

Page 219: ... set between other refrigerant systems It is necessary to set on the remote controller by manual when group sets on the different refrigerant system Please refer to remote controller installation manual SC 201 Group 1 Group 3 Group 4 Group 2 ME R C 01 02 03 04 05 101 105 09 10 08 07 06 110 107 ME R C ME R C ME R C TB7 TB3 56 CN41 CN40 OFF DipSW2 1 TB3 TB7 TB7 TB3 52 51 CN41 CN40 CN41 CN40 OFF DipS...

Page 220: ...N41 CN40 CN41 CN40 ON DipSW2 1 ON DipSW2 1 ON DipSW2 1 ME R C ME R C Indoor unit ME R C ME R C 142 144 145 195 41 42 43 44 45 TB5 TB5 Interlocked LOSSNAY TB5 TB5 TB5 Group 32 46 TB5 TM4 LOSSNAY Group 35 Group 31 Group 33 Group 34 ME R C 141 PUHY PUHY PUHY 1 TG 2000A Ver 5 5 or later supports AG 150A Ver 1 series TG 2000A Ver 6 1 or later supports AG 150A Ver 2 1 or later connected with the expansi...

Page 221: ...02 03 30 TB5 TB5 TB5 TB2 Transmission Booster PAC SF46EPA TB5 ME R C 101 102 130 180 TB3 Group 2 Group 1 Group 21 TB3 TB3 TB7 TB7 TB7 TB7 TB7 TB7 TB3 53 52 51 OC OS1 OS2 TB3 TB3 92 91 OC OS1 TB3 96 OC CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 ON DipSW2 1 ON DipSW2 1 ON DipSW2 1 ON DipSW2 1 ON DipSW2 1 ON DipSW2 1 ME R C ME R C Indoor unit ME R C ME R C PZ 52SF E 142 143 144 145 1...

Page 222: ...42 TB15 TB5 TB5 TB5 TB2 Transmission Booster PAC SF46EPA TB5 TB15 TB15 TB3 TB15 Group 2 Group 1 Group 40 TB3 TB3 TB7 TB7 TB3 TB2 TB7 TB7 TB7 TB7 TB3 53 52 51 OC OS1 OS2 TB3 TB3 52 51 OC OS1 TB3 51 OC CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 OFF DipSW2 1 OFF DipSW2 1 OFF DipSW2 1 OFF DipSW2 1 OFF DipSW2 1 OFF DipSW2 1 Indoor unit ME R C ME R C ME R C 01 02 03 30 TB5 TB5 TB5 TB2 T...

Page 223: ...B3 TB3 TB7 TB7 TB7 TB7 TB7 TB7 TB3 53 52 51 OC OS1 OS2 TB3 TB3 52 51 OC OS1 TB3 51 OC CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 OFF DipSW2 1 OFF DipSW2 1 OFF DipSW2 1 OFF DipSW2 1 OFF DipSW2 1 OFF DipSW2 1 Indoor unit ME R C ME R C ME R C 01 02 03 30 TB5 TB5 TB5 TB2 Transmission Booster PAC SF46EPA TB5 ME R C 101 102 130 180 TB3 Group 2 Group 1 Group 21 TB3 TB3 TB7 TB7 TB7 TB7 TB...

Page 224: ...Group 21 TB3 TB3 TB7 TB7 TB7 TB7 TB7 TB7 TB3 53 52 51 OC OS1 OS2 TB3 TB3 92 91 OC OS1 TB3 96 OC CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 CN41 CN40 ON DipSW2 1 ON DipSW2 1 ON DipSW2 1 ON DipSW2 1 ON DipSW2 1 ON DipSW2 1 ME R C ME R C Indoor unit ME R C ME R C PZ 52SF E 142 143 144 145 195 41 42 43 44 45 TB5 TB5 LOSSNAY TB5 TB5 TB5 Group 32 Group 33 Group 31 Group 34 Group 35 ME R C 141 PUH...

Page 225: ...Table 3 1 1 3 Piping A size selection rule mm Outdoor Pipe Liquid Pipe Gas PUHY RP200YJM B ø12 7 ø28 58 PUHY RP250YJM B ø12 7 ø28 58 PUHY RP300YJM B ø12 7 ø28 58 PUHY RP350YJM B ø15 88 ø34 93 Table 3 1 1 4 R410A piping B C D E size selection rule mm in Total down stream Indoor capacity Pipe Liquid Pipe Gas P80 ø9 52 3 8 ø15 88 5 8 P81 P160 ø12 7 1 2 ø19 05 3 4 P161 P330 ø12 7 1 2 ø25 4 1 P331 P630...

