58
7 WIRING
7.2 Wiring Inside and Outside the Panel
7.2
Wiring Inside and Outside the Panel
Wiring inside
Run power lines, servo amplifier drive wires, and communication cables so that they do not cross each other.
Noise interference that is generated by cables that cross each other may cause malfunctions.
Surge suppressors are an effective way to filter out surge noise that is generated from no fuse breakers (NFB),
electromagnetic contactors (MC), relays (RA), solenoid valves, and induction motors.
Refer to the section to follow for surge killers.
Page 59 Attaching surge killers to control equipment
Outside the panel
To pull the power line and communication cable out of the panel, make two pullout holes away from each other and pull the
cables through.
Putting both cables through the same pullout hole will increase noise interference.
Keep the power line and communication cable inside the duct at least 100mm away from each other.
If that is not possible, the use of a metal separator inside the duct can reduce noise interference.
NFB
MC
PLC
MC
RA
RA
Terminal block
Crossing power lines and
communication cables
GOT connection cable
PLC I/O wire
Drive control wire
NFB
MC
PLC
MC
RA
RA
Terminal block
Uncrossed power lines and
communication cables
GOT connection cable
PLC I/O wire
Drive control wire
Power
cable
Power
cable
Power line
Connection
cable
Pullout hole
Pullout hole
Connection
cable
Power line
100mm or more
Separator
Signal line
Power line
Power line
Wiring duct
Signal line
Summary of Contents for GOT SIMPLE Series
Page 1: ...GOT SIMPLE Series User s Manual GS21 model ...
Page 2: ......
Page 20: ...18 MEMO ...
Page 24: ...22 1 OVERVIEW 1 1 Features MEMO ...
Page 34: ...32 3 SPECIFICATIONS 3 4 GOT Connector Specifications MEMO ...
Page 40: ...38 4 PART NAME 4 3 Bottom MEMO ...
Page 62: ...60 7 WIRING 7 2 Wiring Inside and Outside the Panel MEMO ...
Page 76: ...74 10 LANGUAGE SETTING LANGUAGE 10 1 Display language setting MEMO ...
Page 130: ...128 12 DISPLAY AND OPERATION SETTINGS GOT SET UP 12 7 IP Filter Setting MEMO ...
Page 160: ...158 14 CLOCK SETTINGS TIME SETTING AND DISPLAY 14 1 Time Setting and Display MEMO ...
Page 268: ...266 16 GOT SELF CHECK DEBUG 16 3 FX3U ENET ADP Communication Setting Function MEMO ...
Page 274: ...272 17 MAINTENANCE 17 3 Clean MEMO ...
Page 280: ...278 20 ERROR MESSAGE LIST MEMO ...
Page 296: ...294 22 TROUBLESHOOTING 22 1 GOT Restoration Sheets MEMO ...
Page 298: ...296 23 CONNECTION MEMO ...
Page 305: ...24 APPENDIX 24 1 External Dimensions 303 24 MEMO ...
Page 309: ......