8-6. AUTO operation
1. Initial operation mode
Control modes
Remarks
Control details
When a operation mode turns into AUTO operation;
1
HEAT mode will be operated if intake temperature < set temperature
2
COOL mode will be operated if intake temperature
]
set temperature
2. Change of
operation mode
1
HEAT mode will turn into COOL mode when intake temperature
]
set tempe 2deg
and 15 minutes have passed since the HEAT operation started.
2
COOL mode will turn into HEAT mode when intake temperature
[
set temperature – 2deg
and 15 minutes have passed since the COOL operation started.
3. COOL mode
Same controls as those of COOL operation.
Same controls as those of HEAT and defrosting operation.
4. HEAT mode
8-7. Inverter control
1. Basic control
Control modes
Control details
1-1. Frequency setting
COOL
HEAT
COOL
HEAT
COOL
HEAT
COOL
HEAT
COOL
HEAT
COOL
HEAT
COOL
HEAT
PUHZ-
RP1.6VHA
PUHZ-
RP2VHA
PUHZ-
RP2.5VHA
PUHZ-
RP3VHA
PUHZ-
RP4VHA
PUHZ-
RP5VHA
PUHZ-
RP6VHA
22
22
30
30
32
32
32
32
30
30
30
30
30
30
49
52
66
74
47
51
55
61
49
55
68
68
85
80
66
77
82
106
54
67
70
87
62
81
86
87
96
97
-
-
74
77
47
51
59
58
53
55
70
68
82
77
-
-
85
106
55
67
69
85
69
78
85
87
96
94
49
57
74
61
-
-
-
-
-
-
-
-
-
-
76
80
85
106
-
-
-
-
-
-
-
-
-
-
-
-
-
-
46
51
55
58
54
55
-
-
-
-
-
-
-
-
54
67
67
84
67
79
-
-
-
-
53
62
67
82
51
57
55
65
54
54
59
71
79
79
70
80
85
106
58
67
72
92
66
74
78
87
96
92
-
-
-
-
-
-
59
57
53
53
72
63
76
70
-
-
-
-
-
-
72
84
65
74
88
82
96
85
-
-
-
-
51
57
55
65
54
54
-
-
-
-
-
-
-
-
58
67
72
92
66
74
-
-
-
-
min
Rated max
max
max
max
max
max
max
Rated
Rated
Rated
Rated
Rated
Rated
PLA-RP•AA PCA-RP•GA PKA-RP•GAL PKA-RP•FAL PEA-RP•EA PEAD-RP•EA PEAD-RP•GA
1-2. 1.2 V/F pattern
W
1. Actual performance does not exactly match the V/F line on both graphic charts due to
the air-conditioning load because the inverter control is based on vector.
W
2. Actual values of V/F will be almost the same as the V/F line on the graphic chart because
the inverter control is based on voltage and frequency. However, they may not exactly
match the V/F line on the graphic chart because voltage correction control makes an effect
on the performance.
250
200
150
100
50
0
0
50
Operating frequency (Hz)
PUHZ-RP2.5, 3VHA
V
oltage (V)
100
150
250
200
150
100
50
0
0
50
Operating frequency (Hz)
PUHZ-RP1.6, 2VHA
V
oltage (V)
100
150
W
1
W
1
W
2
250
200
150
100
50
0
0
50
Operating frequency (Hz)
PUHZ-RP4-6VHA
V
oltage (V)
100
150
OCT04A-2.qxp 04.9.29 9:15 AM Page 59