2 INSTALLATION
2.1 Installation direction and clearances
17
2
2.1
Installation direction and clearances
Installation
Make sure to connect a drive unit to the right side of a power regeneration converter unit. Since the units require a cooling
mechanism outside the cabinet, an opening must be provided in each mounting surface as shown below.
The TE2-1 terminal block of the drive unit and the TE2 terminal block of the power regeneration converter unit are connected
using a bus bar. Thus, remove the supplied cover on the right side of the power regeneration converter unit.
■
Clearance between sets of combined power regeneration converter units and drive units
mounted side by side
*1 A clearance of at least 120 mm is required. Leave a clearance, taking into consideration the flexibility of the cable.
CAUTION
• The equipment must be installed in the specified direction. Otherwise, it may cause a malfunction.
• Maintain specified clearances between the converter unit/drive unit and the inner surfaces of a control cabinet or other equipment. Otherwise, it may cause a
malfunction.
Cooling
fan
exhaust
80 mm
or more
Side
Front
100 mm
or more
120 mm
or more
*1
Drive unit
Converter unit
Drive unit
Converter unit
30 mm
Top
Bottom