119
3. Cooling [Ceiling cassette (1-way flow type)]
INDOOR UNITS
3. Cooling [Ceiling cassette (1-way flow type)]
3-1. Cooling capacity with PUHY,PURY-RP200-250YJM
PMFY-P-VBM-E
CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
Model
Outdoor
Indoor air temp.
size
air temp.
21.5°C D.B.
23°C D.B.
25°C D.B.
27°C D.B.
28°C D.B.
30°C D.B.
32°C D.B.
(Rated kW)
15°C W.B.
16°C W.B.
18°C W.B.
19°C W.B.
20°C W.B.
22°C W.B.
24°C W.B.
°C D.B.
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
CA
SHC
20
(2.2)
20.0 2.1
1.8
2.2
1.9
2.3
1.9
2.4
2.0
2.5
2.0
2.6
2.0
2.8
1.9
22.5 2.1
1.8
2.2
1.9
2.3
1.9
2.4
2.0
2.5
2.0
2.6
2.0
2.8
1.9
25.0 2.1
1.8
2.2
1.9
2.3
1.9
2.4
2.0
2.4
2.0
2.6
2.0
2.7
1.9
27.5 2.1
1.8
2.1
1.9
2.3
1.9
2.3
2.0
2.4
2.0
2.5
1.9
2.7
1.9
30.0 2.0
1.8
2.1
1.9
2.2
1.8
2.3
2.0
2.3
2.0
2.5
1.9
2.6
1.9
32.5 2.0
1.8
2.1
1.8
2.2
1.8
2.2
2.0
2.3
1.9
2.4
1.9
2.6
1.9
35.0 2.0
1.8
2.0
1.8
2.1
1.8
2.2
1.9
2.3
1.9
2.4
1.9
2.5
1.9
37.5 1.9
1.7
2.0
1.8
2.1
1.8
2.2
1.9
2.2
1.9
2.3
1.9
2.5
1.8
40.0 1.9
1.7
2.0
1.8
2.1
1.8
2.1
1.9
2.2
1.9
2.3
1.9
2.4
1.8
43.0 1.8
1.7
1.9
1.8
2.0
1.7
2.1
1.9
2.1
1.9
2.2
1.8
2.3
1.8
25
(2.8)
20.0 2.7
2.2
2.8
2.3
2.9
2.3
3.0
2.5
3.1
2.4
3.3
2.4
3.5
2.4
22.5 2.7
2.2
2.8
2.3
2.9
2.3
3.0
2.5
3.1
2.4
3.3
2.4
3.5
2.4
25.0 2.7
2.2
2.8
2.3
2.9
2.3
3.0
2.4
3.1
2.4
3.3
2.4
3.5
2.4
27.5 2.7
2.2
2.7
2.3
2.9
2.3
3.0
2.4
3.0
2.4
3.2
2.4
3.4
2.3
30.0 2.6
2.2
2.7
2.3
2.8
2.2
2.9
2.4
3.0
2.4
3.2
2.3
3.3
2.3
32.5 2.6
2.2
2.6
2.3
2.8
2.2
2.9
2.4
2.9
2.4
3.1
2.3
3.3
2.3
35.0 2.5
2.2
2.6
2.2
2.7
2.2
2.8
2.4
2.9
2.3
3.0
2.3
3.2
2.3
37.5 2.5
2.1
2.5
2.2
2.7
2.2
2.8
2.3
2.8
2.3
3.0
2.3
3.1
2.2
40.0 2.4
2.1
2.5
2.2
2.6
2.2
2.7
2.3
2.8
2.3
2.9
2.3
3.1
2.2
43.0 2.4
2.1
2.4
2.2
2.6
2.1
2.6
2.3
2.7
2.3
2.8
2.2
3.0
2.2
32
(3.6)
20.0 3.4
2.6
3.5
2.6
3.8
2.6
3.9
2.8
4.0
2.8
4.3
2.7
4.6
2.7
22.5 3.4
2.6
3.5
2.6
3.8
2.6
3.9
2.8
4.0
2.8
4.3
2.7
4.6
2.7
25.0 3.4
2.6
3.5
2.6
3.8
2.6
3.9
2.8
4.0
2.8
4.2
2.7
4.5
2.7
27.5 3.4
2.6
3.5
2.6
3.7
2.6
3.8
2.7
3.9
2.7
4.1
2.7
4.4
2.6
30.0 3.3
2.5
3.4
2.6
3.6
2.6
3.7
2.7
3.8
2.7
4.1
2.7
4.3
2.6
32.5 3.3
2.5
3.4
2.6
3.6
2.5
3.7
2.7
3.8
2.7
4.0
2.6
4.2
2.6
35.0 3.2
2.5
3.3
2.5
3.5
2.5
3.6
2.7
3.7
2.6
3.9
2.6
4.1
2.6
37.5 3.2
2.4
3.3
2.5
3.4
2.5
3.5
2.6
3.6
2.6
3.8
2.6
4.0
2.5
40.0 3.1
2.4
3.2
2.5
3.4
2.5
3.5
2.6
3.6
2.6
3.7
2.5
3.9
2.5
43.0 3.0
2.4
3.1
2.4
3.3
2.4
3.4
2.6
3.5
2.5
3.6
2.5
3.8
2.5
40
(4.5)
20.0 4.3
3.1
4.4
3.2
4.7
3.2
4.9
3.4
5.0
3.4
5.3
3.3
5.7
3.3
22.5 4.3
3.1
4.4
3.2
4.7
3.2
4.9
3.4
5.0
3.4
5.3
3.3
5.7
3.3
25.0 4.3
3.1
4.4
3.2
4.7
3.2
4.9
3.4
5.0
3.4
5.3
3.3
5.6
3.3
27.5 4.3
3.1
4.4
3.2
4.6
3.2
4.8
3.4
4.9
3.3
5.2
3.3
5.5
3.2
30.0 4.2
3.1
4.3
3.2
4.6
3.1
4.7
3.3
4.8
3.3
5.1
3.2
5.4
3.2
32.5 4.1
3.1
4.2
3.1
4.5
3.1
4.6
3.3
4.7
3.3
5.0
3.2
5.3
3.2
35.0 4.0
3.0
4.1
3.1
4.4
3.1
4.5
3.2
4.6
3.2
4.9
3.2
5.2
3.1
37.5 4.0
3.0
4.1
3.1
4.3
3.0
4.4
3.2
4.5
3.2
4.8
3.1
5.0
3.1
40.0 3.9
2.9
4.0
3.0
4.2
3.0
4.3
3.2
4.4
3.1
4.7
3.1
4.9
3.0
43.0 3.8
2.9
3.9
3.0
4.1
2.9
4.2
3.1
4.3
3.1
4.5
3.0
4.8
3.0
kcal/h=kW x 860 , BTU/h = kW x 3,412
Summary of Contents for PUHY-RP-Y(S)JM-B
Page 1: ...DATA BOOK AIR CONDITIONERS MODEL PUHY RP Y S JM B PURY RP YJM B ...
Page 3: ......
Page 63: ...60 OUTDOOR UNITS ...
Page 191: ...188 INDOOR UNITS ...
Page 243: ...240 SYSTEM DESIGN ...
Page 287: ...284 SYSTEM DESIGN ...