Page 226: ... 93 PUHY RP550YSJM B ø15 88 ø34 93 Table 3 1 2 4 Piping B C D E size selection rule mm in Total down stream Indoor capacity Pipe Liquid Pipe Gas P80 ø9 52 3 8 ø15 88 5 8 P81 P160 ø12 7 1 2 ø19 05 3 4 P161 P330 ø12 7 1 2 ø25 4 1 P331 P630 ø15 88 5 8 ø34 93 1 3 8 P631 ø19 05 3 4 ø41 28 1 5 8 Table 3 1 2 5 Piping a b c d e f g size selection rule mm in Indoor Unit size Pipe Liquid Pipe Gas P20 P25 P3...

Page 227: ...RP650YSJM B ø19 05 ø41 28 Table 3 1 3 4 Piping B C D E size selection rule mm in Total down stream Indoor capacity Pipe Liquid Pipe Gas P80 ø9 52 3 8 ø15 88 5 8 P81 P160 ø12 7 1 2 ø19 05 3 4 P161 P330 ø12 7 1 2 ø25 4 1 P331 P630 ø15 88 5 8 ø34 93 1 3 8 P631 ø19 05 3 4 ø41 28 1 5 8 Table 3 1 3 5 Piping a b c d e f g size selection rule mm in Indoor Unit size Pipe Liquid Pipe Gas P20 P25 P32 P40 ø6 ...

Page 228: ... size M N S T please refer to specification of the Twining kit CMY RP200VBK at the Outdoor unit s external drawing Table 3 1 4 4 Piping B C D E size selection rule mm in Total down stream Indoor capacity Pipe Liquid Pipe Gas P80 ø9 52 3 8 ø15 88 5 8 P81 P160 ø12 7 1 2 ø19 05 3 4 P161 P330 ø12 7 1 2 ø25 4 1 P331 P630 ø15 88 5 8 ø34 93 1 3 8 P631 ø19 05 3 4 ø41 28 1 5 8 Table 3 1 4 5 Piping a b c d ...

Page 229: ... 18 PUHY RP300 900YJM B 0 39 ޓ L0 0 29 ޓ L1 0 2 ޓ L2 0 12 ޓ L3 0 06 ޓ L4 25 L1 Total length of ø19 05 liquid pipe m L0 Total length of ø22 2 liquid pipe m L2 Total length of ø15 88 liquid pipe m L3 Total length of ø12 7 liquid pipe m L4 Total length of ø9 52 liquid pipe m L5 Total length of ø6 35 liquid pipe m 0 5 6 0 0 6 0 5 5 0 0 5 0 5 4 0 0 4 0 5 3 0 0 3 0 5 2 0 0 2 l e d o m r o o d t u O 0 0 ...

Page 230: ...h pipe completely that are not in use and seal it Is the piping air tight Start YES YES YES NO NO NO NO YES YES YES NO NO Please contact your local distributor Are the existing pipes still connected with indoor units and the outdoor units excluding sealed branch pipes that are not in use Exisiting piping cannot be reused Use new piping If the piping is left disconnected there is a possibility of c...

Page 231: ...15 88 G ø15 88 I ø12 7 J ø15 88 K ø12 7 M ø12 7 a ø12 7 b ø12 7 c ø9 52 d ø9 52 e ø9 52 f ø9 52 g ø9 52 i ø6 35 3 m 2 m 2 m 1 m 10 m 10 m 5 m 5 m 20 m 5 m 5 m 15 m 15 m 5 m 5 m 5 m 5 m 5 m 5 m 2 0 kg 2 5 kg 3 0 kg 3 5 kg 4 5 kg 5 0 kg 6 0 kg 8 0 kg 9 0 kg 10 0 kg 12 0 kg Total length of ø12 7 liquid pipe x 0 12 m x 0 12 kg m Total length for each pipe size This yields the following result Total le...

Page 232: ...the outdoor unit may generate noise 3 Avoid the sites where strong winds blow 4 With strength to bear the weight of the unit 5 Drain flow from the unit is cared at heating mode 6 Enough space for installation and service as shown at 4 2 7 Avoid the sites where acidic solutions or chemical sprays sulfur series are used frequently 8 The unit should be secure from combustible gas oil steam chemical g...

