71
SW2 setting
Display detail
Explanation for display
Unit
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Outdoor unit setting information
Indoor pipe temperature / Liquid
(TH2(1))
Indoor 1
– 39~88
Code
display
:
– 39~88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Indoor room temperature (TH1)
8~39
Setting details
• The tens digit (Total display for applied setting)
• The ones digit
H·P / Cooling only
Single phase / Three phase
Display details
0 : H·P 1 : Cooling only
0 : Single phase 2 : Three phase
Setting details
Defrosting switch
Display details
0 : Normal 1 : For high humidity
(Example) When heat pump,three phase and
defrosting (normal) are set up, “20” is
displayed.
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Indoor pipe temperature / Cond. / Eva.
(TH5(1))
Indoor 1
– 39~88
– 39~88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
:
– 39~88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
– 39~88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
:
:
:
8~39
Indoor pipe temperature / Liquid
(TH2(2))
Indoor 2
– 39~88
Indoor pipe temperature / Cond. / Eva.
(TH5(2))
Indoor 2
– 39~88
1
ON
2 3 4 5 6
:
Indoor setting temperature
17~30
17~30
Code
0
1
2
3
4
5
6
7
Indoor unit
Status of control
Outdoor unit
Normal
Hot adjustment
Defrosting
—
Heater ON
Anti-freezing
Over-rise prevention
Compressor OFF
Normal
Hot adjustment
Defrosting
—
Heater ON
Anti-freezing
Over-rise prevention
Compressor OFF
Indoor control status
Outdoor control status
This code is referred to check the unit’s operating status.
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Code
display