102
12-3. Error code
list.
Error codes are explained on the below tables.
w
1. When a communication error is occurring, the display of remote controller may not match that of the optional parts
“A control service kit (PAC-SK52ST)”, or may not come on at all.
w
2. Beeping sounds come out of the signal receiving section of the wireless remote controller only when the
malfunction-diagnosis is conducted by using the wireless remote controller.
2
Outdoor unit error
Error code
F3
F5
F9
U1
U2
U3
U4
U5
U7
U9
U6
UF
UH
UL
UP
Short 2 beeps (0.4 sec.) x 1
Short 2 beeps (0.4 sec.) x 1
Short 2 beeps (0.4 sec.) x 1
Short 2 beeps (0.4 sec.) x 1
Short 2 beeps (0.4 sec.) x 1
Short 2 beeps (0.4 sec.) x 1
Short 2 beeps (0.4 sec.) x 1
Short 2 beeps (0.4 sec.) x 1
Short 2 beeps (0.4 sec.) x 1
Short 2 beeps (0.4 sec.) x 1
Short 2 beeps (0.4 sec.) x 1
Short 2 beeps (0.4 sec.) x 1
Short 2 beeps (0.4 sec.) x 1
Short 2 beeps (0.4 sec.) x 1
Short 2 beeps (0.4 sec.) x 1
5202
5201
4119
1302
1102
5104
5105
5107
5106
5110
4230
1502
4220
4250
4100
5300
1300
4210
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
P109
P109
P109
P111
P111
P112
P112
P112
P112
P113
P112
P113
P113
P113
P113
Connector(63L) is open.
<RP4~RP6 only>
Connector(63H) is open.
2 or more connectors are open.
<RP4~RP6 only>
Abnormal high pressure (63H worked)
Abnormal discharging temperature
Open/short circuit of discharging thermistor (TH4)
Open/short circuit of outdoor pipe temperature thermistor/Liquid (TH3)
Open/short circuit of outdoor pipe temperature thermistor/Cond./Eva. (TH6)
Open/short circuit of outside temperature thermistor (TH7)
Open/short circuit of heat sink thermistor (TH8)
Abnormal temperature of heat sink
Abnormality such as overvoltage or voltage shortage
Abnormality of power module
Current sensor error
Abnormal low pressure (63L worked)
<RP4~RP6 only>
Compressor overcurrent interruption
Beep output
High prior
remote controller
Unit which
detects error
Error details
Inspection
method and
troubleshooting
Display of remote
controller or A
control service tool
Abnormality of super heat due to low discharge temperature
(RP3 only)
Compressor overcurrent interruption
(When compressor locked)
Error code
P1
P2
P4
P5
P6
P8
P9
Beep(one sec.) x 1
Beep(one sec.) x 2
Beep(one sec.) x 4
Beep(one sec.) x 5
Beep(one sec.) x 6
Beep(one sec.) x 8
Beep(one sec.) x 2
5101
5102
2503
2500, 2502
1503
1504
1110
5103
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
P106
P106
P106
P106
P107
P107
P108
Abnormality of room temperature thermistor (TH1)
Abnormality of pipe temperature thermistor/Liquid (TH2)
Abnormality of drain sensor (DS)
Drain overflow protection
Freezing protection in cooling operation
Overheating protection in heating operation
Abnormality of pipe temperature
Abnormality of pipe temperature thermistor/Cond./Eva
Beep output
High prior
remote controller
Unit which
detects error
Error details
Inspection
method and
troubleshooting
Display of remote
controller or A
control service tool
1
Indoor unit error