Page 233: ...xceeds the wall height restriction 4 If there are obstacles at the upper part of the unit A Top view B Side view C When there is little space up to an obstruction When the height of the walls on the front back or on the sides H exceeds the wall height limit as defined below add the height that exceeds the height limit h to the figures that are marked with an asterisk Wall height limit Front Up to ...

Page 234: ...o sides must be left open As with the single installation add the height that exceeds the height limit h to the figures that are marked with If there is a wall at both the front and the rear of the unit install up to six units consecutively in the side direction and provide a space of 1000mm or more as inlet space passage space for each six units an asterisk Front Must be open 17 23 32 17 23 32 17...

Page 235: ...wo corners and must not be attempt ed Use protective pads to keep the ropes from scratching the panels on the unit Products weighing more than 20 kg 45 LBS should not be carried alone Do not carry the product by the PP bands To avoid the risk of injury do not touch the heat exchanger fins Plastic bags may pose a risk of choking hazard to children Tear plastic bags into pieces before disposing of t...

Page 236: ...dth of the unit leg Install the unit in such a way that the corner of the angle bracket at the base of the unit shown in the figure below is securely supported Install the anchor bolt in such a way that the top end of the anchor bolt do not stick out more than 30 mm 1 3 16 in This unit is not designed to be anchored with post installation type anchor bolts although by adding fixing brackets anchor...

Page 237: ... 32 92 3 5 8 145 5 23 32 A Mounting pitch Mounting pitch 2X2 14X20 Oval hole Refrigerant service valve gas Refrigerant service valve liquid 760 29 15 16 80 760 29 15 16 80 18 18 131 83 251 186 Bottom view 724 721 727 5 3 16 23 32 23 32 28 13 32 28 5 8 3 5 32 3 5 32 7 11 32 9 29 32 3 9 32 8 23 32 5 29 32 The gaps around the edges of through holes for pipes and wires on the unit allow water or mice ...

Page 238: ...f the twinning pipe can be 500 mm 19 in or longer If the length is less than 500 mm 19 in it will cause damage to the unit To Indoor unit Less than 2 m 6 ft To Indoor unit 2m To Indoor unit 200 mm 7 in or over Trap gaspipeonly The piping connection When connecting the twinning kit to the outdoor unit note the following If the length of piping from the twinning kit to the outdoor unit is more than ...

Page 239: ...winning kit The length of the straight pipe must be 500 mm 19 in or longer The length of the straight pipe must be 500 mm 19 in or longer See the following drawing for connecting the pipes between the outdoor units PUHY RP500YSJM B PUHY RP900YSJM B 4 3 7 Twinning on the outdoor unit side The length of the straight pipe must be 500mm 19 in or longer If not it may cause improper operation CAUTION ...

Page 240: ...rame base at customer referring to this figure Material Galvanized steel plate 1 2T 1 16 in T Painting Overall painting with polyester powder Color Munsell 5Y8 1 same as that of unit 4 When the unit is used in a cold region and the heating operation is continuously performed for a long time when the outside air temperature is below freezing install a heater to the unit base or take other appropria...

Page 241: ...ey concern Warm air may flow out from the indoor unit during heating Thermo OFF Refrigerant flow sound may occur in the rooms with low background noise such as hotel rooms hospital rooms bedrooms or conference rooms To avoid the above issues on Y system changing board settings on the indoor and outdoor units is required Ask AC R Works for details ...

Page 242: ...r refrigerant leakage Oxygen sensor or refrigerant sensor At 0 3m height from the floor Fresh air supply fan Indoor space Floor Fig 5 4 Fresh air supply and refrigerant shut off upon sensor action Note 1 Countermeasure 3 should be done in a proper way in which the fresh air supply shall be on whenever the leakage happens Note 2 In principle MITSUBISHI ELECTRIC requires proper piping design install...

Page 243: ...240 SYSTEM DESIGN ...

Page 244: ...ation 249 2 2 Transmission cable specifications 250 2 3 System configuration restrictions 255 2 4 Address setting 258 3 Piping Design 271 3 1 Piping Design 271 3 2 Refrigerant charging calculation 275 4 Outdoor Installation 276 4 1 Requirement on installation site 276 4 2 Spacing 277 4 3 Piping direction 279 4 4 Weather countermeasure 282 5 Caution for refrigerant leakage 283 5 1 Refrigerant prope...

Page 245: ...Be sure to provide designated grounding work to outdoor unit Give some allowance to wiring for electrical part box of indoor and outdoor units because the box is sometimes removed at the time of service work Never connect 380 415V 220 240V power source to terminal block of transmission cable If connected electrical parts will be burnt out Use 2 core shield cable for transmission cable If transmiss...

