80
3
Setting the unit numbers
Set “00” as the unit number when setting functions from Table 2.
When setting functions from Table 3:
- When setting functions for an indoor unit in an independent system, set the unit number to 01.
- When setting functions for a simultaneous-Twin Triple indoor unit system, assign unit numbers from 01 to 03 each indoor unit.
- When setting the same functions for an entire simultaneous Twin Triple-indoor unit system, assign “AL” as the unit number.
5
Selecting the mode number
Selecting from Table 2 and Table 3.
6
Selecting the setting number
Selecting from Table 2 and Table 3.
w
1 Horizontal vane First setting: The angle of the vane is set to standard.
w
2 Horizontal vane Second setting: The angle of the vane is finely changed as a measure against smudging.
Function
Settings
Mode No. Setting No. Check
Remarks
Filter sign
Fan speed
No. of air outlets
Installed options (high-
performance filter)
Horizontal vane
setting
Energy saving air
flow (Heating mode)
Swing
Set temperature in
heating mode 4deg-up
Fan speed when the
heating thermostat is OFF
Fan speed when the
cooling thermostat is OFF
Detection of abnormality
(P8) of the pipe temperature
100Hr
2500Hr
No filter sign indicator
Quiet
Standard
High ceiling
4 directions
3 directions
2 directions
Not supported
Supported
No vanes
Equipped with vane (No.1 set)
Equipped with vane (No.2 set)
Disabled
Enabled
Not available
Available
Available
Not available
Extra low
Low
Setting fan speed
Setting fan speed
Stop
Available
Not available
1
2
3
1
2
3
1
2
3
1
2
1
2
3
1
2
1
2
1
2
1
2
3
1
2
1
2
07
08
09
10
11
12
23
24
25
27
28
standard
High ceiling
1
High ceiling
2
PLA-RP·AA type
Refer to
w
1.
Refer to
w
2.
Table 3. Itemised functions of the indoor unit (select unit numbers 01 to 03 or AL [Wired remote controller] / 07 Wireless remote controller])
Function
Settings
Mode No. Setting No. Check
Remarks
Power failure
automatic recovery
Indoor temperature
detecting
LOSSNAY
connectivity
Power voltage
Auto operating
mode
Frost prevention
temperature
Humidifier control
Change of
defrosting control
Not available
Available
Indoor unit operating average
Set by indoor unit's remote controller
Remote controller's internal sensor
Not supported
Supported (indoor unit in not equipped with outdoor-air intake)
Supported (indoor unit in equipped with outdoor-air intake)
240V
220V, 230V
Auto energy-saving operation ON
Auto energy-saving operation OFF
2
:
3
:
When the compressor operates, the humidifier also operates.
When the fan operates, the humidifier also operates.
Standard
High humidity region
1
2
1
2
3
1
2
3
1
2
1
2
1
2
1
2
1
2
01
02
03
04
05
15
16
17
Approx. 4-minute wait-period
after power is restored.
Table 2. Itemised functions of the entire refrigerant system (select unit number 00)
OCT04A-3.qxp 04.9.29 9:16 AM Page 80