2. INSTALLATION
(2) Installation of two or more servo amplifiers
Leave a large clearance between the top of the servo amplifier and the internal surface of the control
box, and install a fan to prevent the internal temperature of the control box from exceeding the
environmental conditions.
Control box
100mm
(4.0 in.)
or more
10mm
(0.4 in.)
or more
1mm
(0.04 in.)
or more
MITSUBISHI
OPEN
CN1A
CN1B
CNP1
CNP2
CNP3
MELSERVO
MITSUBISHI
OPEN
CN1A
CN1B
CNP1
CNP2
CNP3
MELSERVO
10mm
(0.4 in.)
or more
40mm
(1.6 in.)
or more
(3) Others
Install the servo amplifier on a perpendicular wall in the correct vertical direction.
2.3 Keep out foreign materials
(1) When installing the unit in a control box, prevent drill chips and wire fragments from entering the
servo amplifier.
(2) Prevent oil, water, metallic dust, etc. from entering the servo amplifier through openings in the control
box or a fan installed on the ceiling.
(3) When installing the control box in a place where there are much toxic gas, dirt and dust, conduct an
air purge (force clean air into the control box from outside to make the internal pressure higher than
the external pressure) to prevent such materials from entering the control box.
Summary of Contents for MR-J2-03B5
Page 11: ...A 10 MEMO ...
Page 15: ...4 MEMO ...
Page 21: ...1 6 1 FUNCTIONS AND CONFIGURATION MEMO ...
Page 27: ...2 6 2 INSTALLATION MEMO ...
Page 61: ...5 8 5 PARAMETERS MEMO ...
Page 73: ...7 2 7 INSPECTION MEMO ...
Page 81: ...8 8 8 TROUBLESHOOTING MEMO ...
Page 87: ...9 6 9 OUTLINE DIMENSION DRAWINGS MEMO ...
Page 91: ...10 4 10 CHARACTERISTICS MEMO ...
Page 111: ...11 20 11 OPTIONS AND AUXILIARY EQUIPMENT MEMO ...