Page 246: ...34 0 120 1 07 PLFY P VLMD E Power supply IFM Volts Hz Range 10 MCA A 50 60Hz Output kW FLA A 50 60Hz PLFY P20VLMD E 220 240V 50Hz 220 230V 60Hz Max 264V Min 198V 0 45 0 46 0 015 0 36 0 37 PLFY P25VLMD E 0 45 0 46 0 015 0 36 0 37 PLFY P32VLMD E 0 45 0 46 0 015 0 36 0 37 PLFY P40VLMD E 0 50 0 53 0 015 0 40 0 42 PLFY P50VLMD E 0 51 0 54 0 020 0 41 0 43 PLFY P63VLMD E 0 61 0 64 0 020 0 49 0 51 PLFY P8...

Page 247: ...1 86 PEFY P250VMH E 2 50 2 88 1 08 2 00 2 30 PEFY P VMA E Power supply IFM Volts Hz Range 10 MCA A Output kW FLA A PEFY P20VMA E 220 240V 50Hz 220 240V 60Hz Max 264V Min 198V 1 03 0 085 0 82 PEFY P25VMA E 1 03 0 085 0 82 PEFY P32VMA E 1 18 0 085 0 95 PEFY P40VMA E 1 43 0 085 1 14 PEFY P50VMA E 1 54 0 085 1 23 PEFY P63VMA E 2 22 0 121 1 78 PEFY P71VMA E 2 46 0 121 1 97 PEFY P80VMA E 2 47 0 121 1 98...

Page 248: ...0 056 0 29 PKFY P100VKM E 0 63 0 056 0 50 PCFY P VKM E Power supply IFM Volts Hz Range 10 MCA A Output kW FLA A PCFY P40VKM E 220 240V 50Hz 220V 60Hz Max 264V Min 198V 0 35 0 090 0 28 PCFY P63VKM E 0 41 0 095 0 33 PCFY P100VKM E 0 81 0 160 0 65 PCFY P125VKM E 0 95 0 160 0 76 PFFY P VKM E Power supply IFM Volts Hz Range 10 MCA A Output kW FLA A PFFY P20VKM E 220 240V 50Hz Max 264V Min 198V 0 25 0 0...

Page 249: ...VLRM E 0 50 0 51 0 035 0 40 0 41 PFFY P63VLRM E 0 58 0 59 0 050 0 46 0 47 PFFY P VLRMM E Power supply IFM Volts Hz Range 10 MCA A 50 60Hz Output kW FLA A 50 60Hz PFFY P20VLRMM E 220 240V 50Hz Max 264V Min 198V 0 59 0 58 0 096 0 47 0 46 PFFY P25VLRMM E 0 59 0 58 0 096 0 47 0 46 PFFY P32VLRMM E 0 69 0 69 0 096 0 55 0 55 PFFY P40VLRMM E 0 78 0 76 0 096 0 62 0 61 PFFY P50VLRMM E 0 80 0 79 0 096 0 64 0...

Page 250: ...unlight rain water etc when proceeding with the wiring and connections 3 The wire size is the minimum value for metal conduit wiring If the voltage drops use a wire that is one rank thicker in diameter Make sure the power supply voltage does not drop more than 10 4 Specific wiring requirements should adhere to the wiring regulations of the region 5 Power supply cords of parts of appliances for out...

Page 251: ...ble above 1 25mm2 shielded CVVS CPEVS MVVS among Outdoor units and system controllers is called centralized control transmission cable The shield wire of the centralized control transmission cable must be grounded at the Outdoor unit whose CN41 is changed to CN40 5 MA R C transmission cable 0 3 1 25mm2 must be less than 200m in length while ME R C transmission cable 0 3 1 25mm2 must be less than 1...

Page 252: ... length from ME to Indoor exceed 10m use 1 25 mm2 AWG16 shielded cable but the total length should be counted into Max length via Outdoor OC Outdoor unit controller IC Indoor unit controller MA MA remote controller OC Outdoor unit controller IC Indoor unit controller ME ME remote controller IC M1M2 1 2 S TB5 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB15 1 2 TB 15 1 2 TB15 MA 01 IC M1M2S TB5 02 IC M1M2S...

