75
SW2 setting
Display detail
Explanation for display
Unit
Replacement operation
W
If replacement operation is conducted
even once, “1” is displayed.
If replacement operation time is less
than 2 hrs. “0” is displayed.
1
ON
2 3 4 5 6
–
1: Conducted.
0: Not yet.
Compressor frequency control
1
ON
2 3 4 5 6
Code
display
This code is referred to check the unit’s operating status.
FAN Control
1
ON
2 3 4 5 6
Code
display
This code is referred to check the unit’s operating status.
Code
1
2
Compressor frequency control
Primary current restriction control
Secondary current restriction control
• Tens digit
Code
1
2
4
8
Compressor frequency control
Discharging temperature over-rise prevention control
Condensing temperature over-rise prevention control
Frozen prevention control
Heat sink temperature over-rise prevention control
• Ones digit
(Example)
In the following cases(
1
to
3
), the code will
be displayed as shown in the figure.
1
Primary current restriction control
2
Condensing temperature over-rise prevention control
3
Heat sink temperature over-rise prevention control
Heat sink temperature over-rise
Correction value (0 to +2 ) of FAN
step for this control will be displayed.
• Ones digit
Code
- or
0 to 2
Code
0 to 2
Condensing temperature over-rise
Correction value (-1 to +2 ) of FAN
step for this control will be displayed.
“-“ will be displayed in case the
correction value is -1.
• Tens digit
(Example)
In case of
1
and
2
, correction values of fan
step are displayed as shown in the figure.
1
The correction value of fan step for the
condensing temperature over-rise
prevention control is +1.
2
The correction value of fan step for the
heat sink temperature over-rise prevention
control is +2.
1
ON
2 3 4 5 6
Normal
Overvoltage error
Undervoltage error
T phase interruption error
Abnormal power synchronous signal
PFC error
(Overvoltage / Undervoltage / Overcurrent)
W
Display examples for multiple errors:
Overvoltage (01) + Undervoltage (02) = 03
Undervoltage (02) + Power-sync signal error (08) = 0A
T phase interruption (04) + PFC error (10) = 14
Power circuit board
Controller circuit board
Controller circuit board
Power circuit board
Power circuit board
—
Description
Detection point
Display
00
01
02
04
08
10
U9 Error status during the Error
postponement period
Code
display
OCT04A-3.qxp 04.9.29 9:16 AM Page 75