5. SOUND LEVELS
OUTDOOR UNITS
68
5. SOUND LEVELS
Measurement condition
PURY-RP200, 250, 300YJM-B(-BS)
Measurement
location
1m
1m
63
125
250
500
1k
2k
4k
8k
dB(A)
Standard
50/60Hz
65.0
63.5
61.0
56.0
53.0
48.5
45.0
42.5
59.0
Low noise mode 50/60Hz
61.0
59.5
49.0
44.5
41.5
38.5
39.5
37.5
50.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
63
125
250
500
1k
2k
4k
8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum
audible limit on
continuous noise
Stand 50/60Hz
Low
50/60Hz
Sound level of PURY-RP300YJM-B(-BS)
63
125
250
500
1k
2k
4k
8k
dB(A)
Standard
50/60Hz
62.5
61.0
58.5
53.0
50.0
45.5
39.0
36.0
56.0
Low noise mode 50/60Hz
56.5
48.5
46.0
39.0
38.5
32.5
33.0
25.5
44.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
63
125
250
500
1k
2k
4k
8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum
audible limit on
continuous noise
Stand 50/60Hz
Low
50/60Hz
Sound level of PURY-RP200YJM-B(-BS)
63
125
250
500
1k
2k
4k
8k
dB(A)
Standard
50/60Hz
59.0
62.0
60.0
54.0
50.5
46.0
41.0
35.0
57.0
Low noise mode 50/60Hz
58.0
53.5
44.0
39.0
36.5
32.5
31.0
24.5
44.0
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
63
125
250
500
1k
2k
4k
8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum
audible limit on
continuous noise
Stand 50/60Hz
Low
50/60Hz
Sound level of PURY-RP250YJM-B(-BS)