Page 253: ... system controller after the completion of the refrigerant oil recovery operation Type of cable Cable size Remarks Sheathed 2 core cable unshielded CVV 2 Shielding wire 2 core CVVS CPEVS or MVVS Transmission cables ME Remote controller cables CVVS MVVS PVC insulated PVC jacketed shielded control cable CPEVS Connected with simple remote controller PE insulated PVC jacketed shielded communication ca...

Page 254: ...transmission lines reusability checklist Obtain the system configuration drawing fill out the checklist and make a decision based on them Use the flowcharts on the following pages to determine the reusability of the existing transmission lines 1 If the remote controller ME System controller length exceeds 10 m include the exceeded length in the calculation of the transmission line length indoor ou...

Page 255: ...Wiring for MA remote controller must be under 200m Checking the transmission cable Checking the transmission cable Checking the transmission cable Side Close to power supply unit Outdoor unit Power supply unit Non using wiring on the power supply side Outdoor unit Power supply unit should be connected to the shield terminal The non using wiring on the opposite side should be open and insulated Go ...

Page 256: ...5mm2 Change the centralized transmission line diameter to more than 1 25mm2 Length between power supply unit to outdoor unit and system controller Shielded wiring should be connected to the terminal at the power supply unit side outdoor unit Is the diameter of the current wiring thicker than the diameter read from chart A Is the system single refrigerant system Existing transmission line can be re...

Page 257: ...its Length of transmission line to the farthest unit m 0 75mm2 0 5mm2 MA remote controller Diagram B Checking the cable size 0 3mm2 1 25mm2 ME remote controller Number of indoor units Length of transmission line to the farthest unit m 0 5mm2 0 75mm2 0 3mm2 1 25mm2 0 50 100 150 200 0 5 10 15 20 ...

Page 258: ...nit Indoor unit LOSSNAY and OA processing unit GUF RD H and Controllers the transmission power situation for the M NET should be observed In some cases Transmission booster should be used Taking the power consumption of Indoor unit sized P20 P140 as 1 the equivalent power consumption or supply of others are listed at Table 2 3 1 and Table 2 3 2 RC Remote Controller If PAC SC51KUA is used to supply...

Page 259: ...KUA Maximum 3 System controllers can be connected to TB3 If there is more than 1 Outdoor unit it is necessary to replace power supply switch connector CN41 with CN40 on one Outdoor unit Maximum 3 System controllers can be connected to TB7 and receiving power from the Outdoor unit It is necessary to replace power supply switch connector CN41 with CN40 on one Outdoor unit Fig 2 3 3 A Fig 2 3 3 B Fig...

Page 260: ...y The expansion controller supplies power through TB3 which equals 6 indoor units refer to Table 2 3 2 2 3 5 Power supply to expansion controller 1 phase 100 240VAC power supply is needed The power supply unit PAC SC51KUA is not necessary when only BM ADAPTER is connected Yet make sure to move the power jumper from CN41 to CN40 on the BM ADAPTER 2 3 6 Power supply to BM ADAPTER 1 phase 100 240VAC ...

Page 261: ... as the main remote controller and the other as the sub remote controller No units with identical unit address shall exist in one whole air conditioner system If set erroneously the system can not operate The factory setting is Main 2 4 1 Switch operation 012 3 4 5 6 7 8 9 A B C D E F 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 PAR 21MAA The MA remote controller does not have the switches listed above...

Page 262: ... indoor unit in same refrigerant system 50 Assign sequential address numbers to the outdoor units in one refrigerant circuit system OC OS1 and OS2 are automatically detected Note 2 Please reset one of them to an address between 51 and 99 when two addresses overlap The address automatically becomes 100 if it is set as 01 50 Use the most recent address within the same group of indoor units Make the ...

Page 263: ...ut using a power supply unit Change jumper from CN41 to CN 40 at LMAP will activate transmission power supply to LMAP itself Power supply unit is recommended to use for a system having more than 1 outdoor unit because the central transmission power supply from TB7 of one of outdoor units is risking that the outdoor unit failure may let down the whole system controller system 2 4 3 1 MA remote cont...

Page 264: ...A R C Main Sub MA R C SRU Wireless R C 1 1 For Wireless R C and Signal receiver unit SRU channel 1 2 and 3 are selectable and should be set to same channel SC can be connected to TB3 side or TB7 side Should SC connected to TB7 side change Jumper from CN41 to CN40 at the Outdoor unit module so as to supply power to the SC 1 201 SC 01 02 03 04 05 TB15 TB5 TB5 TB5 TB5 TB5 TB15 TB15 TB15 TB15 TB02 52 ...

