5 EMC DIRECTIVE
5.2 EMC Directive Requirements
41
5
■
Treatment of the power cable and the ground cable
Twist the ground cable led from the ground point with the power cable.
Twisting with the ground cable relieves more noise from the power cable to the ground.
When a noise filter is installed to the power cable, twisting the power cable and the ground cable may not be required.
Installing a noise filter (power supply line filter)
A noise filter is a part to effectively reduce conducted noise.
Except some models, installation of a noise filter to the power supply lines is not necessary. However, installing the noise filter
can reduce conducted noise.
The noise filter is effective to reduce conducted noise in the band of 10 MHz or less.
Use a noise filter equivalent to the following noise filters (double
π
-type filters).
Precautions
The following shows the precautions for installing a noise filter.
■
Prohibition of bundling cables
Do not bundle the input and output cables of the noise filter.
Bundling the cables inducts the noise from the output-side cable into the input-side cable where noise has been eliminated by
the noise filter.
■
Grounding the noise filter
Connect the ground terminal of the noise filter to the control panel with a short cable as much as possible (approximately 10
cm).
Model
Manufacturer
Rated current
Rated voltage
FN343-3/05
SCHAFFNER
3A
250V
FN660-6/06
SCHAFFNER
6A
RSHN-2003
TDK
3A
Input side
(power supply side)
Output side
(device side)
Filter
Wire the input and output cables separately.
Filter
Input side
(power supply side)
Induction
Output side
(device side)
Bundling the input and output cables inducts noise.
Bundling
Summary of Contents for GOT SIMPLE Series
Page 1: ...GOT SIMPLE Series User s Manual GS21 model ...
Page 2: ......
Page 20: ...18 MEMO ...
Page 24: ...22 1 OVERVIEW 1 1 Features MEMO ...
Page 34: ...32 3 SPECIFICATIONS 3 4 GOT Connector Specifications MEMO ...
Page 40: ...38 4 PART NAME 4 3 Bottom MEMO ...
Page 62: ...60 7 WIRING 7 2 Wiring Inside and Outside the Panel MEMO ...
Page 76: ...74 10 LANGUAGE SETTING LANGUAGE 10 1 Display language setting MEMO ...
Page 130: ...128 12 DISPLAY AND OPERATION SETTINGS GOT SET UP 12 7 IP Filter Setting MEMO ...
Page 160: ...158 14 CLOCK SETTINGS TIME SETTING AND DISPLAY 14 1 Time Setting and Display MEMO ...
Page 268: ...266 16 GOT SELF CHECK DEBUG 16 3 FX3U ENET ADP Communication Setting Function MEMO ...
Page 274: ...272 17 MAINTENANCE 17 3 Clean MEMO ...
Page 280: ...278 20 ERROR MESSAGE LIST MEMO ...
Page 296: ...294 22 TROUBLESHOOTING 22 1 GOT Restoration Sheets MEMO ...
Page 298: ...296 23 CONNECTION MEMO ...
Page 305: ...24 APPENDIX 24 1 External Dimensions 303 24 MEMO ...
Page 309: ......