78
•When controlling each unit (unit 01 to 04) individually
➜
Select "01" to "04."
•When controlling all the units (unit 01 to 04) at once
➜
Select "07."
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
CHECK
RESET
SET
CLOCK
E
C
,
D
F
A
B
[Operating instructions] (entering settings with a wireless remote controller)
Changing the power voltage setting
Be sure change the power voltage setting depending on the voltage used.
1
Go to the function select mode
Press the button
F
twice continuously.
(Start this operation from the status of remote controller display turned off.)
is lighted and “00” blinks.
Press The temp button
C
once to set “50”. Direct the wireless remote
controller toward the receiver of the indoor unit and press the button
A
.
2
Setting the unit number
Press the temp button
C
and
D
to set the unit number “00”. Direct the
wireless remote controller toward the receiver of the indoor unit and press the
button
B
. (The display changes at each press: 01 to 50)
3
Selecting a mode
Enter 04 to change the power voltage setting using the
C
and
D
buttons.
Direct the wireless remote controller toward the receiver of the indoor unit and
press the button
A
.
Current setting number:
1 = 1 beep (one second)
2 = 2 beeps (one second each)
3 = 3 beeps (one second each)
4
Selecting the setting number
Use the
C
and
D
buttons to change the power voltage setting to 01
(240V).
Direct the wireless remote controller toward the sensor of the indoor unit and
press the button
A
.
CHECK
h
CHECK
min
h
h
CHECK
00
1
CHECK
00
2
CHECK
04
3
CHECK
01
4
Flow of function selection procedure
The flow of the function selection procedure is shown below. This example shows how to turn
off the function that raises the set temperature by 4 degrees during HEAT operation .
The procedure is given after the flow chart.
1
Check the function selection setting.
2
Switch to function selection mode.
(Enter address "50" in troubleshooting
mode, then press the HOUR button.)
Troubleshooting mode is the mode entered when
you press the INSPECT button twice to display
"INSPECT".
3
Specify unit No. "01" (since the function applies to unit 01).
(Set address "01" while still in troubleshooting mode, then press the MINUTE button.)
Note: You can't specify the refrigerant address.
4
Select mode No. "24" (function that raises set temperature by 4 degrees during HEAT operation).
(Set address "24" while still in troubleshooting mode, then press the HOUR button.)
6
Finished
8
End function selection mode.
(End troubleshooting mode.)
YES
NO
Note: When you switch to function selection mode
on the wireless remote controller's operation
area, the unit ends function selection mode
automatically if nothing is input for 10 minutes
or longer.
5
Select setting No. "02" (OFF).
(Set address "02" while still in troubleshooting mode, then press the HOUR button.)
Change
unit No.
YES
NO
7
Wireless remote controller type