Page 265: ...as sub Make the setting to only one of the system controllers for prohibition of operation from local remote controller 1 01 BC controller 52 BC controller Main 92 02 03 30 TB15 TB5 TB02 TB5 TB5 TB2 Transmission Booster PAC SF46EPA TB5 TB15 TB15 TB3 TB15 MA R C Main Sub MA R C TB15 Indoor unit ME R C MA R C PZ 52SF E SRU Wireless R C 1 1 142 143 2 SC 3 SC 3 41 42 43 95 45 46 TB15 TB5 TB02 TB5 LOSS...

Page 266: ...3 Indoor units should be set with a branch number 2 4 3 5 ME remote controller Single refrigerant system System controller LOSSNAY 1 Address should be set to Indoor units LOSSNAY centralized controller ME remote controllers 2 For a system having more than 32 indoor unit P15 P140 confirm the need of Booster at 2 3 System configuration restrictions NOTE ME R C ME R C Indoor unit ME R C ME R C PZ 52S...

Page 267: ... BC controller TB02 TB5 TB5 TB2 Transmission Booster PAC SF46EPA TB5 TB3 ME R C ME R C PZ 60 DR E Indoor unit ME R C ME R C PZ 52SF E 142 144 145 195 130 180 143 1 41 92 42 43 44 45 TB5 TB5 LOSSNAY TB5 TB5 TB5 ME R C 141 ME R C 101 ME R C 102 Group 2 Group 1 Group 21 Group 32 Group 33 Group 31 Group 34 Group 35 TB7 TB7 TB7 TB3 TB2 000 or 201 Power supply unit PAC SC51KUA 51 OC PURY SC TB3 91 OC PU...

Page 268: ...ntroller 57 TB02 TB7 TB3 56 CN41 CN40 OFF DipSW2 1 TB7 TB3 51 CN41 CN40 OFF DipSW2 1 OC OC PURY PURY NOTE It is necessary to change the connecter to CN40 on the outdoor unit control board only one outdoor unit when the group is set between other refrigerant systems It is necessary to set on the remote controller by manual when group sets on the different refrigerant system Please refer to remote c...

Page 269: ...ter PAC SF46EPA TB5 ME R C 101 102 130 180 TB3 Group 2 Group 1 Group 21 TB7 TB7 TB3 51 OC TB3 91 OC CN41 CN40 CN41 CN40 ON DipSW2 1 ON DipSW2 1 ME R C ME R C Indoor unit ME R C ME R C 142 144 145 195 41 42 43 44 45 TB5 TB5 Interlocked LOSSNAY TB5 TB5 TB5 Group 32 Group 31 Group 33 Group 34 ME R C 141 PURY PURY PURY PURY It is planned that GB 50ADA will be supported on TG 2000A Ver 6 3 or later 1 T...

Page 270: ...oup 40 TB7 TB7 TB3 51 OC TB3 51 OC CN41 CN40 CN41 CN40 ON DipSW2 1 ON DipSW2 1 Indoor unit ME R C ME R C ME R C 01 02 03 30 TB5 TB5 TB5 TB2 Transmission Booster PAC SF46EPA TB5 ME R C 101 102 130 180 TB3 Group 2 Group 1 Group 21 TB7 TB7 TB3 51 OC TB3 91 OC CN41 CN40 CN41 CN40 ON DipSW2 1 ON DipSW2 1 ME R C ME R C Indoor unit ME R C ME R C 142 144 145 195 41 42 43 44 45 TB5 TB5 Interlocked LOSSNAY ...

Page 271: ... SRU Wireless R C 1 1 01 02 03 42 TB15 TB5 BC controller 52 TB02 TB5 TB5 TB2 Transmission Booster PAC SF46EPA TB5 TB15 TB15 TB3 TB15 Group 2 Group 1 Group 40 TB7 TB7 TB3 TB3 TB2 51 OC TB3 51 OC CN41 CN40 CN41 CN40 OFF DipSW2 1 OFF DipSW2 1 Indoor unit ME R C ME R C ME R C 01 02 03 30 TB5 BC controller Main 52 TB02 BC controller Sub 80 BC controller Sub 94 TB02 TB02 BC controller Main 92 TB02 TB5 T...

Page 272: ... R C ME R C 01 02 03 30 TB5 BC controller Main 52 TB02 BC controller Sub 80 BC controller Sub 94 TB02 TB02 BC controller Main 92 TB02 TB5 TB5 TB2 Transmission Booster PAC SF46EPA TB5 ME R C 101 102 130 180 TB3 Group 2 Group 1 Group 21 TB7 TB7 TB7 TB3 51 OC TB3 91 OC TB3 96 OC CN41 CN40 CN41 CN40 CN41 CN40 ON DipSW2 1 ON DipSW2 1 ON DipSW2 1 ME R C ME R C Indoor unit ME R C ME R C PZ 52SF E 142 143...

Page 273: ...Group 1 Group 21 TB7 TB7 TB7 TB3 51 OC TB3 91 OC TB3 96 OC CN41 CN40 CN41 CN40 CN41 CN40 ON DipSW2 1 ON DipSW2 1 ON DipSW2 1 ME R C ME R C Indoor unit ME R C ME R C PZ 52SF E 142 143 144 145 195 41 42 43 44 45 TB5 TB5 LOSSNAY TB5 TB5 TB5 Group 33 Group 32 Group 31 Group 34 Group 35 ME R C 141 PURY PURY PURY PURY PURY CN41 CN40 000 CN41 CN40 NOTE It is not necessary to connect the M NET transmissio...

Page 274: ...ual piping length M x Quantity of bent Note5 Set DIP SW 4 6 to ON of BC controller in case of connected Indoor unit sized P100 P140 with 2 ports Note6 It is also possible to connect Indoor unit sized P100 P140 with 1 port set DIP SW 4 6 to OFF Note7 Individual indoor units grouped together to connect to the BC controller via one port cannot operate individually in heating and cooling modes at the ...

Page 275: ...doors down stream For example PEFY P63VML E PEFY P32VML E Total Indoor capacity P63 P32 P95 S T M N CMY R160 J1 Gas side IU CMY R160 J1 Liquid side BC controller Fig 3 1 2AA BC controller Main BC IU a IU C b H H h1 h1 IU P15 P80 P100 P250 CMY R160 J1 Joint IU CMY Y102S G Joint Max 3 sets for 1 port Total capacity P80 BC controller Sub BC BC controller Sub BC B c d IU f h3 D E CMY Y202 G2 CMY Y102L...

Page 276: ...16 ޓ L1 0 11 ޓ L2 0 12 ޓ L3 0 06 ޓ L4 0 024 ޓ 20 L1 Total length of ø19 05 high pressure pipe m L2 Total length of ø15 88 high pressure pipe m L3 Total length of ø12 7 liquid pipe m L4 Total length of ø9 52 liquid pipe m L5 Total length of ø6 35 liquid pipe m 0 0 3 0 5 2 0 0 2 l e d o m r o o d t u O 0 0 1 0 8 1 7 3 6 0 5 0 4 2 3 5 2 0 2 5 1 l e d o m r o o d n I Standard Usable Unit performance w...

Page 277: ...h pipe completely that are not in use and seal it Is the piping air tight Start YES YES YES NO NO NO NO YES YES YES NO NO Please contact your local distributor Are the existing pipes still connected with indoor units and the outdoor units excluding sealed branch pipes that are not in use Exisiting piping cannot be reused Use new piping If the piping is left disconnected there is a possibility of c...

Page 278: ... 2 P125 b ø12 7 3m 3 P15 c ø6 35 2m 4 P20 d ø6 35 3m Total length for each pipe size ø15 88 A 40m ø12 70 b 3m ø9 52 B a 10 5 15 m ø6 35 c d 2 3 5 m Therefore additional refrigerant charge 0 11 x 40 0 12 x 3 0 06 x 15 0 024 x 5 2 3 10 78 kg 10 8 kg Additional refrigerant charge kg High pressure pipe size Total length of ø 19 05 x 0 16 m x 0 16 kg m High pressure pipe size Total length of ø 15 88 x ...

Page 279: ...the outdoor unit may generate noise 3 Avoid the sites where strong winds blow 4 With strength to bear the weight of the unit 5 Drain flow from the unit is cared at heating mode 6 Enough space for installation and service as shown at 4 2 7 Avoid the sites where acidic solutions or chemical sprays sulfur series are used frequently 8 The unit should be secure from combustible gas oil steam chemical g...

Page 280: ...xceeds the wall height restriction 4 If there are obstacles at the upper part of the unit A Top view B Side view C When there is little space up to an obstruction When the height of the walls on the front back or on the sides H exceeds the wall height limit as defined below add the height that exceeds the height limit h to the figures that are marked with an asterisk Wall height limit Front Up to ...

Page 281: ...o sides must be left open As with the single installation add the height that exceeds the height limit h to the figures that are marked with If there is a wall at both the front and the rear of the unit install up to six units consecutively in the side direction and provide a space of 1000mm or more as inlet space passage space for each six units an asterisk Front Must be open 17 23 32 17 23 32 17...

Page 282: ... two corners and must not be attempt ed Use protective pads to keep the ropes from scratching the panels on the unit Products weighing more than 20 kg 45 LBS should not be carried alone Do not carry the product by the PP bands To avoid the risk of injury do not touch the heat exchanger fins Plastic bags may pose a risk of choking hazard to children Tear plastic bags into pieces before disposing of...

Page 283: ...of the unit leg Install the unit in such a way that the corner of the angle bracket at the base of the unit shown in the figure below is securely supported Install the anchor bolt in such a way that the top end of the anchor bolt do not stick out more than 30 mm 1 3 16 in This unit is not designed to be anchored with post installation type anchor bolts although by adding fixing brackets anchoring ...

Page 284: ...ke sure that the through hole at the base of the unit does not get blocked with the installation base When the pipes are routed at the bottom of the unit the base should be at least 100 mm 3 15 16 in in height The gaps around the edges of through holes for pipes and wires on the unit allow water or mice to enter the unit and damage its parts Close these gaps with filler plates This unit allows two...

Page 285: ... side install a filler plate between the fan guard and the outlet side snow food as shown in Figure A The filler plate provided accommodates the installation pitch of between 30 80 mm 1 3 16 3 5 32 in 5 When the unit is used in a cold region and the heating operation is continuously performed for a long time when the outside air temperature is below freezing install a heater to the unit base or ta...

Page 286: ...r refrigerant leakage Oxygen sensor or refrigerant sensor At 0 3m height from the floor Fresh air supply fan Indoor space Floor Fig 5 4 Fresh air supply and refrigerant shut off upon sensor action Note 1 Countermeasure 3 should be done in a proper way in which the fresh air supply shall be on whenever the leakage happens Note 2 In principle MITSUBISHI ELECTRIC requires proper piping design install...

Page 287: ...284 SYSTEM DESIGN ...

Page 288: ...285 CONTROLLER CONTROLLER 1 1 System component 286 1 2 Outdoor unit input output connector 288 1 3 Indoor unit E type input output connector 289 ...

Page 289: ...r Operation status of the compressor Error status PUHY CN3D CN3S CN3N CN51 PURY CN3D CN3S CN51 1 Table 1 1 1 SW4 4 OFF Compressor ON OFF Low noise mode 2 When SW4 4 on one outdoor unit in one refrigerant circuit system is set to ON 4 levels of on DEMAND 8 3 When SW4 4 on the two outdoor units in one refrigerant circuit system is set to ON 8 levels of on DEMAND 8 9 CN3D 1 3P Open Short circuit 6 Wh...

Page 290: ...regardless of Indoor units state Setting Dip Switch 1 4 1 9 OFF ON OFF 1 10 ON OFF OFF Auto ON Auto recovery All OFF 1 The Dip Switch setting should be carried out on every Indoor unit in the group 2 Outdoor unit s power supply should NOT be cut Otherwise power supply to case heater of the compressor would be cut too which may cause damage to the compressor 3 Above method can not be applied to the...

Page 291: ...ntact rating voltage 15VDC Contact rating current 0 1A Minimum applicable load 1mA at DC Contact rating voltage 15VDC Contact rating current 0 1A Minimum applicable load 1mA at DC 2 Low noise mode CN3D DipSW4 4 OFF X CN3D Preparations in the field Maximum cable length is 10m Adapter 2 Outdoor unit control board 2 3 1 X Relay The sound pressure level is reduced by controlling the maximum fan freque...

Page 292: ...Distant ON OFF switch L1 Status lamp L2 Error lamp X Relay a point of contact fixed DC1mA Y Z Relay L1 Status lamp Fan motor output SW1 5 OFF Thermostat ON SW1 5 ON L2 Cooling Dry status lamp L3 Heating status lamp X Y Z Relay Coil with fixed 12VDC a power consumption of 0 9W or less SW1 Distant Local switching SW2 ON OFF switch X Y Relay CN52 Indoor unit control board Power supply of relay Maximu...

Page 293: ... S JM B PURY RP YJM B HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN MEE10K014 New publication effective Feb 2011 Specifications subject to change without notice http Global MitsubishiElectric com ...

Reviews: